Plan Review Details - Permit 20030968
Plan Review Stops For Permit 20030968
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-12-29 Cont ID  
Sent By cpuell Date 2020-12-29 Time 10:51 Rev Time 0.00
Received By cpuell Date   Time   Sent To  
Notes
2020-12-29 10:52:30GIVEN ADDRESS OF 3186 @ BROADWAY BASED ON START OF
 PROJECT

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 15:39 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 15:39 Sent To  
Notes
2020-07-31 15:39:55PLEASE CONTACT [email protected], TO BE ASSIGNED A GENERIC
 PROPERTY CONTROL NUMBER FOR VERIZON, ALSO PLEASE EMAIL
 A SITE PLAN SHOWING THE EXACT LOCATION OF THE POLE IS
 TO BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2021-10-07 Cont ID  
Sent By jgomez Date 2021-10-07 Time 15:59 Rev Time 0.00
Received By jgomez Date 2021-10-07 Time 14:54 Sent To  
Notes
2021-10-07 16:01:1305/28/21 DISCUSSED WITH ROBERT BROWN.
 POLE IS LOCATED WITHIN FDOT ROW. POLE DESIGN AND
 SPECIFICATIONS REVIEWED/APPROVED UNDER FDOT PERMIT
 #2019-H-496-00737.
 FDOT PERMIT PACKAGE IS INCLUDED IN THIS SUBMITTAL. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-06-07 Cont ID  
Sent By jgomez Date 2021-06-07 Time 11:25 Rev Time 0.00
Received By jgomez Date 2021-06-07 Time 11:19 Sent To  
Notes
2021-06-07 11:29:48EMAIL FROM CHRISTINA WARR (REAL ESTATE PROJECT MANAGER)
 DATED 06/03/21 STATES THAT "THE METAL POLE WILL BE
 INSTALLED UNDER THE ROW PERMIT ISSUED BY FDOT. THE
 ENCLOSURE ATTACHED TO THE POLE IS ALSO PERMITTED UNDER
 A SEPARATE ROW PERMIT WHICH HAS BEEN ISSUED BY FDOT.
 THESE APPLICATIONS ARE ONLY FOR THE ELECTRICAL
 CONNECTION TO THE POLE."
  
 NOTE:
 PROVIDE FDOT APPROVED PERMIT PACKAGE. IF THERE IS NOT
 FDOT APPROVED PERMIT PACKAGE THEN ALL THE BUILDING
 REVIEW COMMENTS APPLY. SEE COMMENTS BELOW.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 HI JULIO,
 I NOTICED YOU MADE THE SAME COMMENTS TO SEVERAL OF
 VERIZON?S ELECTRICAL PERMIT PROJECTS, SO I WANTED TO
 ADDRESS THEM AS A WHOLE. THIS PERTAINS TO THE FOLLOWING
 PROJECTS:
  
 20030966
 20030968
 20101190
 20101364
 21020848
 20030970
 20030971
 20030974
  
 1) ORIGINAL COMMENT:
 VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 RESPONSE:
 THE SCOPE OF WORK IS ONLY FOR THE ELECTRICAL CONNECTION
 TO THE POLE. TOTAL VALUATION IS $1,800. THE
 INSTALLATION OF THE POLE IS NOT INCLUDED IN THIS
 PERMIT. THE POLE INSTALLATION AND DIRECTIONAL BORE IS
 APPROVED UNDER A SEPARATE FDOT PERMIT.
 2) ORIGINAL COMMENT:
 APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT ONLY
 FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE TO
 SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED, IT
 LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 RESPONSE:
 THE RIGHT-OF-WAY PERMITS HAVE BEEN APPROVED AND ISSUED
 BY FDOT. THESE APPLICATIONS ARE ONLY FOR THE ELECTRICAL
 CONNECTION TO THE POLE.
 3) ORIGINAL COMMENT:
 TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL? PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT.
 RESPONSE:
 THE METAL POLE WILL BE INSTALLED UNDER THE ROW PERMIT
 ISSUED BY FDOT. THE ENCLOSURE ATTACHED TO THE POLE IS
 ALSO PERMITTED UNDER A SEPARATE ROW PERMIT WHICH HAS
 BEEN ISSUED BY FDOT. THESE APPLICATIONS ARE ONLY FOR
 THE ELECTRICAL CONNECTION TO THE POLE.
  
