Plan Review Details - Permit 20030974
Plan Review Stops For Permit 20030974
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 09:47 Rev Time 0.00
Received By cpuell Date 2020-12-29 Time 09:47 Sent To  
Notes
2020-12-29 09:47:59GIVEN ADDRESS IF 189@OKEECHOBEE BLVD TO REFLECT THE
 START OF THE PROJECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 15:54 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 15:54 Sent To  
Notes
2020-07-31 15:55:03PLEASE CONTACT [email protected], TO BE ASSIGNED A GENERIC
 PROPERTY CONTROL NUMBER FOR VERIZON, ALSO PLEASE EMAIL
 A SITE PLAN SHOWING THE EXACT LOCATION OF THE POLE IS
 TO BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 13:22 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 13:10 Sent To  
Notes
2021-06-24 13:22:3405/28/21 DISCUSSED WITH ROBERT BROWN.
 POLE IS LOCATED WITHIN FDOT ROW. POLE DESIGN AND
 SPECIFICATIONS REVIEWED/APPROVED UNDER FDOT PERMIT
 #2019-H-496-00552.
 PERMIT PACKAGE IS INCLUDED IN THIS SUBMITTAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 14:00 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 13:57 Sent To  
Notes
2021-06-07 14:01:13NOTE:
 CHRISTINA WARR SEND ME EMAIL ON 06/03/21 LISTING
 SEVERAL PROJECTS, INCLUDING THIS ONE 20030974. THERE IS
 NOTHING NEW UPLOADED TO PROJECTDOX. CONTRACTOR NEEDS TO
 UPLOAD TO PROJECTDOX THE INFORMATION TO ADDRESS THE
 COMMENTS BY ALL THE PLAN REVIEWERS.
 NOTE:
 PROVIDE FDOT APPROVED PERMIT PACKAGE. IF THERE IS NOT
 FDOT APPROVED PERMIT PACKAGE THEN ALL THE BUILDING
 REVIEW COMMENTS APPLY. SEE COMMENTS BELOW.
  
  
 SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE.
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT?. SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-09 Cont ID  
Sent By jgomez Date 2021-03-09 Time 13:05 Rev Time 0.00
Received By jgomez Date 2021-03-09 Time 12:50 Sent To  
Notes
2021-03-09 13:13:26SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE.
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT?. SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jgomez Date 2020-07-02 Time 17:59 Rev Time 0.00
Received By jgomez Date 2020-06-17 Time 16:54 Sent To  
Notes
2020-07-02 18:00:11BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 4- PLANS SUBMITTED HAVE A COPY OF THE ENGINEER'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS. ENGINEER TO SUBMIT
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ENGINEER MAY
 SUBMIT PLANS WITH DIGITAL SIGNATURE IF FOLLOWING THE
 PROCEDURE OF SEC. 61G15-23.004 FAC.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-10-28 Cont ID  
Sent By jleahy Date 2021-10-28 Time 11:16 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2021-08-27 Cont ID  
Sent By jleahy Date 2021-08-27 Time 15:12 Rev Time 0.00
Received By jleahy Date 2021-08-27 Time 15:12 Sent To  
Notes
2021-08-27 15:13:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WITH THE PANEL BEING IN THE POLE HOW DOES IT COMPLY
 WITH 110.26 FOR WORKING CLEARANCES?

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-17 Cont ID  
Sent By jleahy Date 2021-06-17 Time 13:16 Rev Time 0.00
Received By jleahy Date 2021-06-17 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By jleahy Date 2021-03-05 Time 12:43 Rev Time 0.00
Received By jleahy Date 2021-03-05 Time 07:41 Sent To  
Notes
2021-03-05 12:45:08REVIEW COMMENTS FROM 3/23/20 HAVE BEEN ADDRESSED ALL
 BUT #1 PLEASE SEE COMMENTS AND REPLY. JLEAHY
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 15:30 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 15:30 Sent To I
Notes
2020-03-23 15:30:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE GROUNDING DETAIL FOR SERVICE ON RISER
 DIAGRAM. NEC 215.5, 250; WPB FBC 107.2.1
 6. PROVIDE WIND LOAD DESIGN CRITERIA FOR POWER POLE.
 FBC 1609.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2021-07-07 Cont ID  
Sent By gpatrie Date 2021-07-07 Time 06:57 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-07-07 06:57:24I WILL REVIEW THE WIRELESS COMMUNICATION FACILITY
 PERMIT WITH REGARD TO THIS.
  
