Plan Review Details - Permit 20031049
Plan Review Stops For Permit 20031049
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-06-05 Cont ID  
Sent By jpearson Date 2020-06-05 Time 11:42 Rev Time 0.00
Received By jpearson Date 2020-06-03 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-05-12 Cont ID  
Sent By jpearson Date 2020-05-12 Time 15:26 Rev Time 0.00
Received By jpearson Date 2020-05-12 Time 13:02 Sent To  
Notes
2020-05-12 15:26:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONE OF THE PLAN SHEETS APPEARS TO HAVE BEEN DELETED.
 THE DRAWING IN THE PLAN FOLDER DOES NOT SHOW ANY
 ELECTRICAL DETAILS. PROVIDE CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-17 Cont ID  
Sent By jpearson Date 2020-04-17 Time 08:56 Rev Time 0.00
Received By jpearson Date 2020-04-17 Time 08:56 Sent To  
Notes
2020-04-17 09:06:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. TWO PLAN SHEETS HAVE BEEN SUPPLIED, BUT THEY HAVE
 THE SAME SHEET NUMBER E-1. THESE SHOULD BE NAMED
 DIFFERENTLY. PROVIDE CORRECTION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By jpearson Date 2020-03-25 Time 08:07 Rev Time 0.00
Received By jpearson Date 2020-03-25 Time 08:05 Sent To I
Notes
2020-03-25 08:05:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. THE PRINTED SIGNATURE/SEAL
 IS NOT ACCEPTABLE, THIS MUST BE AN ORIGINAL
 SIGNATURE/SEAL. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 FOR RESUBMITTAL:
  
 PLEASE PAY ANY BALANCE DUE ONLINE SO YOUR PERMIT CAN BE
 EMAILED TO YOU.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), OR IF THE DESIGN
 PROFESSIONAL HAS A DIGITAL SIGNATURE, AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-06-05 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-15 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-12 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-27 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-21 Cont ID  
Sent By lmarchan Date 2020-04-21 Time 07:30 Rev Time 0.00
Received By lmarchan Date 2020-04-08 Time 16:54 Sent To  
Notes
2020-04-16 16:55:07CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-20 Time 16:03 Sent To  
Notes
2020-03-24 15:00:04TO ELECTRICAL
2020-03-20 16:03:37ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-05 Cont ID  
Sent By jpearson Date 2020-06-05 Time 11:40 Rev Time 0.00
Received By jpearson Date 2020-06-05 Time 11:40 Sent To  
Notes
2020-06-05 11:42:08NOTIFIED ENGINEER RONALD LEVINSON BY EMAIL THAT
 SELF-CERTIFIED SIGNATURES ARE NOT ACCEPTABLE PER FBPE.
 PER BUILDING OFFICIAL, THIS REVIEW HAS BEEN PASSED
 BECUASE THERE ARE NO CODE VIOLATIONS. ANY FUTURE
 SUBMITTALS WILL REQUIRE THE PROPER TYPE OF SIGNATURE.
 WPB FBC 105.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-12 Cont ID  
Sent By jpearson Date 2020-05-12 Time 15:35 Rev Time 0.00
Received By jpearson Date 2020-05-12 Time 15:35 Sent To  
Notes
2020-05-12 15:35:40PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-17 Cont ID  
Sent By jpearson Date 2020-04-17 Time 08:57 Rev Time 0.00
Received By jpearson Date 2020-04-17 Time 08:57 Sent To  
Notes
2020-04-17 08:57:44PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop Z ZONING
Rev No 4 Status P Date 2020-05-19 Cont ID  
Sent By llouie Date 2020-05-19 Time   Rev Time 0.00
Received By llouie Date 2020-05-19 Time   Sent To  
Notes
2020-05-19 11:58:32ZONING APPROVED WITH THE FOLLOWING NOTE AND PROVISO:
  
 1.) SEE PLAN AND RISER NOTES COMMENT #13 AND #14 IN
 PLAN(S).
  
 2.) ALL NEW LIGHT POLE FIXTURES SHALL BE PLACED AT
 LEAST 5 FT. FROM THE PROPERTY LINES PER ZLDR
 S.94-145(2).
  
  
 NOTES:
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK?D BY AVANN AND VNOEL).
  