 COULD YOU PLEASE REVIEW THESE PERMITS WITH THIS
 INFORMATION?
  
 THANK YOU,
 CHRISSY
  
 CHRISTINA WARR
 REAL ESTATE PROJECT MANAGER
 [email protected]
 C. 815-405-3664
 WWW.SMARTLINKGROUP.COM
  
  
  
  
  
 SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE.
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT?. SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-04-20 Cont ID  
Sent By jgomez Date 2021-04-20 Time 15:02 Rev Time 0.00
Received By jgomez Date 2021-04-20 Time 14:40 Sent To  
Notes
2021-04-20 15:02:56SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 RESPONSE.
 PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT?. SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 RESPONSE:
 A) IT IS NOT CLEAR IF A NEW POLE WILL BE INSTALLED OR
 NOT. IF NEW POLE IS INSTALLED, THEN PROVIDE COMPLETE
 ENGINEERING DETAILS AND SPECIFICATIONS, INCLUDING THE
 EFFECTIVE PROJECTIVE AREA OF THE POLE AND PROPOSED
 EQUIPMENT TO BE INSTALLED IN IT.
 PLANS ALSO SHOW VERIZON WIRELESS ENCLOSURES ATTACHED TO
 THE POLE. THERE ARE NO SPECIFICATIONS FOR THE
 ATTACHMENT OF THIS ENCLOSURES TO THE POLE. SEC. 1609.1
 FBC-BUILDING. ALSO, PROVIDE ALL THE WIND DESIGN DATA AS
 REQUIRED BY SEC. 1603.4 FBC-BUILDING.
  
 B)PROVIDE POLE MANUFACTURER'S SPECS MEETING THE
 ENGINEER'S DESIGN CRITERIA. ENGINEER OF RECORD TO
 REVIEW/APPROVED POLE SPECS PRIOR TO SUBMITTAL. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 RESPONSE
 NOT ADDRESSED. SCOPE OF WORK IS NOT CLEAR. UNABLE TO
 DETERMINE VALUE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By jgomez Date 2020-06-17 Time 11:47 Rev Time 0.00
Received By gpatrie Date 2020-06-17 Time 11:46 Sent To  
Notes
2020-07-29 07:37:27ENG/RIGHT-OF-WAY
  
 1) PROPOSED POLE DOES NOT MEET STEALTH REQUIREMENTS FOR
 CONSEALMENT.
2020-06-17 11:47:50BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 4- PLANS SUBMITTED HAVE A COPY OF THE ENGINEER'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS. ENGINEER TO SUBMIT
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ENGINEER MAY
 SUBMIT PLANS WITH DIGITAL SIGNATURE IF FOLLOWING THE
 PROCEDURE OF SEC. 61G15-23.004 FAC.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2021-11-06 Cont ID  
Sent By jleahy Date 2021-11-06 Time 07:38 Rev Time 0.00
Received By jleahy Date 2021-11-06 Time 07:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-06-15 Cont ID  
Sent By jleahy Date 2021-06-15 Time 13:35 Rev Time 0.00
Received By jleahy Date 2021-06-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-04-06 Cont ID  
Sent By jleahy Date 2021-04-06 Time 09:07 Rev Time 0.00
Received By jleahy Date 2021-04-06 Time 08:56 Sent To  
Notes
2021-04-06 09:11:06 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THE WORK SHOWN ON PAGES E-3 AND E-4 WHO IS RESPONSIBLE
 FOR THIS WORK?
  
 THIS WORK SHALL BE INCLUDED WITH THE COST ESTIMATE FOR
 THE JOB. IF THIS WORK IS BEING DONE BY SOMEONE ELSE
 THEN WE NEED TO KNOW WHO IT IS, ARE THEY LICENSED, DO
 THEY HAVE A PERMIT?

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-30 Cont ID  
Sent By jleahy Date 2020-06-30 Time 11:11 Rev Time 0.00
Received By jleahy Date 2020-06-29 Time 15:55 Sent To  
Notes
2020-06-30 11:36:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FIRST A FEW QUESTION
  
 COVER SHEET SHOWS A PROPOSED POLE WHO WILL INSTALL?
  
 SHEET E-2 SHOW APPROXIMATLEY 284' OF UNDERGROUND
 SERVICE WHO IS INSTALLING THIS CONDUIT AND WIRE?
  