 CONTACT: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By gpatrie Date 2021-05-05 Time 07:55 Rev Time 0.00
Received By gpatrie Date 2021-05-05 Time 07:54 Sent To  
Notes
2021-05-05 07:55:00SEE PREVIOUS COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By gpatrie Date 2020-09-16 Time 07:02 Rev Time 0.00
Received By gpatrie Date 2020-09-16 Time 07:01 Sent To  
Notes
2020-09-16 07:02:42NO PLOE DESIGN SHOWN.
 OKEECHOBEE IS A FDOT ROADWAY.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-10-14 Cont ID  
Sent By mpeterso Date 2021-10-14 Time 09:20 Rev Time 0.00
Received By mpeterso Date 2021-08-11 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-07-08 Cont ID  
Sent By rmcdouga Date 2021-07-08 Time 17:33 Rev Time 0.00
Received By rmcdouga Date 2021-06-10 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 14:01 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 13:57 Sent To I
Notes
2021-06-07 14:02:08NOTE:
 CHRISTINA WARR SEND ME EMAIL ON 06/03/21 LISTING
 SEVERAL PROJECTS, INCLUDING THIS ONE 20030974. T
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-06 Cont ID  
Sent By rmcdouga Date 2021-05-06 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2021-03-01 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-21 Cont ID  
Sent By shill Date 2020-09-21 Time 17:43 Rev Time 0.00
Received By shill Date 2020-06-17 Time 12:09 Sent To  
Notes
2020-06-17 16:53:5706/17/2020 NEW INCOMING STOP WAS ADDED BECAUSE A
 COMMUNICATIONS PERMIT MAY BE REQUIRED (CITY ORDINANCE
 NO. 4774-18). THEREFORE, ZONING AND ENGINEERING REVIEWS
 WERE ADDED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 15:33 Sent To  
Notes
2020-03-19 15:33:54ELEC<5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-14 Cont ID  
Sent By mpeterso Date 2021-10-14 Time 09:20 Rev Time 0.00
Received By mpeterso Date 2021-10-14 Time 09:20 Sent To  
Notes
2021-10-14 08:46:33APPEARS AS ALL DOCUMENTS ARE DIGITALLY SIGNED
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 13:25 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 13:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-03-09 Cont ID  
Sent By jgomez Date 2021-03-09 Time 13:14 Rev Time 0.00
Received By jgomez Date 2021-03-09 Time 13:14 Sent To  
Notes
2021-03-09 13:17:59DRAWINGS T1, E1, E2, E3, E4, E5, E6 AND MT1 HAVE
 DIGITAL SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jgomez Date 2020-07-02 Time 17:37 Rev Time 0.00
Received By jgomez Date 2020-07-02 Time 17:37 Sent To  
Notes
2020-07-02 17:47:471-ENGINEER DRAWINGS SUBMITTED DON'T HAVE THE ENGINEER'S
 ORIGINAL SIGNATURE. PLANS SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL
 SEAL AND SIGNATURE OF THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 F.S.
 WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE:
 NEED TO PROVIDE HARD COPY OF DRAWINGS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR
 SUBMIT DIGITALLY SIGNED DRAWINGS FOLLOWING THE
 PROCEDURE OF SEC.61G15-23.004. NOTE: COORDINATE WITH
 CITY LIBRARIAN AT [email protected] FOR PROPER
 UPLOADING.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-10-28 Cont ID  
Sent By eschneid Date 2021-10-28 Time 14:26 Rev Time 0.25
Received By eschneid Date 2021-10-28 Time 14:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2021-10-08 Cont ID  
Sent By eschneid Date 2021-10-08 Time 13:24 Rev Time 0.25
Received By eschneid Date 2021-09-21 Time 08:17 Sent To  
Notes
2021-10-08 13:29:27FAILED
  
 THE COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY HAS NOT BEEN ISSUED FOR THE PORTION OF
 THIS FACILITY WITHIN THE CITY RIGHT-OF-WAY. PLEASE SEE
 THE COMMENTS UNDER PERMIT NO. 21090908 FOR THE
 CORRECTIONS THAT NEED TO BE MADE FOR THE CITY TO
 APPROVE THE TWO PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2021-07-02 Cont ID  
Sent By eschneid Date 2021-07-02 Time 11:33 Rev Time 0.50
Received By eschneid Date 2021-07-01 Time 15:12 Sent To  
Notes
2021-07-02 09:37:16FAILED
  
 THE RESPONSE COMMENTS WERE FOR A DIFFERENT PERMIT,
 PLEASE PROVIDE THE CORRECT COMMENTS.
  
