Plan Review Details - Permit 20030973
Plan Review Stops For Permit 20030973
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2020-11-16 Cont ID  
Sent By dbattles Date 2020-11-16 Time 11:08 Rev Time 0.00
Received By dbattles Date 2020-11-16 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2020-09-25 Cont ID  
Sent By rmcphers Date 2020-09-25 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2020-09-25 Time 15:29 Sent To  
Notes
2020-09-25 15:31:53BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 YOU NEED TO APPLY FOR A NEW PERMIT FOR THE ADDITION
 (EXPIRED 02041430) BEFORE PERMITING A REVISION FOR A
 VIOLATION (A BUILDING THAT DID NOT RECEIVE A CO AND HAS
 AN EXPIRED PERMIT IS A VIOLATION). EXPIRED PERMIT SHOWN
 ON YOUR SITE PLAN. FBC WPB AMENDMENTS 111.1
  
 TO ASK QUESTIONS AND GET INFORMATION ABOUT EXPIRED OR
 OPEN PERMITS ON YOUR PROPERTY EMAIL US AT:
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2020-08-21 Time 10:05 Sent To  
Notes
2020-08-21 10:07:48ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 3RD REVIEW - YOU STATED IN YOUR RESUBMITTAL COMMENTS
 "EXTERIOR WALLS ARE EXISTING" EXTERNAL WALLS MAY BE
 EXISTING BUT, THE ADDITION DOES NOT HAVE A PERMIT
 (02041430 IS EXPIRED) - IF THIS IS NOT THE PERMIT FOR
 THE ADDITION YOU NEED TO APPLY FOR A NEW PERMIT FOR THE
 ADDITION BEFORE PERMITING A REVISION FOR A VIOLATION.
 ON YOUR SITE PLAN THE SCOPE OF WORK SAYS "ADDITION".
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE EXTERIOR DOOR LANDING FOR THE
 SLIDING DOOR AT THE MASTER BED ROOM TO COMPLY WITH FBC
 R311.3.2 AND R311.3
 2) DRAWING A-1 SHOWS ADDITION AS CMU WALL - DRAWING S-1
 SHOWS WOOD FRAMED WALL - PLEASE CLEARIFY - DETAILS
 SHOULD MATCH.
 3) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE USED.
 4) JOB DESCRIPTION ON THE BUILDING PERMIT APPLICATION
 NEEDS TO REFLECT THE DRAWINGS (SITE PLAN SHOWS SCOPE OF
 WORK AS ADDITION).
 5) DRAWING E-1 = THE SMOKE DETECTOR IN FRONT OF THE
 BATHROOM SHOULD BE SHOWN IN THE HALLWAY OF THE BEDROOMS
 FBC R314.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 15:04 Sent To  
Notes
2020-06-30 15:06:29ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE EXTERIOR DOOR LANDING FOR THE
 SLIDING DOOR AT THE MASTER BED ROOM TO COMPLY WITH FBC
 R311.3.2 AND R311.3
 2) DRAWING A-1 SHOWS ADDITION AS CMU WALL - DRAWING S-1
 SHOWS WOOD FRAMED WALL - PLEASE CLEARIFY - DETAILS
 SHOULD MATCH.
 3) PLEASE PROVIDE THE FRONT PAGES FOR THE "MASONITE"
 DOOR PRODUCT APPROVAL (MIAMI DADE OR FLORIDA STATE
 FRONT PAGES)
 4) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-25 Cont ID  
Sent By rmcphers Date 2020-03-25 Time 16:54 Rev Time 0.00
Received By rmcphers Date 2020-03-25 Time 16:36 Sent To  
Notes
2020-03-25 16:40:55ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE EXTERIOR DOOR LANDING FOR THE
 SLIDING DOOR AT THE MASTER BED ROOM TO COMPLY WITH FBC
 R311.3.2 AND R311.3
 2) PLEASE SHOW THE EXTERIOR WALL WATER RESISTIVE
 BARRIER TO COMPLY WITH FBC R703.2 WATER-RESISTIVE
 BARRIER.
 ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND
 BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR
 OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED
 OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS.
 3) DRAWING A-1 SHOWS ADDITION AS CMU WALL - DRAWING S-1
 SHOWS WOOD FRAMED WALL - PLEASE CLEARIFY - DETAILS
 SHOULD MATCH.
 4) PLEASE PROVIDE A TRUSS PLAN SHOWING ANY TRUSS
 BRACING REQUIRED. FBC R802.10.3
 5) PLEASE SHOW WALL AND CEILING INSULATION "R" VALUE
 AND INSULATION TYPE TO MATCH OR EXCEED THE "R" VALUE
 SHOWN ON THE ENERGY CALCS.
 6) BUILDER PLEASE SIGN THE "ENERGY PERFORMANCE LEVEL
 DISPLAY CARD" IN THE SPACE PROVIDED.
 7) OWNER PLEASE SIGN THE ENERGY CALCS. (FORM R405) IN
 THE SPACE PROVIDED.
 8) PLEASE PROVIDE THE FRONT PAGES FOR THE "MASONITE"
 DOOR PRODUCT APPROVAL (MIAMI DADE OR FLORIDA STATE
 FRONT PAGES)