 YOUR LETTER FROM FPL GIVES YOU THE 21,100 AVAILABLE
 FAULT CURRENT IF YOU ARE JUST GOING TO USE THIS AS A
 BASIS THEN WHAT IS THE AIC RATING OF THE 100A MAIN AND
 THE BRANCH CIRCUIT BREAKERS. YOU NEED TO STATE THIS ON
 PANEL SCHEDULE OR AS A NOTE TO THE CONTRACTOR
 INSTALLING THE PANEL AND BREAKERS.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 15:22 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 15:22 Sent To I
Notes
2020-03-23 15:22:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE GROUNDING DETAIL FOR SERVICE ON RISER
 DIAGRAM. NEC 215.5, 250; WPB FBC 107.2.1
 6. PROVIDE WIND LOAD DESIGN CRITERIA FOR POWER POLE.
 FBC 1609.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2021-08-13 Cont ID  
Sent By gpatrie Date 2021-08-13 Time 07:39 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2021-08-13 07:39:48BROADWAY IS A FDOT ROADWAY AND OUT OF THE CITY
 RIGHT-OF-WAY.
 RIGHT-0F WAY PERMIT REQUIRED FOR THE BORE ALONG 31TH
 ST.
  
 CONTACT: [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2021-05-05 Cont ID  
Sent By gpatrie Date 2021-05-05 Time 08:16 Rev Time 0.00
Received By gpatrie Date 2021-05-05 Time 08:15 Sent To  
Notes
2021-05-05 08:16:04SEE PREVIOUS COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By gpatrie Date 2020-09-16 Time 06:51 Rev Time 0.00
Received By gpatrie Date   Time   Sent To  
Notes
2020-09-16 06:51:09POLE DESIGN DOES NOT MEET STEALTH REQUIREMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-12-10 Cont ID  
Sent By lmarchan Date 2021-12-10 Time 09:56 Rev Time 0.00
Received By lmarchan Date 2021-10-09 Time 17:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-07 Cont ID  
Sent By jgomez Date 2021-10-07 Time 16:05 Rev Time 0.00
Received By jgomez Date 2021-09-16 Time 10:41 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 09:04 Rev Time 0.00
Received By jleahy Date 2021-06-04 Time 12:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-11 Cont ID  
Sent By lmarchan Date 2021-05-11 Time 16:37 Rev Time 0.00
Received By lmarchan Date 2021-03-31 Time 13:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 09:05 Rev Time 0.00
Received By jleahy Date 2020-06-15 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 15:32 Sent To  
Notes
2020-03-19 15:33:02ELEC <5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-11-06 Cont ID  
Sent By jleahy Date 2021-11-06 Time 07:38 Rev Time 0.00
Received By jleahy Date 2021-11-06 Time 07:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-06-15 Cont ID  
Sent By jleahy Date 2021-06-15 Time 13:35 Rev Time 0.00
Received By jleahy Date 2021-06-15 Time 13:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-04-20 Cont ID  
Sent By jgomez Date 2021-04-20 Time 14:58 Rev Time 0.00
Received By jgomez Date 2021-04-20 Time 14:57 Sent To  
Notes
2021-04-20 15:01:411-ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM WHEN
 SUBMITTING FOR PUBLIC RECORDS. DRAWING E8 DOESN'T HAVE
 A DIGITAL SIGNATURE. IT HAS A COPY OF THE ENGINEER'S
 SEAL/SIGNATURE. NOTE: THERE ARE TWO E-8 DRAWINGS.
 REVISE/CLARIFY AS REQUIRED.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE PAPER VERSION OF
 DRAWINGS WITH THE ENGINEER?S ORIGINAL HANDWRITTEN
 SIGNATURE AND SEAL. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 09:05 Rev Time 0.00
Received By jleahy Date 2020-06-30 Time 11:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-15 Cont ID  
Sent By shill Date 2020-06-15 Time 14:10 Rev Time 0.00
Received By shill Date 2020-06-15 Time 14:10 Sent To  
Notes
2020-06-15 14:11:21SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 PAPER ORIGINALS WERE SUBMITTED FOR 1ST REVIEW, BUT
 RESUBMITTED PAGES ARE NOT DIGITALLY SIGNED.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED
 PAPER ORIGINAL WITH A WET SIGNATURE TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.

