Plan Review Details - Permit 20030953
Plan Review Stops For Permit 20030953
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-04-07 Cont ID  
Sent By jwitmer Date 2020-04-07 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2020-05-31 Time 09:45 Sent To  
Notes
2020-04-07 10:20:44BUILT IN 1997 NO ASBESTOS. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-06 Cont ID  
Sent By jwitmer Date 2020-07-06 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2020-07-06 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-31 Cont ID  
Sent By jwitmer Date 2020-05-31 Time 12:19 Rev Time 0.00
Received By jwitmer Date 2020-05-31 Time 09:45 Sent To  
Notes
2020-05-31 12:19:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030953
 ADD: 360 N. ROSEMARY AVE. 9TH FLOOR
 CONT: MOSS & ASSOCIATES
 TEL: 561-719-5517
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SUNDAY MAY 31ST/ 2020
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) COMPLIED. 6/09/2020.
  
 4) SHEET A.3.0.1., A.3.0.2. & A3.0.3. PLEASE SEE THE
 PLUMBING REVIEWER COMMENTS ON ACCESSIBILITY
 REQUIREMENTS MISSING FROM THIS SHEET. 107.2.1.2
 ADDITIONAL REQUIREMENTS FOR CONFORMANCE TO THE 2017
 FBC-ACCESSIBILITY CODE.
  
 5A) COMPLIED.
  
 5B) 2ND REQUEST. THE NARRATIVE RESPONSE STATES 5 INCH
 CIP (CAST-IN-PLACE) SLAB. NO INFORMATION AS TO THE
 RE-ENFORCING STEEL PLACEMENT IN THE CEILING SLAB NOR
 BEAM.
 SHEET A5.0.1. IN BOTH DETAILS 3 & 4 BOTH DETAILS
 INDICATE A CONCRETE BEAM AND POURED CONCRETE CEILING.
 THERE IS NO INFORMATION AS TO THE CONCRETE DESIGN,
 THICKNESS OF THE SLAB, SIZE OF RE-ENFORCING RODS,
 SPACING, IF TURNED ENDS ARE REQUIRED OR NOT TO TIE INTO
 THE BEAM? SEE 2017 FBC-B 1905.
  
 5C) COMPLIED. 6/09/2020.
  
 5D) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-07 Cont ID  
Sent By jwitmer Date 2020-04-07 Time 10:25 Rev Time 0.00
Received By jwitmer Date 2020-04-06 Time 10:30 Sent To  
Notes
2020-04-07 10:19:312017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030953
 ADD: 360 N. ROSEMARY AVE. 9TH FLOOR
 CONT: MOSS & ASSOCIATES
 TEL: 561-719-5517
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY APRIL 06TH/ 2020
 ACTION: DENIED
  
 1) LIFE SAFETY SHEET ALS1.1:
  
 1A) CODE ANALYSIS. THE ALS1.1 SHOWS THE FITNESS ROOM
 WITH AT 1,274 SQ. FT./ 50 = 30 OCCUPANTS. 1274/50=
 25.48 OR 26 OCCUPANTS. SEE TABLE 1004.1.2 OF THE 2017
 FBC-B.
  
 1B) CODE ANALYSIS. SHEET ALS1.1 SHOWS A OCCUPANT LOAD
 OF 82 OCCUPANTS @ 15 SQ. FT. OCCUPANT LOAD FACTOR
 PLEASE PROVIDE THE SQUARE FOOTAGE THIS AREA INCLUDES.
 TABLE 1004.1.2. 2017 FBC-B. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1C) COMMON PATH IS INDICATED TABLE 1006.2.1 OF THE
 FBC-B FOR SPRINKLERED BUILDINGS 100 FEET. THE PROPOSED
 COMMON PATH IS 102 FEET 4 (MEN?S SHOWER) INCHES AND THE
 COMMENT STATES- MEETS THE REQUIREMENT. WHEN MEASURING
 FOR THE COMMON PATH OF TRAVEL YOU SHOULD MEASURE
 BETWEEN 12 TO 18 INCHES OF THE WALL LINE SINCE YOU
 WOULD OR SHOULD BE CRAWLING BECAUSE OF SMOKE AND YOU
 FEEL YOUR WAY THROUGH THE OFFICE YOU WOULD BE ABOUT 12
 TO 18 INCHES AWAY FROM THE WALL, DOING THIS YOUR
 DISTANCE WOULD BE GREATER THAN AS YOU MEASURED. PLEASE
 PROVIDE AN EXPLANATION AS TO WHAT IS MEANT? DISCREPANCY
 IN PLANS. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1D)UNDER THE HEADING OF OCCUPANCY THE PLANS STATES THE
 OCCUPANCY OF THE CONFERENCE ROOM IS 82, UNDER THE
 HEADING FOR MEANS OF EGRESS THE PLANS STATE THE
 OCCUPANCY FOR THE CONFERENCE ROOM IS 61, DISCREPANCY IN
 PLANS. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1E) WITH THE OCCUPANT LOAD OF THE CONFERENCE ROOM AREA
 BEING GREATER THAN 49 OCCUPANTS 2 EXITS ARE REQUIRED.
 THE 2 DOORS FOR EGRESS FOR THIS AREA ARE DOOR # 170
 WHICH SWINGS OUT IN THE DIRECTION OF EGRESS TRAVEL AND
 THE DOOR THAT IS IN THE BREAK ROOM 918 WHICH IS A IN
 SWING DOOR. THIS DOOR DOES NOT SWING IN THE DIRECTION
 OF EGRESS TRAVEL AND DOES NOT COMPLY WITH THE 2017
 FBC-B SECTION 1010.1.2.1. TRAVEL IS NOT ALLOWED THROUGH
 A KITCHEN OR STORAGE ROOM BUT WOULD BE ALLOWED THROUGH
 A BREAK ROOM. FBC-B 1016.2.5.
  