 9) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE ROOFING SYSTEM TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rmcphers Date 2020-03-25 Time 12:26 Sent To  
Notes
2020-03-25 15:35:59ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE BATH DOOR
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-24 Cont ID  
Sent By jleahy Date 2020-09-24 Time 07:46 Rev Time 0.00
Received By jleahy Date 2020-09-24 Time 07:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-17 Cont ID  
Sent By fgiaquin Date 2020-08-17 Time 22:54 Rev Time 0.00
Received By fgiaquin Date 2020-08-17 Time 22:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-30 Cont ID  
Sent By rmcdouga Date 2020-03-30 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2020-03-30 Time 06:42 Sent To I
Notes
2020-03-30 09:13:02MARKUPS ON PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-11-16 Cont ID  
Sent By dbattles Date 2020-11-16 Time 11:19 Rev Time 0.00
Received By dbattles Date 2020-11-13 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-11-12 Cont ID  
Sent By lmarchan Date 2020-11-12 Time 07:50 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 16:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 10:42 Rev Time 0.00
Received By rmcphers Date 2020-08-06 Time 07:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-06 Cont ID  
Sent By lmarchan Date 2020-07-06 Time 10:19 Rev Time 0.00
Received By lmarchan Date 2020-06-25 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-30 Cont ID  
Sent By rmcdouga Date 2020-03-30 Time 09:13 Rev Time 0.00
Received By rmcdouga Date 2020-03-19 Time 15:50 Sent To  
Notes
2020-03-19 15:50:56R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2020-11-16 Cont ID  
Sent By dbattles Date 2020-11-16 Time 11:19 Rev Time 0.00
Received By dbattles Date 2020-11-16 Time 11:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 15:08 Sent To  
Notes
2020-06-30 15:09:51PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By rmcphers Date 2020-03-26 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2020-03-26 Time 07:49 Sent To  
Notes
2020-03-26 07:50:41PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-09-21 Cont ID  
Sent By medwards Date 2020-09-21 Time 07:14 Rev Time 0.00
Received By medwards Date 2020-09-21 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-20 Cont ID  
Sent By medwards Date 2020-03-20 Time 12:15 Rev Time 0.00
Received By medwards Date 2020-03-20 Time 12:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2020-11-16 Cont ID  
Sent By ccole Date 2020-11-16 Time 08:32 Rev Time 0.00
Received By ccole Date 2020-11-16 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2020-09-21 Cont ID  
Sent By ccole Date 2020-09-21 Time 08:44 Rev Time 0.00
Received By ccole Date 2020-09-21 Time 07:09 Sent To  
Notes
2020-09-21 08:44:51 
 3RD REVIEW FBC-2017 RES.
 PERMIT- 20030973
 9/21/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #1 FROM THE 1ST AND 2ND REVIEWS STILL EXISTS. A
 LARGER TANKLESS WATER HEAT- TITAN N-180- IS NOW SHOWN
 ON SHEET P-1, HOWEVER NO SPECS HAVE BEEN SUBMITTED.
 THERE IS A COMMENT RESPONSE NARRATIVE SUBMITTED THAT
 SHOWS A TEMPERATURE RISE CHART FOR THE N-180. THE CHART
 INDICATES A 4.0 GPM FLOW RATE AT 31 DEGREE F
 TEMPERATURE RISE. PLEASE NOTE OUR GROUND WATER
 TEMPERATURE AVERAGING AROUND 75 DEGREES F WOULD REQUIRE
 A MINIMUM OF 31 DEGREE RISE TO REACH HOT WATER
 TEMPERATURE OF 110 DEGREES F. A 4.0 GPM FLOW IS
 UNDERSIZED FOR THE HOUSE WHICH HAS TWO FULL BATHS,
 KITCHEN SINK AND DISHWASHER, AND A WASHING MACHINE.
 PLEASE NOTE THAT THE MAX WATER CONSUMPTION FOR FIXTURES
 AND FAUCETS ON SHEET P1 IS INCOMPLETE AND DOES NOT
 PROVIDE THE TOTAL REQUIRED GPM FLOW FOR THE FIXTURES.
 I HAVE TRIED TO CONTACT THE PERSON WHO PREPARED THE
 COMMENT RESPONSE NARRATIVE HOWEVER THERE WAS NO CONTACT
 INFORMATION- NAME AND TELEPHONE NUMBER- LISTED ON THE
 NARRATIVE.
  
