Plan Review Details - Permit 20030965
Plan Review Stops For Permit 20030965
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By cpuell Date 2020-07-31 Time 15:58 Rev Time 0.00
Received By cpuell Date 2020-07-31 Time 15:58 Sent To  
Notes
2020-07-31 16:01:21PLEASE CONTACT [email protected], TO BE ASSIGNED A GENERIC
 PROPERTY CONTROL NUMBER FOR VERIZON, ALSO PLEASE EMAIL
 A SITE PLAN SHOWING THE EXACT LOCATION OF THE POLE IS
 TO BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-17 Cont ID  
Sent By jgomez Date 2020-06-17 Time 13:57 Rev Time 0.00
Received By jgomez Date 2020-06-17 Time 13:57 Sent To  
Notes
2020-06-17 13:58:25BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- APPLICATION WAS SUBMITTED AS AN ELECTRICAL PERMIT
 ONLY FOR THE INSTALLATION OF 100 AMP ELECTRICAL SERVICE
 TO SMALL CELL POLE. BASED ON THE INFORMATION SUBMITTED,
 IT LOOKS LIKE A COMMUNICATIONS PERMIT IS REQUIRED. CITY
 ORDINANCE NO. 4774-18.
 NOTE: PLEASE SEE ZONING AND ENGINEERING COMMENTS.
  
 2- TITLE SHEET T1 SPECIFIES "INSTALLATION OF PROPOSED
 POWER FOR SMALL CELL EQUIPMENT ON PROPOSED METAL POLE".
 SCOPE OF WORK IS NOT CLEAR. IS THERE A NEW METAL POLE
 OR IS IT EXISTING INSTALLED BY FPL.?. PLANS ALSO SHOW
 VERIZON WIRELESS ENCLOSURE ATTACHED TO THE POLE. THERE
 ARE NO SPECIFICATIONS FOR THE ATTACHMENT OF THIS
 ENCLOSURE TO THE POLE. IS THIS DONE UNDER ANOTHER
 PERMIT. ? SEC. 107.2.1 CITY AMENDMENTS.
 PROVIDE PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 THE PROPOSED METAL POLE AND VERIZON WIRELESS ENCLOSURE
 ATTACHMENT IF THEY ARE PART OF THIS PERMIT. SEC. 1609.1
 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. UPDATE
 VALUATION AS REQUIRED, INCLUDING DESIGN PROFESSIONAL
 FEES.
  
 4- PLANS SUBMITTED HAVE A COPY OF THE ENGINEER'S SEAL
 AND SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS. ENGINEER TO SUBMIT
 PLANS WITH ORIGINAL SEAL AND SIGNATURE OR ENGINEER MAY
 SUBMIT PLANS WITH DIGITAL SIGNATURE IF FOLLOWING THE
 PROCEDURE OF SEC. 61G15-23.004 FAC.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 15:20 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 15:20 Sent To I
Notes
2020-03-23 15:20:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 5. PROVIDE GROUNDING DETAIL FOR SERVICE ON RISER
 DIAGRAM. NEC 215.5, 250; WPB FBC 107.2.1
 6. PROVIDE WIND LOAD DESIGN CRITERIA FOR POWER POLE.
 FBC 1609.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-09-16 Cont ID  
Sent By gpatrie Date 2020-09-16 Time 07:18 Rev Time 0.00
Received By gpatrie Date 2020-09-16 Time 07:17 Sent To  
Notes
2020-09-16 07:18:09POLE DESIGN DOES NOT MEET STEALTH REQUIREMENTS.
 BROADWAY IS A FDOT ROADWAY.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-21 Cont ID  
Sent By shill Date 2020-09-21 Time 17:42 Rev Time 0.00
Received By shill Date 2020-06-17 Time 12:06 Sent To  
Notes
2020-06-17 14:04:4606/17/2020 NEW INCOMING STOP WAS ADDED BECAUSE A
 COMMUNICATIONS PERMIT MAY BE REQUIRED (CITY ORDINANCE
 NO. 4774-18). THEREFORE, ZONING AND ENGINEERING REVIEWS
 WERE ADDED. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-19 Time 15:33 Sent To  
Notes
2020-03-19 15:33:15ELEC <5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-02 Cont ID  
Sent By jgomez Date 2020-07-02 Time 17:56 Rev Time 0.00
Received By jgomez Date 2020-07-02 Time 17:56 Sent To  
Notes
2020-07-02 17:56:191-ENGINEER DRAWINGS SUBMITTED DON'T HAVE THE ENGINEER'S
 ORIGINAL SIGNATURE. PLANS SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SIGNATURE. PLANS NEED TO HAVE THE ORIGINAL
 SEAL AND SIGNATURE OF THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 F.S.
 WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 NOTE:
 NEED TO PROVIDE HARD COPY OF DRAWINGS WITH ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR
 SUBMIT DIGITALLY SIGNED DRAWINGS FOLLOWING THE
 PROCEDURE OF SEC.61G15-23.004. NOTE: COORDINATE WITH
 CITY LIBRARIAN AT [email protected] FOR PROPER
 UPLOADING.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-31 Cont ID  
Sent By eschneid Date 2020-07-31 Time 15:28 Rev Time 0.25
Received By eschneid Date 2020-07-31 Time 15:28 Sent To  
Notes
2020-07-31 15:33:39FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. THE
 ENGINEERING PLAN INCORRECTLY SHOWS THE RIGHT-OF-WAY
 LINE. STAFF FOUND AN OLD SURVEY AND WHEN COMPARING THE
 SURVEY TO THE PERMIT SHOWS THE POLE, AND ELECTRIC BOX,
 ENCROACHING PRIVATE PROPERTY, WHICH IS NOT PERMITTED
 UNLESS THE CITY HAS APPROVED A WIRELESS COMMUNICATION
 FACILITIES PERMIT.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PLANS SUBMITTED WITH THE PERMIT SHOW THAT THE
 PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET THE
 CITY OF WEST PALM BEACH CONCEALMENT (STEALTH) OR STYLE
 AND POSSIBLY HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: VERIZON HAS SHOWN POLES ON OTHER APPLICATIONS FOR
 OTHER LOCATIONS WITHIN THE CITY THAT MEET THE CITY CODE
 REQUIREMENTS.
  
 4) THE POWER DRAW IS SHOWN FROM A POLE ALONG THE ALLEY
 TO THE EAST OF THE PROPERTY. THE SURVEY YOUR PROVIDE
 NEEDS TO CLEARLY SHOW THAT THE UNDERGROUND POWER IS
 WITHIN THE ALLEY (CITY WIRELESS COMMUNICATION FACILITY
 IN THE RIGHT-OF-WAY PERMIT IS REQUIRED FOR THIS WORK)
 AND NOT ON PRIVATE PROPERTY. THE STAFF SURVEY SHOWS NO
 UTILITY EASEMENT ON THE PRIVATE PROPERTY, SO YOU MAY
 NOT BORE UNDER THE LOT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  