 1F) FITNESS ROOM 901 DOES NOT SHOW COMPLIANCE WITH
 CLEAR FLOOR SPACE FOR EXERCISE MACHINES AND EQUIPMENT.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY
 CODE 1004,1 CLEAR FLOOR SPACE. ASLO REVIEW ADVISORY
 1004.1 TO BE ABLE TO OPTIMIZE SPACE USE.
  
 2) SHEET A1.1.2 INDICATES IN THE CONFERENCE ROOMS THE
 USE OF ACOUSTICAL WOOD PANELING, THERE IS A SECTION
 DETAIL 9/A4.0.1. THIS DETAIL STATES THAT 5/8 INCH
 WALLBOARD CEILING AREA ARE TO BE ON 3 5/8 20 GAUGE
 METAL STUD FRAMING @ 24 INCHES ON CENTER AND TO BE
 ATTACHED TO STRUCTURE ABOVE. THEN THERE IS A 2ND NOTE,
 THE WOOD FINISHED CEILING (ACOUSTICAL WOOD PANELING) ON
 ? INCH PLYWOOD (FIRE RETARDANT TREATED PLYWOOD ?) TO BE
 ATTACHED TO FRAMING ABOVE. THIS DETAIL NEEDS MORE
 ATTENTION. WITH THE CURRENT DETAIL THERE IS A ? INCH
 SHOT HOLDING UP THE UPPER TRACK AND THEN THERE IS A
 METAL STUD WITH 2 STEEL FRAMING SCREWS INTO THE UPPER
 TRACK AND A CHANNEL TRACK SCREWED INTO THE SIDE OF THE
 METAL STUD. THEN THERE IS 3 LAYERS HUNG FROM THIS
 ASSEMBLY, A LAYER OF 5/8 WALL BOARD, ? INCH PLYWOOD
 (QUESTION FIRE RESISTANT?) AND THEN THE ? INCH OAK
 CEILING. NO MENTION OF STRUCTURAL STUDS HOLDING THIS
 DROPPED CEILING, OR IF THERE WILL BE ADDITIONAL
 STIFF-BACK FRAMING MEMBERS AND ADDITIONAL UP RIGHT
 FRAMING SHOT INTO THE DECK ABOVE. PLEASE SHOW
 COMPLIANCE WITH TABLE 2508.1 ASTM C754 STEEL FRAMING
 FOR GYPSUM BOARD AND GYPSUM PANEL PRODUCTS. MAY ALSO
 REVIEW ASTM C1063 THIS IS FOR CEMENT PLASTER BUT GOOD
 INFORMATION FOR HANGING CEILINGS.
  
 3) SHEET A.2.0.1. SHOWS 2 MANUALLY OPERATED FOLDING
 PARTITION WALLS, ( E ) HUFCOR GLASS PARTITION & (F)
 HUFCOR SOLID WOOD PARTITION. BOTH DETAILS REFER TO
 SECTION 4/A.2.0.1 WHERE THE WHOLE ASSEMBLY IS TO BE
 HUNG FROM THE FLOOR / CEILING ASSEMBLY ABOVE. THE
 DETAIL INDICATES STRUCTURAL SUPPORT BY G. C. THIS
 SUPPORT SYSTEM NEEDS TO BE AN ENGINEERED SUPPORT
 SYSTEM. THE NEED AS TO WHAT TYPE OF FLOOR SYSTEM IS IN
 PLACE WILL NEED TO BE KNOWN FOR THE ENGINEER TO BE ABLE
 TO DESIGN THE ANCHORING SYSTEM AND VERTICAL SUPPORT
 SYSTEM. WHAT LOADS ARE EACH OF THE TRACK SYSTEM GOING
 TO BE REQUIRED TO CARRY? WHEN THE WALL SYSTEM IS FOLDED
 UP IN PLACE WHAT WILL THE CONCENTRATED LOADS GOING TO
 BE REQUIRED FOR THIS AREA?
 SEE 2017 FBC-B LIVE LOADS 1607.2 & 1607.4.
  