 1) SHEET P-1 BASED ON THE SUBMITTED SPECIFICATION
 SHEET, THE SELECTED TITAN N-120 TANKLESS WATER AT MAX
 FLOW OF 4.0 GPM DOES NOT HAVE THE LARGE ENOUGH CAPACITY
 TO SUPPLY HOT WATER TO THE FIXTURES SHOWN ON THE PLANS-
 SEE TABLE P2903.1 FBC RES. REVISE THE PLAN TO PROVIDE
 THE MAKE AND MODEL OF WATER HEATER WITH ADEQUATE
 CAPACITY, AND SUBMIT MANUFACTURER?S SPECIFICATIONS WITH
 TEMPERATURE RISE AND FLOW CAPACITY CHART.
  
 2) SHEET P2, ISOMETRIC: PLEASE LABEL THE WASHING
 MACHINE DRAIN AND VENT LINE. TWO SHOWERS ARE INDICATED
 HOWEVER BATH 2 HAS A TUB/SHOWER FIXTURE. CHANGE WB
 LABELS TO LAVATORIES- SECTION 107.2.1 WPB.
  
 3) P-2: PROVIDE A WATER HAMMER ARRESTOR FOR THE SUPPLY
 LINE TO THE ICE MAKER- SECTIONS P2903.5 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-08-07 Cont ID  
Sent By ccole Date 2020-08-07 Time 16:02 Rev Time 0.00
Received By ccole Date 2020-08-07 Time 15:24 Sent To  
Notes
2020-08-07 16:06:042ND REVIEW FBC-2017 RES.
 PERMIT- 20030973
 8/7/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1 BASED ON THE SUBMITTED SPECIFICATION
 SHEET, THE SELECTED TITAN N-120 TANKLESS WATER AT MAX
 FLOW OF 4.0 GPM DOES NOT HAVE THE LARGE ENOUGH CAPACITY
 TO SUPPLY HOT WATER TO THE FIXTURES SHOWN ON THE PLANS-
 SEE TABLE P2903.1 FBC RES. REVISE THE PLAN TO PROVIDE
 THE MAKE AND MODEL OF WATER HEATER WITH ADEQUATE
 CAPACITY, AND SUBMIT MANUFACTURER?S SPECIFICATIONS WITH
 TEMPERATURE RISE AND FLOW CAPACITY CHART.
  
