Plan Review Details - Permit 20030898
Plan Review Stops For Permit 20030898
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-11 Cont ID  
Sent By pvalenti Date 2020-08-11 Time 09:51 Rev Time 0.00
Received By pvalenti Date 2020-08-11 Time 09:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-18 Cont ID  
Sent By pvalenti Date 2020-05-18 Time 15:58 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 13:50 Sent To  
Notes
2020-05-18 16:10:42PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC A FIGURE 404.2.4.1, ON SHEET A-1 (LIFE SAFETY),
 ALONG EXIT PATH "A" THE INTERIOR DOOR DOES NOT MEET THE
 (18") MANEUVERING CLEARANCE REQUIREMENTS OF ACCESSIBLE
 ROUTES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By pvalenti Date 2020-03-24 Time 09:16 Rev Time 0.00
Received By pvalenti Date 2020-03-24 Time 09:16 Sent To  
Notes
2020-03-24 09:29:05PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE RESUBMIT AND CLARIFY WHERE AND
 WHAT THE CHANGES ARE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 15:27 Rev Time 0.00
Received By jleahy Date 2020-10-02 Time 15:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-08-04 Cont ID  
Sent By jleahy Date 2020-08-04 Time 16:28 Rev Time 0.00
Received By jleahy Date 2020-08-04 Time 15:03 Sent To  
Notes
2020-08-04 16:37:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1
  
 RISER DOES NOT SHOW MAIN DISCONNECT AS STATED IN THE
 NOTES
  
 400A FUSES CAN NOT PROTECT 3/0 AND 1/0 CONDUCTORS UNDER
 THESE CONDITIONS, FEEDING SUB PANELS MUST BE TAPS?
 240.21 WHICH ONE 10' 25' RULE?
  
 CONDUCTORS TO FPL COPPER OR ALUMINUMU?
  
 VALUE OF PERMIT HAS NOT BEEN ADJUSTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-19 Cont ID  
Sent By jpearson Date 2020-05-19 Time 15:53 Rev Time 0.00
Received By jpearson Date 2020-05-19 Time 09:16 Sent To  
Notes
2020-05-19 15:06:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE HAS BEEN A SUBSTANTIAL AMOUNT OF WORK ADDED TO
 THE PLANS AND YET THE REVISION FORM INDICATES THAT
 THERE IS NO INCREASE IN THE VALUE OF WORK PERFORMED.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR
 TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC 109.3
 2. WIRE SPECIFIED IN RISER DIAGRAM FOR FEEL TO FPL IS
 NOT SIZED CORRECTLY. FOR A 3 PHASE SERVICE THERE SHOULD
 BE A MINIMUM OF 4 WIRES. ADDITIONALLY, THE WIRE MUST BE
 SIZED FOR THE MAIN OVERCURRENT PROTECTION, WHICH IS
 SHOWN AS 400 AMP. PROVIDE CORRECTION. NEC 250.24(C),
 310.15(B)(16)
 3. RISER DIAGRAM SHOWS FIVE 1/0 CONDUCTORS IN A 2 INCH
 CONDUIT TO FEED PANEL C. THIS CONDUIT IS UNDERSIZED.
 PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C
 4. LOAD CALCULATION SHOWN DOES NOT MATCH THE LOADS
 SHOWN IN PANEL SCHEDULES. PROVIDE ACCURATE LOAD
 CALCULATION INCLUDING ALL LOADS. LOAD FOR PANEL C IS
 NOT REFLECTED ACROSS ALL PHASES. PROVIDE CORRECTION.
 NEC 220
 5. SHEET E-2 SPECIFIES THE 2011 NEC AS BASIS FOR
 DESIGN. THIS IS NOT THE CURRENT CODE. PROVIDE
 CORRECTION. FBC PREFACE, ALSO SEE ABOVE.
 6. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By jpearson Date 2020-03-26 Time 08:51 Rev Time 0.00
Received By jpearson Date 2020-03-26 Time 08:51 Sent To  
Notes
2020-03-26 08:19:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THERE ARE NO REVISIONS INDICATED ON PLAN. PROVIDE
 NARRATIVE OF CHANGES AND CLOUD CHANGES ON PLAN. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-07-21 Cont ID  
Sent By pleduc Date 2020-07-21 Time   Rev Time 0.00
Received By pleduc Date 2020-07-21 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-14 Cont ID  
Sent By pleduc Date 2020-05-14 Time   Rev Time 0.00
Received By pleduc Date 2020-05-14 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By pleduc Date 2020-03-20 Time   Rev Time 0.00
Received By pleduc Date 2020-03-20 Time 11:13 Sent To  
Notes
2020-03-20 11:17:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS DO NOT INDICATE WHAT THE
 REVISIONS ARE AND WHERE THEY ARE LOCATED.
  