 4) SHEET A.3.0.1., A.3.0.2. & A3.0.3. PLEASE SEE THE
 PLUMBING REVIEWER COMMENTS ON ACCESSIBILITY
 REQUIREMENTS MISSING FROM THIS SHEET. 107.2.1.2
 ADDITIONAL REQUIREMENTS FOR CONFORMANCE TO THE 2017
 FBC-ACCESSIBILITY CODE.
  
 5A) SHEET A5.0.1 SHOWS BOTH THE MEN?S AND WOMEN?S
 SHOWERS AS WHAT APPEARS TO BE 8 INCH BLOCK WALLS IS
 THERE GOING TO BE ANY HORIZONTAL JOINT REINFORCEMENT?
 FBC-B 2103.4 METAL REINFORCEMENT.
  
 5B) SHEET A5.0.1. IN BOTH DETAILS 3 & 4 BOTH DETAILS
 INDICATE A CONCRETE BEAM AND POURED CONCRETE CEILING.
 THERE IS NO INFORMATION AS TO THE CONCRETE DESIGN,
 THICKNESS OF THE SLAB, SIZE OF RE-ENFORCING RODS,
 SPACING, IF TURNED ENDS ARE REQUIRED OR NOT TO TIE INTO
 THE BEAM? SEE 2017 FBC-B 1905.
  
 5C) SHEET A.5.0.1. DETAIL 4 SHOWS A TRENCH DRAIN CUT
 INTO THE STRUCTURAL FLOOR SYSTEM. THIS IS TO BE TYPICAL
 FOR BOTH THE MEN?S AND WOMEN?S SHOWERS. THERE HAS BEEN
 NO INVESTIGATION INTO WHAT TYPE OF FLOOR SYSTEM THIS
 BUILDING HAS BY A STRUCTURAL ENGINEER AND WHAT WILL
 REQUIRED FOR THE RE-ENFORCEMENT OF THE FLOOR SYSTEM.
 NOTE THIS IS A HIGH RISE BUILDING, BEING A THRESHOLD
 BUILDING WHICH WOULD REQUIRE A THRESHOLD INSPECTOR AS
 WELL. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE:
 107.3.5.MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS
 107.3.5.1.COMMERCIAL BUILDINGS
 107.3.5.1.1BUILDING REVIEW
 8) STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 WALL SYSTEMS
 FLOOR SYSTEMS
 CEILING SYSTEMS (POURED CONCRETE)
 THRESHOLD INSPECTION PLAN
  
 5D) SHEET A.5.0.1. DETAILS INDICATE WITHIN THE NEW
 CONCRETE AND BLOCK WALL SHOWER THERE IS TO BE CEMENT
 BOARD AND METAL FURRING. THE PLANS INDICATE SEE I. D.
 DRAWINGS. THESE DETAILS SHOULD BE WITH THE
 ARCHITECTURAL AND OR WITH STRUCTURAL SHEETS. PLEASE
 IDENTIFY WHERE THESE DETAILS CAN BE FOUND. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-06-19 Cont ID  
Sent By jpearson Date 2020-06-19 Time 15:52 Rev Time 0.00
Received By jpearson Date 2020-06-19 Time 15:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-04-10 Cont ID  
Sent By jpearson Date 2020-04-10 Time 11:27 Rev Time 0.00
Received By jpearson Date 2020-04-10 Time 08:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-06 Cont ID  
Sent By pleduc Date 2020-07-06 Time   Rev Time 0.00
Received By pleduc Date 2020-07-06 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-28 Cont ID  
Sent By pleduc Date 2020-05-28 Time   Rev Time 0.00
Received By pleduc Date 2020-05-28 Time 16:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-04-06 Cont ID  
Sent By pleduc Date 2020-04-06 Time   Rev Time 0.00
Received By pleduc Date 2020-04-06 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-13 Cont ID  
Sent By lmarchan Date 2020-07-13 Time 11:38 Rev Time 0.00
Received By lmarchan Date 2020-07-02 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-06-19 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-27 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-04-10 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-30 Time 16:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By medwards Date 2020-06-16 Time 10:05 Rev Time 0.00
Received By medwards Date 2020-06-16 Time 10:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By ccole Date 2020-04-01 Time 12:27 Rev Time 0.00
Received By ccole Date 2020-04-01 Time 07:33 Sent To  
Notes
2020-04-01 12:28:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20030953
 4/1/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M2.02 & M6.01: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE BATHROOMS AND LOCKER ROOMS- TABLE
 404.3.1.1 FBC M.
  
