Plan Review Details - Permit 20030970
Plan Review Stops For Permit 20030970
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-06-07 Cont ID  
Sent By cpuell Date 2021-06-07 Time 14:57 Rev Time 0.00
Received By cpuell Date 2021-06-07 Time 14:57 Sent To  
Notes
2021-06-07 14:58:15551 @ OKEECHOBEE BLVD, GIVE THE START OF THE PROJECT,
 UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-03-02 Cont ID  
Sent By cpuell Date 2021-03-02 Time 14:36 Rev Time 0.00
Received By cpuell Date 2021-03-02 Time 14:36 Sent To  
Notes
2021-03-02 14:37:41PLANS SHOW MULTIPLE MANHOLES, PLEASE EMAIL ME A SITE
 PLAN INDICATING THE LOCATION OF THE PROJECT
 SPECIFICALLY THE START OF THE SERVICE, SO THAT AN
 ADDRESS CAN BE ESTABLISHED. EMAIL [email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 12:19 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 12:19 Sent To  
Notes
2020-07-31 12:22:34PLEASE CONTACT [email protected], TO BE ASSIGNED A GENERIC
 PROPERTY CONTROL NUMBER FOR VERIZON, ALSO PLEASE EMAIL
 A SITE PLAN SHOWING THE EXACT LOCATION OF THE POLE IS
 TO BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 11:28 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 11:26 Sent To  
Notes
2021-06-24 11:29:3905/28/21 DISCUSSED WITH ROBERT BROWN.
 POLE IS LOCATED WITHIN FDOT ROW. POLE DESIGN AND
 SPECIFICATIONS REVIEWED/APPROVED UNDER FDOT PERMIT
 #2019-H-496-00550.
 PERMIT PACKAGE IS INCLUDED IN THIS SUBMITTAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 13:22 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 13:21 Sent To  
Notes
2021-06-07 13:23:13NOTE:
 CHRISTINA WARR SEND ME EMAIL ON 06/03/21 LISTING
 SEVERAL PROJECTS, INCLUDING THIS ONE 20030970. THERE IS
 NOTHING NEW UPLOADED TO PROJECTDOX. CONTRACTOR NEEDS TO
 UPLOAD TO PROJECTDOX THE INFORMATION TO ADDRESS THE
 COMMENTS BY ALL THE PLAN REVIEWERS.
 NOTE:
 PROVIDE FDOT APPROVED PERMIT PACKAGE. IF THERE IS NOT
 FDOT APPROVED PERMIT PACKAGE THEN ALL THE BUILDING
 REVIEW COMMENTS APPLY. SEE COMMENTS BELOW.
  
  
  
 SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20030970
  
 ORIGINAL COMMENT:
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE:
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 ORIGINAL COMMENT:
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By jgomez Date 2021-03-05 Time 17:02 Rev Time 0.00
Received By jgomez Date 2021-03-05 Time 16:38 Sent To  
Notes
2021-03-05 17:03:24SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #20030970
  
 ORIGINAL COMMENT:
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE:
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 ORIGINAL COMMENT:
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By jgomez Date 2020-06-17 Time 16:45 Rev Time 0.00
Received By jgomez Date 2020-06-17 Time 16:41 Sent To  
Notes
2020-06-17 16:45:37BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 4- PLANS SUBMITTED HAVE A COPY OF THE ENGINEER'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS. ENGINEER TO SUBMIT
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ENGINEER MAY
 SUBMIT PLANS WITH DIGITAL SIGNATURE IF FOLLOWING THE
 PROCEDURE OF SEC. 61G15-23.004 FAC.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-06-16 Cont ID  
Sent By jleahy Date 2021-06-16 Time 14:00 Rev Time 0.00
Received By jleahy Date 2021-06-16 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-03-03 Cont ID  
Sent By jleahy Date 2021-03-03 Time 12:50 Rev Time 0.00
Received By jleahy Date 2021-03-03 Time 12:45 Sent To  
Notes
2021-03-03 12:52:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 YOU NEED TO ADDRESS THE REVEIW COMMENTS FROM 3/23/20.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 15:23 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 15:23 Sent To  
Notes
2020-03-23 15:23:35CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE GROUNDING DETAIL FOR SERVICE ON RISER
 DIAGRAM. NEC 215.5, 250; WPB FBC 107.2.1
 6. PROVIDE WIND LOAD DESIGN CRITERIA FOR POWER POLE.
 FBC 1609.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-08-12 Cont ID  
Sent By gpatrie Date 2021-08-12 Time 08:55 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-08-12 08:55:26NEW POLE DESIGN SUBMITTED.
 THIS IS NOT IN THE CITY RIGHT-OF-WAY, FDOT.
  