 2) P-1: ACCESS TO THE VALVES FOR THE STACKABLE
 WASHER/DRYER UNIT REMAINS NOT CLEARLY INDICATED-
 SECTION P2903.9.3. TYPICALLY, THE VALVE BOX WOULD BE
 LOCATED AT THE FRONT OF THE SIDE WALL TO ALLOW ACCESS.
 THE PLAN SHOWS THE BOX AT THE REAR OF THE UNIT WITH A
 REMOTE VALVE ALSO SHOWN AT THE REAR. HOW WOULD THE
 REMOTE VALVE BE ACCESSED? IF A REMOTE VALVE IS TO BE
 INSTALLED, CLEARLY SHOW THE LOCATIONS AND SUBMIT A
 PRODUCT SPEC SHEET- SECTION 107.2.1 WPB.
  
 3) P-2: A FLAT LINE DRAWING FOR WATER DISTRIBUTION WAS
 PROVIDED IN LIEU OF THE REQUEST FOR WATER RISER PER
 SECTION 107.3.5.3 WPB. PLEASE REVISE THE DRAWING TO
 SHOW THE PIPE SIZES, THE LOCATION AND PIPING FOR THE
 WATER HEATER, THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS, AND BACKFLOW PREVENTERS. PLEASE NOTE THAT
 WATER HAMMER ARRESTORS ARE REQUIRED FOR SUPPLY LINES TO
 QUICK-CLOSING VALVES INCLUDING THE WASHING MACHINE,
 DISHWASHER, AND ICE MAKER- SECTION P2903.5 FBC RES. A
 BACKFLOW PREVENTER IS REQUIRED FOR THE SUPPLY LINE TO
 THE ICE MAKER AND THE DISHWASHER- SECTION P2902.1. THE
 DISHWASHER LINE CAN BE PROTECTED USING AN AIR GAP
 INSTEAD OF A BF PREVENTER- SECTION P2902.3.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-06 Cont ID  
Sent By rmcdouga Date 2020-07-06 Time 08:54 Rev Time 0.00
Received By rmcdouga Date 2020-07-06 Time 07:31 Sent To  
Notes
2020-07-06 08:55:00PLUMBING 2ND REVIEW COMMENTS* 20030973
 1) VALUE APPEARS TOO LOW. YOU MUST INCLUDE ALL COST,
 THIS INCLUDES ALL OWNER SUPPLIED MATERIAL. FBC 109.3
 2) PROVIDE WHICH MODEL TANKLESS YOU ARE USING ON THIS
 PROJECT. THE HEADING SCR-2 IS NOT LISTED ON THE
 TEMPERATURE RISE CHART. WITH OUT THIS INFORMATION I AM
 UNABLE TO VERIFY THE TANKLESS YOU HAVE CHOSEN WILL
 PRODUCE ENOUGH HOT WATER AT FULL LOAD. FBC-PLB 604.3
 3) BOTH THE FLAT AND ISOMETRIC DRAWING ON SHEETS P1 AND
 P2 SHOW THE GUEST BATHROOM COMBO FITTING FACING IN THE
 WRONG DIRECTION. FBC-PLB 706.3
 4) SHOW LOCATION OF WASHING MACHINE REMOTE SHUT OFF
 VALVES AS IT DOES NOT APPEAR YOU WILL HAVE ACCESS TO
 THE ONES IN THE WASHING MACHINE BOX WITH IT BEHIND THE
 STACKABLE WASHER AND DRYER. FBC-PLB 606.3
 5) SHEET ON P1 UNDER TUB AND SHOWER WALL NOTES REFERS
 TO FBC 2004. PLEASE CORRECT AS WE HAVE BEEN ON THE 2017
 6TH ED SINCE 12/31/2017. FBC 107.2
 6) PROVIDE A WATER ISOMETRIC DRAWING. WPB AD 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 (CAP GOVERNMENT)
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By ccole Date 2020-03-27 Time 13:11 Rev Time 0.00
Received By ccole Date 2020-03-27 Time 12:49 Sent To  
Notes
2020-03-27 14:24:331ST REVIEW FBC-2017 PLUMBING
 PERMIT #20030973
 3/27/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1:THE WYE FITTINGS FOR THE KITCHEN SINK AND
 CLOTHES WASHER DRAINS ARE DIRECTING THE WASTE FLOWS
 UPSTREAM INTO THE MAIN DRAIN INSTEAD OF DOWNSTREAM-
 SECTION P3005.1 FBC RES.
  