 2) M5.01 & M6.01: PLEASE INDICATE THE SEQUENCE OF
 OPERATION FOR THE EXHAUST SYSTEM IN THE BATHROOMS AND
 LOCKER ROOMS- SECTIONS 401.3 & 501.4 FBC M.
  
 3) M2.01, M2.02: PLEASE PLACE A NOTE ON THE PLAN TO
 INDICATE THERE IS AN ABOVE CEILING RETURN AIR PLENUM,
 AND NOTE THE RESTRICTIONS ON COMBUSTIBLE MATERIALS IN
 THE SPACE- SECTION 602 FBC M
  
 4) M2.01, M2.02, & M6.01: PLEASE CLARIFY HOW THE RETURN
 AIR PLENUM IS COMMUNICATING WITH THE AIR HANDLER-
 SECTION 601.6. A) INDICATE ON SHEET M2.01 WHICH AIR
 HANDLER OR SYSTEM IS SUPPLYING THE NEW ROOMS AND, AND
 WHICH FAN OR SYSTEM IS EXHAUSTING THE NEW ROOMS-
 SECTION 107.2.1 WPB.
  
 5) M2.02: THERE IS A MISSING FIRE DAMPER AT THE
 PENETRATION OF THE 8" DUCT THROUGH THE SHOWER ROOM
 WALL- SECTION 607.5.2 FBC M.
  
 6) M2.02 & M6.01: THE TRANSFER GRILL DIMENSIONS ON THE
 PLANS DO NOT MATCH THE DIMENSIONS IN THE AIR
 DISTRIBUTION SCHEDULE- SECTION 107.2.1 WPB.
  
 7) M9.03: SHOW ON THE PLAN WHICH DUCT WILL BE FIRE
 WRAPPED PER THE DETAIL ON THE PLAN- SECTION 107.2.1
 WPB.
  
 8) VERIFY THAT THE AIR HANDLER SYSTEM SUPPLYING THE NEW
 OCCUPANCY HAS BEEN EQUIPPED WITH A DUCT SMOKE DETECTOR
 AND IDENTIFY THE LOCATION- SECTION 606.2.1 FBC M.
  
 9) INDICATE IN THE NOTES THAT A TEST AND BALANCE REPORT
 WILL BE PROVIDED FOR FINAL APPROVAL AND OCCUPANCY OF
 THE SPACE- SECTION C408.2.2 FBC EC.
  
 10) SUBMIT AC SYSTEM SIZING CALCULATIONS FOR THE NEW
 TENANT SPACE THAT WAS PREVIOUSLY UNCONDITIONED- SECTION
 C403.2.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-07 Cont ID  
Sent By ccole Date 2020-07-07 Time 09:12 Rev Time 0.00
Received By ccole Date 2020-07-06 Time 10:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-06-15 Cont ID  
Sent By ccole Date 2020-06-15 Time 15:18 Rev Time 0.00
Received By ccole Date 2020-06-15 Time 11:10 Sent To  
Notes
2020-06-15 15:30:012ND REVIEW FBC-2017 PLUMBING
 PERMIT #20030953
 6/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE 1ST REVIEW COMMENTS LISTED BELOW WILL BE MARKED AS
 COMPLIED OR FAILED. NOTES ARE PROVIDED FOR FAILED
 COMMENTS.
  
 1) FAILED. SHEET A301, A303: PROVIDE THE REQUIRED
 DIMENSIONS OF ALL THE CLEAR FLOOR SPACE DIAGRAMS FOR
 THE FIXTURES SHOWN ON THE DRAWINGS- WATER CLOSET-
 SECTION 604.3.2, URINALS- 605.3, LAVATORIES AND SINKS-
 606.2, SHOWER- 608.2.2.1, BENCHES -903.2 & 305.3 FBC
 ACC. CLEAR FLOOR SPACES FOR SHOWERS NOT PROVIDED.
  
 2) FAILED. A301, 303: PROVIDE THE DIAMETERS OF THE
 TURNING CIRCLES- SECTION 304.3.1 FBC ACC. DIAMETERS
 PROVIDED HOWEVER THE CIRCLES ARE OVERLAPPING THE URINAL
 PARTITIONS. PLEASE SHOW THE KNEE AND TOES CLEARANCES AT
 THE PARTITONS- SECTION 304.3.1 FBC ACC.
  
 3) FAILED. A301, 303: IT APPEARS THE DOORS WILL SWING
 INTO THE REQUIRED CLEAR FLOOR SPACES AT THE SHOWERS AND
 THE STEAM ROOM BENCHES- SEE SECTION 603.2.3 EXCEPTION 2
 FBC ACC. CLEAR FLOOR SPACE DIAGRAMS BEYOND THE ARCS OF
 THE DOOR SWINGS ARE SHOWN OVERLAPPING THE SHOWER
 THRESHOLDS WHICH IS NON-COMPLIANT PER SECTION 305.2 FBC
 ACC- CHANGES IN LEVEL ARE NOT ALLOWED.
  