 CONTACT: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By gpatrie Date 2021-05-05 Time 07:53 Rev Time 0.00
Received By gpatrie Date 2021-05-05 Time 07:52 Sent To  
Notes
2021-05-05 07:53:20SEE PREVIOUS COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By gpatrie Date 2020-09-16 Time 07:13 Rev Time 0.00
Received By gpatrie Date 2020-09-16 Time 07:12 Sent To  
Notes
2020-09-16 07:13:03NO POLE DESIGN SHOWN.
 OKEECHOBEE BLVD IS A FDOT ROADWAY, PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2021-09-21 Time   Rev Time 0.00
Received By aoliver Date 2021-08-23 Time 07:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-13 Cont ID  
Sent By jgomez Date 2021-08-13 Time 18:26 Rev Time 0.00
Received By jgomez Date 2021-06-08 Time 13:50 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 13:23 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 13:21 Sent To  
Notes
2021-06-07 13:22:10EMAIL FROM CHRISTINA WARR (REAL ESTATE PROJECT MANAGER)
 DATED 06/03/21

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-06 Cont ID  
Sent By rmcdouga Date 2021-05-06 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2021-02-25 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By lmarchan Date 2020-09-22 Time 07:49 Rev Time 0.00
Received By lmarchan Date 2020-06-17 Time 12:08 Sent To  
Notes
2020-06-17 16:40:4406/17/2020 NEW INCOMING STOP WAS ADDED BECAUSE A
 COMMUNICATIONS PERMIT MAY BE REQUIRED (CITY ORDINANCE
 NO. 4774-18). THEREFORE, ZONING AND ENGINEERING REVIEWS
 WERE ADDED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 15:32 Sent To  
Notes
2020-03-19 15:32:38ELEC<5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-09-22 Cont ID  
Sent By ccole Date 2021-09-21 Time 16:37 Rev Time 0.00
Received By ccole Date 2021-09-21 Time 16:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-06-24 Cont ID  
Sent By jgomez Date 2021-06-24 Time 13:08 Rev Time 0.00
Received By jgomez Date 2021-06-24 Time 13:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-03-05 Cont ID  
Sent By jgomez Date 2021-03-05 Time 17:16 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2021-03-05 17:21:23DRAWING E5 HAS A COPY OF THE ENGINEER'S SEAL AND
 SIGNATURE. NEED TO UPLOAD DRAWING WITH ENGINEER'S
 DIGITAL SIGNATURE AS DONE WITH ALL OTHER PLANS UPLOADED
 IN THIS SUBMITTAL.
 DRAWINGS NEED TO HAVE THE ENGINEER'S DIGITAL SIGNATURE
 FOLLOWING THE PROCEDURE OF SEC. 61G15-23.004 F.A.C TO
 ALLOW FOR SIGNATURE VERIFICATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jgomez Date 2020-07-02 Time 17:53 Rev Time 0.00
Received By jgomez Date 2020-07-02 Time 17:53 Sent To  
Notes
2020-07-02 17:53:371-ENGINEER DRAWINGS SUBMITTED DON'T HAVE THE ENGINEER'S
 ORIGINAL SIGNATURE. PLANS SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL
 SEAL AND SIGNATURE OF THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 F.S.
 WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE:
 NEED TO PROVIDE HARD COPY OF DRAWINGS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR
 SUBMIT DIGITALLY SIGNED DRAWINGS FOLLOWING THE
 PROCEDURE OF SEC.61G15-23.004. NOTE: COORDINATE WITH
 CITY LIBRARIAN AT [email protected] FOR PROPER
 UPLOADING.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2021-09-28 Cont ID  
Sent By eschneid Date 2021-09-28 Time 10:37 Rev Time 0.25
Received By eschneid Date 2021-09-28 Time 10:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2021-09-21 Cont ID  
Sent By eschneid Date 2021-09-21 Time 15:30 Rev Time 0.25
Received By eschneid Date 2021-09-20 Time 16:22 Sent To  
Notes
2021-09-21 15:33:08FAILED
  
 IN ACCORDANCE WITH THE WCF ROW REVIEW BY THE
 ENGINEERING DEPARTMENT, YOU MUST ?REVISE LAT / LONG
 LOCATIONS FOR CELL TOWER."
  
