Plan Review Details - Permit 20030969
Plan Review Stops For Permit 20030969
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 10:43 Rev Time 0.00
Received By cpuell Date 2020-12-29 Time 10:43 Sent To  
Notes
2020-12-29 10:44:03GIVEN ADDRESS OF 5575 @ BROADWAY TO REFLECT START OF
 PROJECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 12:31 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 12:31 Sent To  
Notes
2020-07-31 12:31:52PLEASE CONTACT [email protected], TO BE ASSIGNED A GENERIC
 PROPERTY CONTROL NUMBER FOR VERIZON, ALSO PLEASE EMAIL
 A SITE PLAN SHOWING THE EXACT LOCATION OF THE POLE IS
 TO BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2021-12-21 Cont ID  
Sent By jgomez Date 2021-12-21 Time 17:20 Rev Time 0.00
Received By jgomez Date 2021-12-21 Time 17:19 Sent To  
Notes
2021-12-21 17:21:1005/28/21 DISCUSSED WITH ROBERT BROWN.
 POLE IS LOCATED WITHIN FDOT ROW. POLE DESIGN AND
 SPECIFICATIONS REVIEWED/APPROVED UNDER FDOT PERMIT
 #2019-H-496-00742.
 PERMIT PACKAGE IS INCLUDED IN THIS SUBMITTAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By jgomez Date 2020-06-17 Time 16:31 Rev Time 0.00
Received By jgomez Date 2020-06-17 Time 16:30 Sent To  
Notes
2020-06-17 16:31:18BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 4- PLANS SUBMITTED HAVE A COPY OF THE ENGINEER'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS. ENGINEER TO SUBMIT
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ENGINEER MAY
 SUBMIT PLANS WITH DIGITAL SIGNATURE IF FOLLOWING THE
 PROCEDURE OF SEC. 61G15-23.004 FAC.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-02-17 Cont ID  
Sent By mpeterso Date 2022-02-17 Time 09:52 Rev Time 0.00
Received By mpeterso Date 2022-02-17 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 07:51 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 07:51 Sent To  
Notes
2021-12-27 07:54:18IT APPEARS PLAN LABELED "UTILITY ROUTING" IS A COPY OF
 A SIGNED AND SEAL DRAWING BY THE ENGINEER OF RECORD.
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 15:22 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 15:22 Sent To I
Notes
2020-03-23 15:22:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE GROUNDING DETAIL FOR SERVICE ON RISER
 DIAGRAM. NEC 215.5, 250; WPB FBC 107.2.1
 6. PROVIDE WIND LOAD DESIGN CRITERIA FOR POWER POLE.
 FBC 1609.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2021-12-07 Cont ID  
Sent By eschneid Date 2021-12-07 Time 09:49 Rev Time 0.00
Received By eschneid Date 2021-12-07 Time 09:49 Sent To  
Notes
2021-12-07 09:50:10ENGINEERING REIVEW WILL BE COMPLETED AS PART OF
 COMMUNICATION FACILITY IN ROW APPLICATION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By gpatrie Date 2020-09-16 Time 06:57 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2020-09-16 06:57:40NO POLE DESIGN SHOWN.
 THIS IS A FDOT ROADWAY, PERMIT REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-04-07 Cont ID  
Sent By lmarchan Date 2022-04-07 Time 15:43 Rev Time 0.00
Received By lmarchan Date 2022-02-22 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-17 Cont ID  
Sent By mpeterso Date 2022-02-17 Time 09:53 Rev Time 0.00
Received By mpeterso Date 2022-02-04 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-04 Cont ID  
Sent By cpuell Date 2022-01-04 Time 08:31 Rev Time 0.00
Received By cpuell Date 2021-11-30 Time 13:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By lmarchan Date 2020-09-22 Time 07:48 Rev Time 0.00
Received By lmarchan Date 2020-06-17 Time 12:07 Sent To  
Notes
2020-06-17 16:39:3906/17/2020 NEW INCOMING STOP WAS ADDED BECAUSE A
 COMMUNICATIONS PERMIT MAY BE REQUIRED (CITY ORDINANCE
 NO. 4774-18). THEREFORE, ZONING AND ENGINEERING REVIEWS
 WERE ADDED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 15:32 Sent To  
Notes
2020-03-19 15:32:49ELEC<5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-17 Cont ID  
Sent By mpeterso Date 2022-02-17 Time 09:52 Rev Time 0.00
Received By mpeterso Date 2022-02-17 Time 09:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-12-27 Cont ID  
Sent By mpeterso Date 2021-12-27 Time 07:54 Rev Time 0.00
Received By mpeterso Date 2021-12-27 Time 07:54 Sent To  
Notes
2021-12-27 07:54:51IT APPEARS PLAN LABELED "UTILITY ROUTING" IS A COPY OF
 A SIGNED AND SEAL DRAWING BY THE ENGINEER OF RECORD.
 PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED
 AND SEALED BY THE ENGINEER OF RECORD
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jgomez Date 2020-07-02 Time 17:54 Rev Time 0.00
Received By jgomez Date 2020-07-02 Time 17:54 Sent To  
Notes
2020-07-02 17:54:121-ENGINEER DRAWINGS SUBMITTED DON'T HAVE THE ENGINEER'S
 ORIGINAL SIGNATURE. PLANS SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL
 SEAL AND SIGNATURE OF THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 F.S.
 WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE:
 NEED TO PROVIDE HARD COPY OF DRAWINGS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR
 SUBMIT DIGITALLY SIGNED DRAWINGS FOLLOWING THE
 PROCEDURE OF SEC.61G15-23.004. NOTE: COORDINATE WITH
 CITY LIBRARIAN AT [email protected] FOR PROPER
 UPLOADING.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2022-06-22 Cont ID  
Sent By eschneid Date 2022-06-22 Time 09:31 Rev Time 0.25
Received By eschneid Date 2022-06-22 Time 09:31 Sent To  
Notes
2022-06-22 09:32:26THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. THE
 POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042
 TRAFFIC GREY A.
  