 4) COMPLIED. A301, 303, DETAILS 6 & 2: THE HEIGHT OF
 THE LAVATORY FRONT RIM SHALL BE 34"- SECTION 606.3 FBC
 ACC. A) SHOW THE HEIGHT OF THE MIRROR BOTTOM EDGE FROM
 THE FINISHED FLOOR- SECTION 603.3 FBC ACC.
  
 5) FAILED. A301, 303: THE TOILET AND SHOWER ROOM GRAB
 BARS SHALL BE HORIZONTALLY POSITIONED A MINIMUM 33" AND
 MAXIMUM 36" ABOVE THE FINISHED FLOORS MEASURED TO THE
 TOP OF THE GRIPPING SURFACES- SECTION 609.4 FBC ACC.
 PLEASE CORRECT. MAXIMUM HEIGHT PROVIDED, THE REQUIRED
 MINIMUM 33? DIMENSION WAS NOT PROVIDED.
  
 6) COMPLIED. A301, 303: THE SHOWER GRAB BARS SHALL BE
 SPACED A MAXIMUM 6" FROM THE ADJACENT WALLS- SECTION
 608.3.2 FBC ACC.
  
 7) FAILED. A301, 303, DETAILS 3 & 8, & 4 & 11: SHOW THE
 HEIGHTS OF THE SHOWER CONTROLS ABOVE THE FINISHED
 SHOWER FLOORS- SECTION 608.5.2 FBC ACC. A) THE SHOWER
 SPRAY UNITS AT 5'7"ARE EXCEEDING THE MAXIMUM 48"
 MOUNTING HEIGHTS ABOVE THE FINISHED FLOORS. THE
 CONTROLS TO BE CENTERED AND ABOVE THE MAXIMUM 48?
 HEIGHT. PLEASE SEE SECTION 608.5.2 AND FIGURE 608.5.3
 FBC ACC.
  
 8) COMPLIED A301, 303, DETAILS 3 & 8, & 4 & 11:
 INDICATE COMPLIANCE WITH SECTION 608.6 FBC ACC. A
 SHOWER SPRAY UNIT WITH A HOSE 59 INCHES (1500 MM) LONG
 MINIMUM THAT CAN BE USED BOTH AS A FIXED-POSITION
 SHOWER HEAD AND AS A HAND-HELD SHOWER SHALL BE
 PROVIDED. THE SHOWER SPRAY UNIT SHALL HAVE AN ON/OFF
 CONTROL WITH A NON-POSITIVE SHUT-OFF. IF AN
 ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120 DEGREES F MAXIMUM. EXCEPTION: A FIXED
 SHOWER HEAD LOCATED AT 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE SHOWER FINISH FLOOR SHALL BE PERMITTED
 INSTEAD OF A HAND-HELD SPRAY UNIT IN FACILITIES THAT
 ARE NOT MEDICAL CARE FACILITIES, LONG-TERM CARE
 FACILITIES, TRANSIENT LODGING GUEST ROOMS, OR
 RESIDENTIAL DWELLING UNITS.
  
 9) COMPLIED. A301, 303, DETAILS 6 & 7: SHOW THE
 REQUIRED TOE AND KNEE CLEARANCES AT THE SINK- SECTIONS
 306.2 & 306.3 FBC ACC.
  
 10) PARTIALLY COMPLIED. THE EWC-1 SHALL MEET
 ACCESSIBILITY REQUIREMENTS AS OUTLINED IN SECTIONS 305
 THROUGH 309 FBC ACC. PROVIDE DETAILS ON THE PLAN TO
 SHOW COMPLIANCE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS. THE CUT SHEET FOR THE DF DOES NOT
 INDICATE THE FIXTURE IS ADA OR FL. ACCESSIBILITY CODE
 COMPLIANT. PLEASE PLACE NOTES ON THE PLANS TO INDICATE
 THE MINIMUM TWO ACCESSIBLE DRINKING FOUNTAINS ARE BEING
 PROVIDED ON THE SAME FLOOR AS THE NEW OCCUPANCY-
 SECTION 211.2 A& 211.3 FBC ACC.
  
 11) COMPLIED P0.01: PLEASE INCLUDE THE STEAM GENERATORS
 IN THE FIXTURE SCHEDULE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 107.2.1 WPB.
  
 12) PARTIALLY COMPLIED P4.01 & P9.01: BACKFLOW
 PREVENTERS ARE REQUIRED FOR THE WATER SUPPLY PIPING TO
 THE STEAM GENERATORS. PLEASE INDICATE THEM IN THE
 DRAWINGS- SECTION 608.3 FBC P. PLEASE INDICSTE WHICH
 TYPE OF BACKFLOW PREVENTER DEVICE WILL BE PROVIDED AND
 ADD THE MAKE AND MODEL TO THE FIXTURE OR DEVICE
 SCHEDULE.
  
