Plan Review Details - Permit 20030856
Plan Review Stops For Permit 20030856
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By rmcdouga Date 2020-05-12 Time 12:18 Rev Time 0.00
Received By rmcdouga Date 2020-05-12 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By cthroop Date 2020-04-01 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2020-04-01 Time 10:30 Sent To I
Notes
2020-04-01 13:17:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ARCHITECT THAT SIGNED AND SEALED THE REVISED
 DRAWINGS IS NOT THE ORIGINAL DESIGNER OF RECORD. THE
 NEW ARCHITECT IS REQUIRED TO FOLLOW THE PROCDURES FOR A
 SUCCESSOR ARCHITECT FOR ADOPTING THE WORK OF ANOTHER AS
 HIS OWN PER FAC 61G1-18.002.
  
 2) WHEN REVISING PLANS BE MINDFUL OF THE PAGE
 NUMBERING. THE REVISED PLAN SHEET TAKES THE PLACE OF
 THE OLD PLAN SHEET. THE ARCHITECTUAL SHEET THAT YOU ARE
 REVISING IS ACTUALLY SHEET A-2 OF THE PREVIOUS PLANS.
 MAKE SURE THAT THERE ARE NOT ANY DETAILS OR NOTES ON
 THE PREVIOUS PLANS THAT SHOULD NOT BE ELIMINATED ON THE
 REVISED DRAWINGS. FBC 107.2.1
  
 NOTE: DUE TO RECENT EVENTS WE ARE ENCOURAGING OUR
 CUSTOMERS TO CHANGE FROM PAPER TO DIGITAL PLANS. IF YOU
 WISH TO CONVERT TO DIGITAL PLAN REVIEW, CONTACT:
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By jpearson Date 2020-05-13 Time 08:54 Rev Time 0.00
Received By jpearson Date 2020-05-13 Time 07:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-25 Cont ID  
Sent By cthroop Date 2020-03-25 Time 12:41 Rev Time 0.00
Received By jpearson Date 2020-03-25 Time 12:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-01 Cont ID  
Sent By rmcdouga Date 2020-04-01 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2020-03-17 Time 09:47 Sent To  
Notes
2020-03-18 09:48:00R11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-07 Cont ID  
Sent By medwards Date 2020-05-07 Time 07:21 Rev Time 0.00
Received By medwards Date 2020-05-07 Time 07:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-04-20 Cont ID  
Sent By cthroop Date 2020-03-26 Time 15:52 Rev Time 0.00
Received By medwards Date 2020-04-20 Time 15:29 Sent To  
Notes
2020-04-20 15:31:18INFORMATION I ASKED FOR IS INCLUDED WITH THE ORIGINAL
 PERMIT # 20020708.
2020-03-26 15:53:151ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030856
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE AN ACCURATE AND COMPLETED RESIDENTIAL
 BUILDING FORM R405 ALONG WITH AN ENERGY GAUGE AND
 MANUAL S CALCULATIONS FOR THE NEW MECHANICAL SYSTEMS.
 FBC EC 101.5.1.1.2: FBC RES M1401.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-05-13 Cont ID  
Sent By ccole Date 2020-05-13 Time 12:38 Rev Time 0.00
Received By ccole Date 2020-05-13 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-01 Cont ID  
Sent By cthroop Date 2020-04-01 Time 15:22 Rev Time 0.00
Received By tklarge Date 2020-03-31 Time 10:23 Sent To  
Notes
2020-03-31 15:22:391) SHOW THE LOCATION OF THE WASHING MACHINE ON THE
 PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE FIRST FLOOR 4" VENT IS DRAWN AS A FLAT DRY VENT.
 COMPLY WITH FBC-PLUMBING SEC.905.3.
 3) A CLEANOUT IS REQUIRED IN THE STACKS TO THE 2ND
 FLOOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-05-07 Cont ID  
Sent By medwards Date 2020-05-07 Time 07:25 Rev Time 0.00
Received By medwards Date 2020-05-07 Time   Sent To  
Notes
***NONE***