Plan Review Details - Permit 20030878
Plan Review Stops For Permit 20030878
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 06:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-19 Cont ID  
Sent By lmarchan Date 2020-03-19 Time 14:50 Rev Time 0.00
Received By lmarchan Date 2020-03-18 Time 09:51 Sent To  
Notes
2020-03-18 09:51:53PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-02 Cont ID  
Sent By rmcdouga Date 2020-04-02 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2020-04-02 Time 06:55 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2020-03-19 Time   Rev Time 0.00
Received By jbaker Date 2020-03-19 Time 14:36 Sent To  
Notes
2020-03-19 14:37:41PERMIT NUMBER 20030878
 1. PER FBC 107.2.1, PROVIDE A SANITARY RISER DIAGRAM
 AND PLAN VIEW SHOWING THE REVISED SANITARY PIPING,
 VENTS AND FIXTURE LAYOUT TO ACCOMMODATE ALL NEW
 APPLIANCES AND FIXTURES THAT REQUIRE SANITARY DRAINAGE.
 2. PER FBC 107.2.1, PROVIDE A DOMESTIC WATER PLAN VIEW
 AND ISOMETRIC SHOWING THE REVISED DOMESTIC WATER
 PIPING, VALVES AND MATERIALS FOR ALL NEW APPLIANCES
 THAT USE HOT AND COLD WATER.
 3. PER FPC 406.2 THE WASTE FROM AN AUTOMATIC CLOTHES
 WASHER SHALL DISCHARGE THROUGH AN AIR BREAK INTO A
 STANDPIPE IN ACCORDANCE WITH SECTION 802.3.3 OR INTO A
 LAUNDRY SINK. THE TRAP AND FIXTURE DRAIN FOR AN
 AUTOMATIC CLOTHES WASHER STANDPIPE SHALL BE NOT LESS
 THAN 2 INCHES IN DIAMETER. THE FIXTURE DRAIN FOR THE
 STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3 INCH
 OR LARGER DIAMETER FIXTURE BRANCH OR STACK.
  