 13) FAILED. P4.01 & P9.01: PLEASE SHOW THE LOCATIONS OF
 SHUT OFF VALVES, WATER HAMMER ARRESTORS, MIXING VALVES
 AND ANY OTHER REQUIRED WATER CONTROLS- SECTION 107.2.1
 WPB AND SECTIONS 604.9 & 606.2 FBC P. IN RESPONSE TO
 THIS COMMENT THE AOR REFERS TO THE FIXTURE SCHEDULE.
 PLEASE PROVIDE LOCATIONS AND SYMBOLS ON THE SHEETS FOR
 THE WATER HAMMER ARRESTORS FOR WATER SUPPLY LINES TO
 THE BOTTLE FILLER, LAVATORIES, URINALS, FLUSHOMETER
 VALVERS, AND ICE MAKER. A BACKFLOW PREVENTER IS ALSO
 REQUIRED FOR THE ICE MAKER WATER LINE.
  
 14) COMPLIED. P4.01 & P9.01: PLEASE INDICATE HOW
 TEMPERED WATER WILL BE REQUIRED TO THE LAVATORIES-
 SECTION 416.5. PLEASE NOTE THAT TEMPERATURE LIMITING
 DEVICES SHALL CONFORM TO ASSE 1070- SECTION 607.1.2 FBC
 P, AND WHERE REQUIRED SHALL BE INSTALLED AT POINT OF
 USE- SECTION 607.1.1.
  
 15) COMPLIED. P4.01, P5.01, & P9.02: THE WATER HEATER
 DETAIL INDICATES THE RELIEF VALVE DISCHARGE PIPING
 DRAINING INTO A FLOOR DRAIN. THIS DOES NOT APPEAR TO BE
 CONSISTENT WITH THE PLUMBING DRAWINGS. PLEASE SHOW HOW
 THE PIPING AND PAN DRAIN PIPING WILL BE DISCHARGED TO
 THE EXTERIOR OF THE BUILDING- SECTION 504.7.2 FBC P.
  
 16) COMPLIED. P4.01: REFER TO GENERAL NOTE #2 AND
 PROVIDE WATER PIPING AND DWV SPECIFICATIONS ON THE
 PLANS- SECTIONS 303.1 & 307.6 FBC P.
  
 18) FAILED. P9.01 & P9.02: SHOW REQUIRED TRAP SEAL
 PROTECTION FOR THE FLOOR DRAINS- SECTION 1002.4.1 FBC
 P. TRAP PRIMERS FOR THE FLOOR DRAINS (FD-1) AND THE
 TRENCH DRAINS (TD-1, TD-2, & TD-3) NOT SHOWN IN THE
 ISOMETRIC. PLEASE NOTE FD-1 IS NOT IN THE FIXTURE
 SCHEDULE.
  
 19) COMPLIED. P9.02: TD-1 AND THE DRAIN FROM THE MEN'S
 STEAM GENERATOR DO NOT APPEAR TO BE MAKING A DRAIN AND
 VENT CONNECTION INTO THE SYSTEM- SECTION 107.2.1 WPB.
  
 20) FAILED. P9.02: PLEASE LABEL THE FIXTURES COLLECTING
 THE CONDENSATE FROM THE STEAM GENERATORS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT TRAP SEAL PROTECTION MAY
 BE REQUIRED- SECTION 1002.4.1 FBC P. INDIRECT WASTE
 RECEPTORS NOT IN THE FIXTURE SCHEDULE.
  
 21) PARTIALLY COMPLIED. P9.02: SHOW THE LOCATIONS OF
 THE REQUIRED SERVICE SINK AND PROVIDE PLUMBING DETAILS-
 TABLE 403.1 FBC P. PLEASE PLACE A NOTE ON THE PLAN
 INDICATING SERVICE SINK LOCATION.
  
 22) COMPLIED. P0.01: PROVIDE THE EFFICIENCY RATING OF
 EWH-1 & 2 AND SUBMIT MANUFACTURER'S SPECIFICATIONS TO
 VERIFY COMPLIANCE- SEE TABLE C404.2 FBC EC.
  
 23) COMPLIED. P4.01: SHOW HOW ACCESS FOR THE SERVICE
 AND REPLACEMENT OF THE WATER HEATERS WILL BE PROVIDED-
 SECTION 306.1 FBC M.
  
 24) COMPLIED. P0.01: VERIFY THE CIRCULATION PUMP HAS
 CONTROLS THAT WILL TURN OFF THE PUMP WHEN THE WATER IN
 THE CIRCULATION LOOP HAS REACHED THE DESIRED
 TEMPERATURE, AND WHEN THERE IS NO DEMAND FOR HOT WATER-
 SECTION C404.6.1 FBC EC.
  