 CONTACT ERIC SCHNEIDER @ [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2021-08-06 Cont ID  
Sent By eschneid Date 2021-08-06 Time 15:13 Rev Time 0.25
Received By eschneid Date 2021-08-06 Time 14:42 Sent To  
Notes
2021-08-06 15:13:06FAILED
  
 1) A PORTION OF THE UNDERGROUND POWER TRAVERSES ALABAMA
 AVENUE, A CITY RIGHT-OF-WAY. A COMMUNICATIONS
 FACILITIES PLACEMENT PERMIT APPLICATION - CITY
 RIGHTS-OF-WAY MUST BE SUBMITTED TO THE CITY'S BUILDING
 DIVISION AND APPROVED BY THE CITY'S PLANNING AND
 ENGINEERING SERVICES DIVISIONS FOR THE ALABAMA AVENUE
 PORTION OF THIS PROJECT PRIOR TO THIS PERMIT BEING
 APPROVED.
  
 2) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE SIDEWALK, WITH
 DIMENSIONS, AND THE RIGHT-OF-WAY LINE SO THAT STAFF CAN
 VERIFY THAT THE UNDERGROUND POWER AND HANDHOLES
 ASSOCIATED WITH THE WIRELESS COMMUNICATION FACILITY IS
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 3) THE UTILITY POWER PLAN NEEDS TO VERIFY THE SETBACK
 FROM THE UNDERGROUND POWER AND HANDHOLES FROM THE
 RIGHT-OF-WAY LINE.
  
 4) PLEASE ENSURE THAT YOU COORDINATE WITH THE RELATED
 SIDEWALK PROJECT FOR THE PLACEMENT OF THE FEATURES AT
 THE NORTHEAST CORNER OF THE OKEECHOBEE BOULEVARD AND
 ROSEMARY AVENUE INTERSECTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-03-04 Cont ID  
Sent By eschneid Date 2021-03-04 Time 11:41 Rev Time 0.25
Received By eschneid Date 2021-03-04 Time 11:41 Sent To  
Notes
2021-03-04 11:41:30FAILED - SAME COMMENTS
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION, THE
 HANDHOLES, THE UNDERGROUND ELECTRIC, THE SIDEWALK AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT MUST SHOW THAT
 THE PROPOSED WIRELESS FACILITY (POLE) MEETS THE CITY OF
 WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE AND
 POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By eschneid Date 2020-07-31 Time 11:42 Rev Time 0.25
Received By eschneid Date 2020-07-31 Time 11:35 Sent To  
Notes
2020-07-31 11:48:51FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. THE
 ENGINEERING PLAN SHOWS THE POLE, AND ELECTRIC BOX,
 ENCROACHING PRIVATE PROPERTY, WHICH IS NOT PERMITTED
 UNLESS THE CITY HAS APPROVED A WIRELESS COMMUNICATION
 FACILITIES PERMIT.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET THE
 CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE
 AND POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 4) THE AREA WHERE THE PROPOSED POLE IS SHOWN IS
 CURRENTLY UNDER RECONSTRUCTION TO CHANGE THE LOCATION
 OF THE SIDEWALK AND THE LANDSCAPE AREA. THE LOCATION OF
 THE POLE SHOWN ON THE ENGINEERING PLAN APPEARS TO BE
 LOCATED IN THE MIDDLE OF THE PROPOSED BICYCLE LANE THAT
 IS BEING CONSTRUCTED. PLEASE CONTACT CITYPLACE RETAIL
 LLC FOR THE SPECIFIC PLANS SO THAT YOU CAN COORDINATE
 LOCATING THE POLE OUTSIDE OF THE SIDEWALK AND AVOID THE
 PROPOSED PALM TREES BEING INSTALLED IN THE RIGHT-OF-WAY
 LANDSCAPE STRIP.
  