Review Stop Z ZONING
Rev No 5 Status P Date 2021-12-09 Cont ID  
Sent By eschneid Date 2021-12-09 Time 17:36 Rev Time 0.25
Received By eschneid Date 2021-12-09 Time 17:36 Sent To  
Notes
2021-12-09 17:39:11MUST COMPLY WITH CONDITIONS OF WCF ROW APPROVAL
 21061721.

Review Stop Z ZONING
Rev No 4 Status F Date 2021-09-21 Cont ID  
Sent By eschneid Date 2021-09-21 Time 16:22 Rev Time 0.25
Received By eschneid Date 2021-09-20 Time 16:57 Sent To  
Notes
2021-09-21 16:23:00FAILED - NO NEW PLANS UPLOADED.
  
 1) REPEAT COMMENT: PROVIDE A SURVEY SHOWING THE ENTIRE
 AREA COVERED BY SHEET E2 UTILITY POWER PLAN. THE SURVEY
 NEEDS TO SHOW THE RIGHT-OF-WAY LINE AND THE EDGE OF THE
 SIDEWALK AND EDGE OF PAVEMENT IN THE ALLEY SO THAT
 STAFF CAN VERIFY THE UNDERGROUND POWER IS ENTIRELY
 WITHIN THE RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) REPEAT COMMENT: PROVIDE THE SETBACKS OF THE
 UNDERGROUND POWER FROM THE EDGE OF THE RIGHT-OF-WAY
 LINE ON SHEET E2 UTILITY POWER PLAN SO THAT STAFF CAN
 VERIFY THE UNDERGROUND POWER IS ENTIRELY WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 3) POLE COMPLIES WITH CITY STANDARDS.
  
 4) THE WIRELESS COMMUNICATIONS FACILITY (ROW) PERMIT
 HAS BEEN REVIEWED AND HAS SAME COMMENTS AS ABOVE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2021-07-30 Cont ID  
Sent By eschneid Date 2021-07-30 Time 11:15 Rev Time 0.25
Received By eschneid Date 2021-07-30 Time 10:40 Sent To  
Notes
2021-07-30 11:16:23FAILED
  
 1) PROVIDE A SURVEY SHOWING THE ENTIRE AREA COVERED BY
 SHEET E2 UTILITY POWER PLAN. THE SURVEY NEEDS TO SHOW
 THE RIGHT-OF-WAY LINE AND THE EDGE OF THE SIDEWALK AND
 EDGE OF PAVEMENT IN THE ALLEY SO THAT STAFF CAN VERIFY
 THE UNDERGROUND POWER IS ENTIRELY WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE THE SETBACKS OF THE UNDERGROUND POWER FROM
 THE EDGE OF THE RIGHT-OF-WAY LINE ON SHEET E2 UTILITY
 POWER PLAN SO THAT STAFF CAN VERIFY THE UNDERGROUND
 POWER IS ENTIRELY WITHIN THE RIGHT-OF-WAY AND NOT ON
 PRIVATE PROPERTY.
  
 3) POLE COMPLIES WITH CITY STANDARDS.
  
 4) THE WIRELESS COMMUNICATIONS FACILITY (ROW) PERMIT
 HAS BEEN REVIEWED AND HAS SAME COMMENTS AS ABOVE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-05-11 Cont ID  
Sent By eschneid Date 2021-05-11 Time 15:29 Rev Time 0.25
Received By eschneid Date 2021-05-11 Time 15:29 Sent To  
Notes
2021-05-11 15:30:06FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) PROVIDE VERIFICATION THAT THE SITE HAS BEEN ISSUED A
 COMMUNICATION FACILITY PLACEMENT PERMIT - CITY
 RIGHTS-OF-WAY AND A RIGHT-OF-WAY USE PERMIT FOR THE
 UNDERGROUND POWER AND THE HANDHOLE THAT ARE SHOWN
 WITHIN THE ALLEY AND THE 31ST STREET RIGHTS-OF-WAY. THE
 PLANS INCLUDED WITH THIS ELECTRICAL PERMIT MUST MATCH
 THE PLANS APPROVED WITH THE AFOREMENTIONED PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By eschneid Date 2020-07-24 Time 16:38 Rev Time 0.25
Received By eschneid Date 2020-07-24 Time 16:38 Sent To  
Notes
2020-07-24 16:41:40FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH),
 STYLE OR HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  