 25) COMPLIED. PROVIDE WATER PIPING INSULATION
 SPECIFICATIONS IN ACCORDANCE WITH SECTION C404.4 FBC
 EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-06 Cont ID  
Sent By ccole Date 2020-04-06 Time 09:14 Rev Time 0.00
Received By ccole Date 2020-04-01 Time 07:36 Sent To  
Notes
2020-04-06 09:42:331ST REVIEW FBC-2017 PLUMBING
 PERMIT #20030953
 4/6/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A301, A303: PROVIDE THE REQUIRED DIMENSIONS OF
 ALL THE CLEAR FLOOR SPACE DIAGRAMS FOR THE FIXTURES
 SHOWN ON THE DRAWINGS- WATER CLOSET- SECTION 604.3.2,
 URINALS- 605.3, LAVATORIES AND SINKS- 606.2, SHOWER-
 608.2.2.1, BENCHES -903.2 & 305.3 FBC ACC.
  
 2) A301, 303: PROVIDE THE DIAMETERS OF THE TURNING
 CIRCLES- SECTION 304.3.1 FBC ACC.
  
 3) A301, 303: IT APPEARS THE DOORS WILL SWING INTO THE
 REQUIRED CLEAR FLOOR SPACES AT THE SHOWERS AND THE
 STEAM ROOM BENCHES- SEE SECTION 603.2.3 EXCEPTION 2 FBC
 ACC.
  
 4) A301, 303, DETAILS 6 & 2: THE HEIGHT OF THE LAVATORY
 FRONT RIM SHALL BE 34"- SECTION 606.3 FBC ACC. A) SHOW
 THE HEIGHT OF THE MIRROR BOTTOM EDGE FROM THE FINISHED
 FLOOR- SECTION 603.3 FBC ACC.
  
 5) A301, 303: THE TOILET AND SHOWER ROOM GRAB BARS
 SHALL BE HORIZONTALLY POSITIONED A MINIMUM 33" AND
 MAXIMUM 36" ABOVE THE FINISHED FLOORS MEASURED TO THE
 TOP OF THE GRIPPING SURFACES- SECTION 609.4 FBC ACC.
 PLEASE CORRECT.
  
 6) A301, 303: THE SHOWER GRAB BARS SHALL BE SPACED A
 MAXIMUM 6" FROM THE ADJACENT WALLS- SECTION 608.3.2 FBC
 ACC.
  
 7) A301, 303, DETAILS 3 & 8, & 4 & 11: SHOW THE HEIGHTS
 OF THE SHOWER CONTROLS ABOVE THE FINISHED SHOWER
 FLOORS- SECTION 608.5.2 FBC ACC. A) THE SHOWER SPRAY
 UNITS AT 5'7"ARE EXCEEDING THE MAXIMUM 48" MOUNTING
 HEIGHTS ABOVE THE FINISHED FLOORS.
  
 8) A301, 303, DETAILS 3 & 8, & 4 & 11: INDICATE
 COMPLIANCE WITH SECTION 608.6 FBC ACC. A SHOWER SPRAY
 UNIT WITH A HOSE 59 INCHES (1500 MM) LONG MINIMUM THAT
 CAN BE USED BOTH AS A FIXED-POSITION SHOWER HEAD AND AS
 A HAND-HELD SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY
 UNIT SHALL HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE
 SHUT-OFF. IF AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A
 VERTICAL BAR IS USED, THE BAR SHALL BE INSTALLED SO AS
 NOT TO OBSTRUCT THE USE OF GRAB BARS. SHOWER SPRAY
 UNITS SHALL DELIVER WATER THAT IS 120 DEGREES F
 MAXIMUM.
 EXCEPTION: A FIXED SHOWER HEAD LOCATED AT 48 INCHES
 (1220 MM) MAXIMUM ABOVE THE SHOWER FINISH FLOOR SHALL
 BE PERMITTED INSTEAD OF A HAND-HELD SPRAY UNIT IN
 FACILITIES THAT ARE NOT MEDICAL CARE FACILITIES,
 LONG-TERM CARE FACILITIES, TRANSIENT LODGING GUEST
 ROOMS, OR RESIDENTIAL DWELLING UNITS.
  
 9) A301, 303, DETAILS 6 & 7: SHOW THE REQUIRED TOE AND
 KNEE CLEARANCES AT THE SINK- SECTIONS 306.2 & 306.3 FBC
 ACC.
  
 10) THE EWC-1 SHALL MEET ACCESSIBILITY REQUIREMENTS AS
 OUTLINED IN SECTIONS 305 THROUGH 309 FBC ACC. PROVIDE
 DETAILS ON THE PLAN TO SHOW COMPLIANCE AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS.
  