  

Review Stop Z ZONING
Rev No 4 Status F Date 2022-04-07 Cont ID  
Sent By eschneid Date 2022-04-07 Time 11:18 Rev Time 0.25
Received By eschneid Date 2022-04-07 Time 11:08 Sent To  
Notes
2022-04-07 11:17:58FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-02-16 Cont ID  
Sent By eschneid Date 2022-02-16 Time 17:28 Rev Time 0.25
Received By eschneid Date 2022-02-16 Time 14:35 Sent To  
Notes
2022-02-16 17:28:51FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. SOME OF THE COMMENTS BELOW
 ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS
 WITH THIS PERMIT.
  
 2) UPDATED COMMENT: THANK YOU FOR PROVIDING THE
 ENGINEERING SITE PLANS FOR THE ENTIRE UNDERGROUND
 ELECTRIC PATH; HOWEVER, SURVEY SHEET B-3, WHICH SHOWS
 THE WESTERN PORTION OF THE PROJECT TO THE POWER POLE AT
 MANNING AVENUE WAS NOT INCLUDED WITH THE RESUBMITTAL.
  
 3) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By eschneid Date 2022-01-03 Time 16:20 Rev Time 0.25
Received By eschneid Date 2022-01-03 Time 15:25 Sent To  
Notes
2022-01-03 16:25:11FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY MUST BE APPROVED PRIOR TO
 THIS PERMIT BEING APPROVED. SOME OF THE COMMENTS BELOW
 ARE INCLUDED ON THE PLACEMENT PERMIT REVIEW AS WELL AS
 WITH THIS PERMIT.
  
 2) THE SURVEY AND ENGINEERING SITE PLANS NEED TO SHOW
 THE ENTIRE UNDERGROUND ELECTRIC PATH. THE SURVEY NEEDS
 TO SHOW THE RIGHT-OF-WAY LINE FOR THE ENTIRE LENGTH OF
 THE INSTALLATION SO THAT STAFF CAN VERIFY THAT THE
 UNDERGROUND ELECTRIC IS FULLY WITHIN THE RIGHT-OF-WAY.
  
 3) PROVIDE CROSS SECTIONS OF THE LOCATION OF THE
 UNDERGROUND ELECTRIC FOR THE FULL LENGTH OF THE
 INSTALLATION ALONG 55TH STREET. THERE UNDERGROUND
 ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE STREET TREE
 ROOT SYSTEMS AND ANY INFRASTRUCTURE THAT IT CROSSES
 (EXAMPLE THE SANITARY LINE SHOWN ON THE SURVEY).
  
 4) SHEET E5, UTILITY ROUTING / GROUNDING PLAN SHOWS A
 WIRELESS FACILITY DESIGN THAT DOES NOT COMPLY WITH CITY
 STANDARDS. NOTE: A COMPLIANT FACILITY IS SHOWN ON
 SHEETS E2, E3 AND C3.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By eschneid Date 2020-07-31 Time 11:27 Rev Time 0.25
Received By eschneid Date 2020-07-31 Time 11:17 Sent To  
Notes
2020-07-31 11:29:55FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. THE
 ENGINEERING PLAN SHOWS THE POLE, AND ELECTRIC BOX,
 ENCROACHING PRIVATE PROPERTY, WHICH IS NOT PERMITTED
 UNLESS THE CITY HAS APPROVED A WIRELESS COMMUNICATION
 FACILITIES PERMIT.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET THE
 CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE
 AND POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  