 PER NFPA 1
  
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE
 REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS,
 ARE LOCATED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-12-09 Cont ID  
Sent By lmarchan Date 2020-12-09 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2020-12-03 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 15:28 Rev Time 0.00
Received By jleahy Date 2020-09-26 Time 07:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-11 Cont ID  
Sent By jleahy Date 2020-08-11 Time 09:56 Rev Time 0.00
Received By pvalenti Date 2020-07-20 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-28 Cont ID  
Sent By lmarchan Date 2020-05-28 Time 07:50 Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 14:44 Sent To  
Notes
2020-05-12 10:30:15CONVERTED TO DIGITAL. JG.
 05/12/2020 SENT TO TEQUESTA FOR SCANNING. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-17 Cont ID  
Sent By shill Date 2020-04-14 Time 08:47 Rev Time 0.00
Received By shill Date 2020-03-18 Time 09:54 Sent To  
Notes
2020-04-04 15:42:56B07
2020-03-19 09:54:49B07

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-07-27 Cont ID  
Sent By medwards Date 2020-07-27 Time 14:27 Rev Time 0.00
Received By medwards Date 2020-07-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-05-20 Cont ID  
Sent By medwards Date 2020-05-20 Time 08:51 Rev Time 0.00
Received By medwards Date 2020-05-20 Time 08:51 Sent To  
Notes
2020-05-20 08:56:25PLEASE SEE ORIGINAL REVIEWERS COMMENTS BELOW. THIS
 NEEDS TO BE ADDRESSED BEFORE THIS PROJECT CAN BE
 APPROVED.
 YOU SHOW NO COOLING CALCULATIONS FOR THIS PROJECT. THE
 HEATING CALCULATIONS SHOW 48,189 BTU, THIS WOULD
 REQUIRE A 4 TON SYSTEM ONLY. THE PLANS SHOW A 5 TON AND
 A 2.5 TON. PLEASE PROVIDE JUSTIFICATION FOR THESE SIZE
 UNITS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  
 ORIGINAL REVIEWER COMMENTS: 1ST REVIEW FBC-2017
 MECHANICAL
 PERMIT #20020898
 3/23/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 & M-2: THERE IS NO JUSTIFICATION FOR THE
 ADDED 2.5 TON AC SYSTEM IN THE TENANT SPACE. THERE
 APPEARS TO BE NO INCREASE IN SQUARE FOOTAGE OR HEAT
 LOAD FOR THE SPACE. PLEASE NOTE THAT REVISED AC AND
 ENERGY CALCULATIONS ARE REQUIRED- SECTIONS C403.2.1,
 C101.5, & C401.2 FBC EC
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By ccole Date 2020-03-23 Time 08:46 Rev Time 0.00
Received By ccole Date 2020-03-23 Time 08:26 Sent To  
Notes
2020-03-23 09:05:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020898
 3/23/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1 & M-2: THERE IS NO JUSTIFICATION FOR THE
 ADDED 2.5 TON AC SYSTEM IN THE TENANT SPACE. THERE
 APPEARS TO BE NO INCREASE IN SQUARE FOOTAGE OR HEAT
 LOAD FOR THE SPACE. PLEASE NOTE THAT REVISED AC AND
 ENERGY CALCULATIONS ARE REQUIRED- SECTIONS C403.2.1,
 C101.5, & C401.2 FBC EC
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By jesmith Date 2020-03-27 Time 11:02 Rev Time 0.00
Received By ccole Date 2020-03-27 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-10-02 Cont ID  
Sent By jleahy Date 2020-10-02 Time 15:28 Rev Time 0.00
Received By jleahy Date 2020-10-02 Time 15:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-08-05 Cont ID  
Sent By medwards Date 2020-08-05 Time 08:04 Rev Time 0.00
Received By medwards Date 2020-07-27 Time 14:31 Sent To  
Notes
2020-07-27 14:32:13PLEASE ADDRESS PREVIOUS COMMENTS ON THE SIGNATURE
 REVIEWS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-18 Cont ID  
Sent By pvalenti Date 2020-05-18 Time 16:16 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 16:16 Sent To  
Notes
2020-05-18 16:32:43PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, F.S. 471 AND 481, THE PLANS NEED TO BE
 SUBMITTED DIGITALLY TO PROJECT DOX WITH DESIGN
 PROFESSIONAL'S SIGNATURES/SEALS VERIFIED BY THIRD PARTY
 VERIFICATION.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-18 Cont ID  
Sent By jgomez Date 2020-05-18 Time 14:46 Rev Time 0.00
Received By pvalenti Date 2020-05-18 Time 14:02 Sent To  
Notes
2020-05-13 14:15:25CONVERTED TO DIGITAL.
 DRAWINGS WITH ARCHITECT'S ORIGINAL SEAL/SIGNATURE ON
 CITY'S FILE. JG
  