 11) P0.01: PLEASE INCLUDE THE STEAM GENERATORS IN THE
 FIXTURE SCHEDULE AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 107.2.1 WPB
  
 12) P4.01 & P9.01: BACKFLOW PREVENTERS ARE REQUIRED FOR
 THE WATER SUPPLY PIPING TO THE STEAM GENERATORS. PLEASE
 INDICATE THEM IN THE DRAWINGS- SECTION 608.3 FBC P.
  
 13) P4.01 & P9.01: PLEASE SHOW THE LOCATIONS OF SHUT
 OFF VALVES, WATER HAMMER ARRESTORS, MIXING VALVES AND
 ANY OTHER REQUIRED WATER CONTROLS- SECTION 107.2.1 WPB
 AND SECTIONS 604.9 & 606.2 FBC P.
  
 14) P4.01 & P9.01: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE REQUIRED TO THE LAVATORIES- SECTION 416.5.
 PLEASE NOTE THAT TEMPERATURE LIMITING DEVICES SHALL
 CONFORM TO ASSE 1070- SECTION 607.1.2 FBC P, AND WHERE
 REQUIRED SHALL BE INSTALLED AT POINT OF USE- SECTION
 607.1.1
  
 15) P4.01, P5.01, & P9.02: THE WATER HEATER DETAIL
 INDICATES THE RELIEF VALVE DISCHARGE PIPING DRAINING
 INTO A FLOOR DRAIN. THIS DOES NOT APPEAR TO BE
 CONSISTENT WITH THE PLUMBING DRAWINGS. PLEASE SHOW HOW
 THE PIPING AND PAN DRAIN PIPING WILL BE DISCHARGED TO
 THE EXTERIOR OF THE BUILDING- SECTION 504.7.2 FBC P.
  
 16) P4.01: REFER TO GENERAL NOTE #2 AND PROVIDE WATER
 PIPING AND DWV SPECIFICATIONS ON THE PLANS- SECTIONS
 303.1 & 307.6 FBC P.
  
 18) P9.01 & P9.02: SHOW REQUIRED TRAP SEAL PROTECTION
 FOR THE FLOOR DRAINS- SECTION 1002.4.1 FBC P.
  
 19) P9.02: TD-1 AND THE DRAIN FROM THE MEN'S STEAM
 GENERATOR DO NOT APPEAR TO BE MAKING A DRAIN AND VENT
 CONNECTION INTO THE SYSTEM- SECTION 107.2.1 WPB. PLEASE
 NOTE THAT AN INDIRECT
  
 20) P9.02: PLEASE LABEL THE FIXTURES COLLECTING THE
 CONDENSATE FROM THE STEAM GENERATORS- SECTION 107.2.1
 WPB. PLEASE NOTE THAT TRAP SEAL PROTECTION MAY BE
 REQUIRED- SECTION 1002.4.1 FBC P.
  
 21) P9.02: SHOW THE LOCATIONS OF THE REQUIRED SERVICE
 SINK AND PROVIDE PLUMBING DETAILS- TABLE 403.1 FBC P.
  
 22) P0.01: PROVIDE THE EFFICIENCY RATING OF EWH-1 & 2
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS TO VERIFY
 COMPLIANCE- SEETABLE C404.2 FBC EC.
  
 23) P4.01: SHOW HOW ACCESS FOR THE SERVICE AND
 REPLACEMNT OF THE WATER HEATERS WILL BE PROVIDED-
 SECTION 306.1 FBC M.
  
 24) P0.01: VERIFY THE CIRCULATION PUMP HAS CONTROLS
 THAT WILL TURN OFF THE PUMP WHEN THE WATER IN THE
 CIRCULATION LOOP HAS REACHED THE DESIRED TEMPERATURE,
 AND WHEN THERE IS NO DEMAND FOR HOT WATER- SECTION
 C404.6.1 FBC EC.
  
 25) PROVIDE WATER PIPING INSULATION SPECIFICATIONS IN
 ACCORDANCE WITH SECTION C404.4 FBC EC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2021-01-20 Time   Rev Time 0.00
Received By   Date 2021-01-20 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-06 Cont ID  
Sent By jwitmer Date 2020-07-06 Time 09:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-06-16 Cont ID  
Sent By medwards Date 2020-06-16 Time 10:18 Rev Time 0.00
Received By medwards Date 2020-06-16 Time 10:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-09 Cont ID  
Sent By jpearson Date 2020-04-09 Time 16:47 Rev Time 0.00
Received By jpearson Date 2020-04-09 Time 16:47 Sent To  
Notes
2020-04-09 16:41:30ALL SHEETS HAVE PROPER THIRD-PARTY VERIFICATION.
 HOWEVER, ON THE MECHANICAL AND PLUMBING SHEETS THE
 DIGITAL SIGNATURE IS NOT VISIBLE. ANY NEW SHEETS
 SUBMITTED NEXT CYCLE WILL NEED TO BE CHECKED. WPB FBC
 105.1