 1) THE UNDERGROUND ELECTRIC WITHIN THE CHASE STREET
 RIGHT-OF-WAY REQUIRES A CITY WIRELESS COMMUNICATION
 FACILITY - ROW PERMIT. INFORMATION HAS BEEN SENT TO
 CHRISTINA WARR REGARDING THE APPLICATION. ONCE IT IS
 APPROVED, ZONING CAN COMPLETE THE REVIEW OF THE
 ELECTRIC PERMIT.
  
 2) ON GOING - PLEASE NOTE THAT THE CITY HAS APPROVED A
 REDEVELOPMENT PROJECT AT THIS LOCATION AND THE PROPOSED
 POLE LOCATION APPEARS TO CONFLICT WITH THE FINAL DESIGN
 OF THE IMPROVEMENTS WITHIN THE RIGHT-OF-WAY WHERE THE
 POLE AND HANDHOLE ARE PROPOSED (POLE LOCATED A FEW FEET
 TO THE SOUTH MAY CORRECT THIS). ADDITIONALLY, THE
 DEVELOPER PLANS TO REMOVE THE POWER POLE THAT YOU
 PROPOSE TO GET POWER FROM. THIS WILL NOT AFFECT THE
 ZONING APPROVAL OF THE ELECTRIC PERMIT; HOWEVER IT DOES
 AFFECT THE ULTIMATE PLACEMENT OF THE ITEMS WITHIN THE
 FDOT ROW.
  
 POLE COMPLIES WITH CITY STEALTH REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-25 Cont ID  
Sent By eschneid Date 2021-03-25 Time 11:21 Rev Time 0.25
Received By eschneid Date 2021-03-25 Time 10:50 Sent To  
Notes
2021-03-25 11:22:25FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS,
  
 1) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET THE
 CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE
 REQUIREMENTS LISTED IN SECTIONS 78-411(E) AND 78-411(F)
 OF THE CITY CODE. PROVIDE A POLE THAT MEETS THE CITY
 CODE REQUIREMENTS. NOTE: VERIZON HAS SHOWN POLES ON
 OTHER APPLICATIONS FOR OTHER LOCATIONS WITHIN THE CITY
 THAT MEET THE CITY CODE REQUIREMENTS.
  
 2) PLEASE NOTE THAT THE CITY HAS APPROVED A
 REDEVELOPMENT PROJECT AT THIS LOCATION AND THE PROPOSED
 POLE LOCATION APPEARS TO CONFLICT WITH THE FINAL DESIGN
 OF THE IMPROVEMENTS WITHIN THE RIGHT-OF-WAY WHERE THE
 POLE AND HANDHOLE ARE PROPOSED (POLE LOCATED A FEW FEET
 TO THE SOUTH MAY CORRECT THIS). PLEASE CONTACT ANA
 MARIA APONTE, CITY URBAN DESIGNER, @ (561) 822-1439 OR
 [email protected] FOR MORE DETAILS. ADDITIONALLY, THE
 DEVELOPER PLANS TO REMOVE THE POWER POLE THAT YOU
 PROPOSE TO GET POWER FROM.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By eschneid Date 2020-07-31 Time 10:37 Rev Time 0.25
Received By eschneid Date 2020-07-31 Time 10:37 Sent To  
Notes
2020-07-31 10:41:46FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET THE
 CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE
 AND POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 4) PLEASE NOTE THAT THE CITY HAS APPROVED A
 REDEVELOPMENT PROJECT AT THIS LOCATION AND THE PROPOSED
 POLE LOCATION APPEARS TO CONFLICT WITH THE FINAL DESIGN
 OF THE IMPROVEMENTS WITHIN THE AREA (POLE LOCATED A FEW
 FEET TO THE SOUTH MAY CORRECT THIS). PLEASE CONTACT ANA
 MARIA APONTE, CITY URBAN DESIGNER, @ (561) 822-1439 OR
 [email protected] FOR MORE DETAILS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  