 ENVELOPE COMPLIANCE CERTIFICATE AND COMMENTS RESPONSE
 LETTER DON'T HAVE ORIGINAL SEAL/SIGNATURE. THEY ARE
 COPIES. JG.

Review Stop Z ZONING
Rev No 5 Status P Date 2020-12-09 Cont ID  
Sent By llouie Date 2020-12-09 Time   Rev Time 0.00
Received By llouie Date 2020-12-09 Time   Sent To  
Notes
2020-12-09 10:16:03MASTER PERMIT #18050987.

Review Stop Z ZONING
Rev No 4 Status F Date 2020-10-01 Cont ID  
Sent By llouie Date 2020-10-01 Time   Rev Time 0.00
Received By llouie Date 2020-10-01 Time   Sent To  
Notes
2020-10-01 13:41:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) IT IS NOT CLEAR IN THE RESPONSE LETTER TO STAFF'S
 COMMENTS IF A SEPARATE PERMIT WILL BE SUBMITTED FOR THE
 BICYCLE RACK. PLEASE CLARIFY IN THE PLANS AND NOTE.
  
 [7/22/2020 MODIFIED COMMENT: BICYCLE RACK SHALL BE
 INSTALLED PRIOR TO FINAL CERTIFICATE OF COMPLETION IF
 THE BICYCLE RACK IS TO BE PROVIDED BY A SEPARATE
 PERMIT.]
  
  
 2.) PARKING STALL STRIPING DETAIL IS INCONSISTENT WITH
 THE CITY'S STANDARDS. THE CITY'S PARKING STALL PAINTING
 DETAIL WAS SENT TO THE ARCHITECT ON 7/22/2020 TO
 CORRECT THE PLANS.
  
 [7/22/2020 REPEAT COMMENT: NOT ADDRESSED. PARKING STALL
 STRIPING DETAIL IS STILL INCONSISTENT WITH THE STALL
 STRIPING STANDARDS OF THE CITY.]
  
  
 3.) PER LANDSCAPING'S COMMENTS (PERMIT #20050261), A
 72-INCH GARDEN WALL MUST BE IN PLACE FOR THE WEST
 PROPERTY LINE SEPARATING THE USE FROM ADJACENT
 RESIDENTIAL PER ZLDR S.94-221(D)93). THIS CAN BE A WALL
 OR A FENCE. THE ALTERNATIVE IS TO KEEP THE CHAIN LINK
 FENCE AND ADD A HEDGE FOR SCREENING. A SEPARATE PERMIT
 FOR THE WALL/FENCE IS REQUIRED IF A WALL OR A FENCE IS
 PROPOSED.
  
 [7/22/2020 REPEAT COMMENT: THE SITE PLAN DOES NOT SHOW
 THAT A GARDEN WALL WILL BE PROVIDED ALONG THE ENTIRE
 WEST PROPERTY LINE. ADDITIONALLY, THE ADDITION OF THE
 GARDEN WALL MUST BE REFLECTED IN A CONCURRENT LANDSCAPE
 PERMIT RESUBMITTAL (NOT PROVIDED), SHOWING CONSISTENCY
 WITH THE PERMIT PLANS.]
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MASTER PERMIT #18050987
  