 * CROSS REFERENCE: #20021029 (BUILDING FACADE
 RENOVATION AND NEW COVERED ENTRY @ 420 CLAREMORE
 DRIVE.) AND #20031047 (LANDSCAPING).
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-05-04 Cont ID  
Sent By llouie Date 2020-05-04 Time   Rev Time 0.00
Received By llouie Date 2020-05-04 Time   Sent To  
Notes
2020-05-04 14:04:00** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DISTANCE FOR ALL NEW LIGHT FIXTURES
 FROM THE PROPERTY LINES. THE LIGHT FIXTURES MUST BE
 PLACED AT LEAST 5 FT. FROM THE SIDE PROPERTY LINES.
 [ZLDR S.94-145(2)] [3/24/2020 AND 4/21/2020]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK?D BY AVANN AND VNOEL).
  
 * CROSS REFERENCE: #20021029 (BUILDING FA?ADE
 RENOVATION AND NEW COVERED ENTRY @ 420 CLAREMORE
 DRIVE.) AND #20031047 (LANDSCAPING).
  
 * SEPARATE PERMIT REQUIRED FOR: PARKING AREA.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-04-21 Cont ID  
Sent By llouie Date 2020-04-21 Time   Rev Time 0.00
Received By llouie Date 2020-04-21 Time   Sent To  
Notes
2020-04-21 07:18:59** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DISTANCE FOR ALL NEW LIGHT FIXTURES
 FROM THE PROPERTY LINES. THE LIGHT FIXTURES MUST BE
 PLACED AT LEAST 5 FT. FROM THE PROPERTY LINES. [ZLDR
 S.94-145(2)] [3/24/202 REPEAT COMMENT]
  
 2.) APPROVAL OF THIS PERMIT IS CONTINGENT UPON THE
 APPROVAL OF PERMIT #20021029 (BUILDING FACADE
 RENOVATION AND NEW COVERED ENTRY). PLEASE ENSURE THAT
 THE LIGHTING PLAN REMAINS CONSISTENT WITH ANY CHANGES
 MADE TO THIS PERMIT.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK'D BY AVANN AND VNOEL)
  
 * CROSS REFERENCE: PERMIT #20021029 - BUILDING FACADE
 RENOVATION AND NEW COVERED ENTRY @ 420 CLAREMORE DR.);
 LANDSCAPING (PERMIT #20031047)
  
 * SEPARATE PERMITS REQUIRED FOR: PARKING AREA.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By llouie Date 2020-03-24 Time   Rev Time 0.00
Received By llouie Date 2020-03-24 Time   Sent To  
Notes
2020-03-24 07:49:17** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DISTANCE FOR ALL NEW LIGHT FIXTURES
 FROM THE PROPERTY LINES. THE LIGHT FIXTURES MUST BE
 PLACED AT LEAST 5 FT. FROM THE PROPERTY LINES. [ZLDR
 S.94-145(2)]
  
 2.) PROVIDE THE FOLLOWING NOTE IN THE PLAN: ALL OUTDOOR
 LIGHTING SHALL BE SHIELDED TO REDUCE GLARE AND SHALL BE
 ARRANGED TO REFLECT LIGHT OR GLARE AWAY FROM ALL
 ADJACENT RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR
 PUBLIC THOROUGHFARES, PURSUANT TO SEC. 94-309(A) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3.) APPROVAL OF THIS PERMIT IS CONTINGENT UPON THE
 APPROVAL OF PERMIT #20021029 (BUILDING FACADE
 RENOVATION AND NEW COVERED ENTRY). PLEASE ENSURE THAT
 THE LIGHTING PLAN REMAINS CONSISTENT WITH ANY CHANGES
 MADE TO THIS PERMIT.
  
 4.) THE VALUE OF THE CONSTRUCTION FROM PERMITS
 TABULATED FOR THE YEAR EXCEEDS 50% OF THE STRUCTURE'S
 VALUE ($260,915) ACCORDING TO THE P.B.C. PROPERTY
 APPRAISER'S OFFICE; THEREFORE, PURSUANT TO SECTION
 94-441(C)(2) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: GC
  
 * UNITY OF TITLE RECORDED FOR LOTS 5 THROUGH 8 (LESS
 43.25 FT. OF THE SOUTHERN HALF OF LOT 8) - REFERENCE
 ORB 31211, PAGE 236 (OK'D BY AVANN AND VNOEL)
  
 * CROSS REFERENCE: PERMIT #20021029 - BUILDING FACADE
 RENOVATION AND NEW COVERED ENTRY @ 420 CLAREMORE DR.)
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING, PARKING
 AREA.
  