 2) P-1: PROVIDE A SANITARY ISOMETRIC DRAWING- SECTION
 P3005.4 FBC RES AND SECTION 107.3.5.3 WPB RES.
  
 3) P-1: SHOW HOW ACCESS AND VENTILATION WILL BE
 PROVIDED FOR THE STUDOR VENTS AT THE TUB/SHOWER, AND
 THE SHOWER IN MASTER BATH- SECTION P3114.5 FBC RES.
  
 4) SUBMIT A SPEC SHEET FOR THE TANKLESS WATER HEATER-
 SECTION P2801.3 & M2005 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2020-11-16 Cont ID  
Sent By dbattles Date 2020-11-16 Time 11:09 Rev Time 0.00
Received By dbattles Date 2020-11-16 Time 11:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2020-09-28 Cont ID  
Sent By rmcphers Date 2020-09-28 Time 07:28 Rev Time 0.00
Received By rmcphers Date 2020-09-28 Time 07:28 Sent To  
Notes
2020-09-28 07:28:53SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 15:10 Sent To  
Notes
2020-06-30 15:10:21SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By rmcphers Date 2020-03-26 Time 07:51 Rev Time 0.00
Received By rmcphers Date 2020-03-26 Time 07:51 Sent To  
Notes
2020-03-26 07:51:54SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-11-16 Cont ID  
Sent By dbattles Date 2020-11-16 Time 11:15 Rev Time 0.00
Received By dbattles Date 2020-11-16 Time 11:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2020-09-28 Cont ID  
Sent By rmcphers Date 2020-09-28 Time 07:34 Rev Time 0.00
Received By rmcphers Date 2020-09-28 Time 07:34 Sent To  
Notes
2020-09-28 07:35:18ALL DRAWINGS ADDED TO PROJECTDOX (ELECTRONIC PLAN
 REVIEW) AFTER 06/25/2020 = SIGNED AND SEALED DRAWINGS
 IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY
 SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN
 ELECTRONIC PLAN REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE
 READER" AS DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF
 YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-21 Cont ID  
Sent By rmcphers Date 2020-08-21 Time 10:37 Rev Time 0.00
Received By rmcphers Date 2020-08-21 Time 10:37 Sent To  
Notes
2020-08-21 10:39:05ALL DRAWINGS ADDED TO PROJECTDOX (ELECTRONIC PLAN
 REVIEW) AFTER 06/25/2020 = SIGNED AND SEALED DRAWINGS
 IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY
 SIGNED BY THE ENGINEER OR ARCHITECT TO BE USED IN
 ELECTRONIC PLAN REVIEW. DRAWINGS DO NOT SHOW IN "ADOBE
 READER" AS DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF
 YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 15:10 Sent To  
Notes
2020-06-30 15:11:20SEE COMMENTS ON PREVIOUS "SIGNATURE" REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-06-22 Cont ID  
Sent By jgomez Date 2020-06-22 Time 17:45 Rev Time 0.00
Received By jgomez Date 2020-06-22 Time 17:45 Sent To  
Notes
2020-06-22 17:47:09CONVERTED TO DIGITAL.
 (1)DRAWINGS HAVE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE. JG.
 (2) TRUSS PACKAGE. DRAWINGS HAVE ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2020-10-27 Cont ID  
Sent By rthermid Date 2020-10-27 Time   Rev Time 0.00
Received By rthermid Date 2020-10-27 Time   Sent To I
Notes
***NONE***