 * LANDSCAPE PERMIT #20050261
  
 * ZONE: BMUD-TYPE II
  

Review Stop Z ZONING
Rev No 3 Status F Date 2020-07-22 Cont ID  
Sent By llouie Date 2020-07-22 Time   Rev Time 0.00
Received By llouie Date 2020-07-22 Time   Sent To  
Notes
2020-07-22 10:56:14** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) DETAIL OF THE BICYCLE RACK REQUIRED IN THE PLANS.
 THE CITY'S BICYCLE PARKING STANDARDS MANUAL WAS SENT TO
 THE ARCHITECT ON 7/22/2020. THE ARCHITECT WAS ADVISED
 TO PROVIDE A BICYCLE RACK THAT IS CONSISTENT WITH THE
 CITY'S STANDARDS. [5/27/2020 MODIFIED AND REPEAT
 COMMENT]
  
 2.) PROPOSED BICYCLE RACK IN THE SITE PLAN SHALL BE
 CONSISTENT WITH THE DIMENSIONAL STANDARDS OF THE CITY'S
 BICYCLE PARKING. THE DETAIL IN THE SITE PLAN DOES NOT
 HAVE DIMENSIONS NOR IS IT CONSISTENT WITH THE CITY'S
 STANDARDS FOR BICYCLE PARKING.
  
 3.) PARKING STALL STRIPING DETAIL IS INCONSISTENT WITH
 THE CITY'S STANDARDS. THE CITY'S PARKING STALL PAINTING
 DETAIL WAS SENT TO THE ARCHITECT ON 7/22/2020 TO
 CORRECT IN THE PLANS.
  
 4.) PER LANDSCAPING'S COMMENTS (PERMIT #20050261), A
 72-INCH GARDEN WALL MUST BE IN PLACE FOR THE WEST
 PROPERTY LINE SEPARATING THE USE FROM ADJACENT
 RESIDENTIAL PER ZLDR S.94-221(D)(3). THIS CAN BE A WALL
 OR A FENCE. THE ALTERNATIVE IS TO KEEP THE CHAIN LINK
 FENCE AND ADD A HEDGE FOR SCREENING. A SEPARATE PERMIT
 FOR THE WALL/FENCE IS REQUIRED IF A WALL OR FENCE IS
 PROPOSED.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MASTER PERMIT #18050987
  
 * LANDSCAPE PERMIT #20050261
  
 * ZONE: BMUD-TYPE II
  

Review Stop Z ZONING
Rev No 2 Status F Date 2020-05-27 Cont ID  
Sent By llouie Date 2020-05-27 Time   Rev Time 0.00
Received By llouie Date 2020-05-27 Time   Sent To  
Notes
2020-05-27 20:37:29** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REVISED PLAN SHOWS A BICYCLE WAVE RACK. THE WAVE
 RACK IS NOT PERMITTED. PLEASE REVISE WITH A RACK THAT
 IS CONSISTENT WITH THE CITY'S STANDARDS FOR BICYCLE
 PARKING DESIGN.
  
 2.) BICYCLE RACK SHALL BE LOCATED AS CLOSE AS POSSIBLE
 TO THE MAIN ENTRANCE OF THE BUILDING. THE REVISED PLAN
 SHOWS THAT THE RACK HAS BEEN MOVED TO A LOCATION
 FURTHER AWAY FROM THE ENTRANCE OF THE BUILDING. THE NEW
 LOCATION IS NOT ACCEPTABLE.
  
 3.) A RAMP HAS BEEN ADDED TO THE SITE PLAN. DIMENSIONS
 SHALL BE ADDED TO THE PLAN TO DEMONSTRATE THAT THE RAMP
 WILL NOT CONFLICT WITH THE EXISTING DRIVE AISLE.
  
 4.) THE APPLICATION IMPLIES THAT THERE HAS BEEN CHANGES
 TO THE LANDSCAPING. PLEASE CLARIFY WHAT LANDSCAPING
 CHANGES HAVE BEEN MADE. ADDITIONALLY, A SEPARATE
 LANDSCAPE PERMIT IS REQUIRED FOR ANY CHANGES MADE TO
 THE APPROVED LANDSCAPING ON THE PROPERTY.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * MASTER PERMIT #18050987
  
 * ZONE: BMUD-TYPE II
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By rfalcone Date 2020-04-14 Time 15:04 Rev Time 0.00
Received By rfalcone Date 2020-04-14 Time 15:04 Sent To I
Notes
2020-04-14 15:05:14ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 4/14/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. SHOW WHERE THE REVISIONS WERE MADE ON PLAN SETS.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved