Plan Review Details - Permit 20030788
Plan Review Stops For Permit 20030788
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2021-09-29 Cont ID  
Sent By rmcphers Date 2021-09-29 Time 07:38 Rev Time 0.00
Received By rmcphers Date 2021-09-29 Time 07:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 09:50 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 09:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-05-06 Cont ID  
Sent By rmcphers Date 2021-05-06 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2021-05-06 Time 14:37 Sent To  
Notes
2021-05-06 14:46:53DOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PRODUCT APPROVAL PROVIDED FOR THE LOUVERS HAS
 EXPIRED - PLEASE PROVIDE AN UPDATED LOUVER PRODUCT
 APPROVAL.
 2) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE ARCHITECT (STEPHEN BORUFF) OR THE
 PRODUCT APPROVAL NUMBERS CAN BE LISTED ON THE DRAWINGS.
 FBC WPB 107.3.4 THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-03-08 Cont ID  
Sent By pvalenti Date 2021-03-08 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2021-03-08 Time 10:28 Sent To  
Notes
2021-03-08 10:28:44DOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND LOUVERS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-29 Cont ID  
Sent By rmcphers Date 2020-09-29 Time 10:03 Rev Time 0.00
Received By rmcphers Date 2020-09-29 Time 10:02 Sent To  
Notes
2020-09-29 10:03:45DOOR ALTERATION AT PUMP ROOM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND LOUVERS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 08:55 Sent To  
Notes
2020-03-23 09:03:30DOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) BUILDING RISK CATEGORY IV WIND SPEED FOR DESIGN
 SHOULD BE 180MPH FBC FIGURE 1609.3(2)
 2) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND LOUVERS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2021-09-10 Cont ID  
Sent By pleduc Date 2021-09-10 Time   Rev Time 0.00
Received By pleduc Date 2021-09-10 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-04-22 Cont ID  
Sent By pleduc Date 2021-04-22 Time   Rev Time 0.00
Received By pleduc Date 2021-04-22 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2021-02-22 Cont ID  
Sent By pleduc Date 2021-02-22 Time   Rev Time 0.00
Received By pleduc Date 2021-02-22 Time 11:36 Sent To  
Notes
2021-02-22 11:52:04********THE PREVIOUS FIRE COMMENTS WERE NO SPECIFICALLY
 ADDRESSED OR THERE ARE NO INDICATIONS THAT WERE
 CHANGED/CLOUDED ON THE PLAN SHEETS********
  
 ********THERE ARE NO INDICATIONS OF ANY ATTEMPT TO
 ADDRESS FIRE COMMENTS. ALL PALNE SHEETS ARE DATE
 9/18/20, THE SAME DATE OF THE PREVIOUS
 COMMENTS.********
  
 THE PREVIOUS COMMENTS ARE SUBMITTED AGAIN BELOW:
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A NEW LOUVER ASSEMBLY
 WITHIN THE WALL HOUSING A FIRE PUMP.
  
 THE FIRE PUMP ROOM WALL SHALL HAVE A FIRE RESISTIVE
 RATING OF 2-HOUR.
  
 THERE ARE NO MANUFACTURE SPEC SHEETS OF THE NEW LOUVER
 INDCATING THE REQUIRED RATING.
  
 PER NFPA 20
  
 4.12.1.1.2* INDOOR FIRE PUMP ROOMS IN NON-HIGH-RISE
 BUILDINGS
 OR IN SEPARATE FIRE PUMP BUILDINGS SHALL BE PHYSICALLY
 SEPARATED OR PROTECTED BY FIRE-RATED CONSTRUCTION IN
 ACCORDANCE
 WITH TABLE 4.12.1.1.2.
  
 THE TABLE INDICATES IF BOTH THE PUMP ROOM AND ADJACENT
 STRUCTURES ARE SPRINKLED
  
 1 HOUR FIRE-RATED
 OR
 50 FT (15.3 M)
  
 PLEASE PROVIDE DETAILS AND FIRE RATING SPEC SHEETS IF
 APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By pleduc Date 2020-09-22 Time   Rev Time 0.00
Received By pleduc Date 2020-09-22 Time 11:25 Sent To  
Notes
2020-09-22 13:20:21THE PREVIOUS FIRE COMMENTS WERE NO SPECIFICALLY
 ADDRESSED OR THERE ARE NO INDICATIONS THAT WERE
 CHANGED/CLOUDED ON THE PLAN SHEETS
  
 THE PREVIOUS COMMENTS ARE SUBMITTED AGAIN BELOW:
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A NEW LOUVER ASSEMBLY
 WITHIN THE WALL HOUSING A FIRE PUMP.
  
 THE FIRE PUMP ROOM WALL SHALL HAVE A FIRE RESISTIVE
 RATING OF 2-HOUR.
  
 THERE ARE NO MANUFACTURE SPEC SHEETS OF THE NEW LOUVER
 INDCATING THE REQUIRED RATING.
  
 PER NFPA 20
  
 4.12.1.1.2* INDOOR FIRE PUMP ROOMS IN NON-HIGH-RISE
 BUILDINGS
 OR IN SEPARATE FIRE PUMP BUILDINGS SHALL BE PHYSICALLY
 SEPARATED OR PROTECTED BY FIRE-RATED CONSTRUCTION IN
 ACCORDANCE
 WITH TABLE 4.12.1.1.2.
  
 THE TABLE INDICATES IF BOTH THE PUMP ROOM AND ADJACENT
 STRUCTURES ARE SPRINKLED
  
 1 HOUR FIRE-RATED
 OR
 50 FT (15.3 M)
  
 PLEASE PROVIDE DETAILS AND FIRE RATING SPEC SHEETS IF
 APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By pleduc Date 2020-03-23 Time   Rev Time 0.00
Received By pleduc Date 2020-03-23 Time 11:34 Sent To  
Notes
2020-03-23 11:43:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF A NEW LOUVER ASSEMBLY
 WITHIN THE WALL HOUSING A FIRE PUMP.
  
 THE FIRE PUMP ROOM WALL SHALL HAVE A FIRE RESISTIVE
 RATING OF 2-HOUR.
  
 THERE ARE NO MANUFACTURE SPEC SHEETS OF THE NEW LOUVER
 INDCATING THE REQUIRED RATING.
  
 PER NFPA 20
  
 4.12.1.1.2* INDOOR FIRE PUMP ROOMS IN NON-HIGH-RISE
 BUILDINGS
 OR IN SEPARATE FIRE PUMP BUILDINGS SHALL BE PHYSICALLY
 SEPARATED OR PROTECTED BY FIRE-RATED CONSTRUCTION IN
 ACCORDANCE
 WITH TABLE 4.12.1.1.2.
  
 THE TABLE INDICATES IF BOTH THE PUMP ROOM AND ADJACENT
 STRUCTURES ARE SPRINKLED
  
 1 HOUR FIRE-RATED
 OR
 50 FT (15.3 M)
  
 PLEASE PROVIDE DETAILS AND FIRE RATING SPEC SHEETS IF
 APPLICABLE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2021-09-29 Cont ID  
Sent By rmcphers Date 2021-09-29 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2021-09-09 Time 11:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 10:11 Rev Time 0.00
Received By rmcphers Date 2021-08-10 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-05-06 Cont ID  
Sent By rmcphers Date 2021-05-06 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2021-04-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-03-08 Cont ID  
Sent By ccarvaja Date 2021-03-08 Time 10:29 Rev Time 0.00
Received By rmcphers Date 2021-02-15 Time 17:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-29 Cont ID  
Sent By rmcphers Date 2020-09-29 Time 10:04 Rev Time 0.00
Received By rmcphers Date 2020-09-18 Time 14:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-27 Cont ID  
Sent By pvalenti Date 2020-03-27 Time 09:41 Rev Time 0.00
Received By pvalenti Date 2020-03-16 Time 15:42 Sent To  
Notes
2020-03-23 09:16:41PLANS TO FIRE BIN
2020-03-21 14:03:09TO RMC DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 14:09 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 14:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 12:33 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 12:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-02-26 Cont ID  
Sent By medwards Date 2021-02-26 Time 08:57 Rev Time 0.00
Received By medwards Date 2021-02-26 Time 08:57 Sent To  
Notes
2021-02-26 09:00:17PLEASE SEE ORIGINAL REVIEWER'S NOTES FOR THE NEW
 LOUVER. PLEASE PROVIDE THE MENTIONED MECHANICAL
 DRAWINGS. PLEASE PROVIDE THE NOA FOR THE NEW LOUVER.
 FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-02-10 15:16:06 
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 09:50 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 09:50 Sent To  
Notes
2020-09-22 09:50:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030788
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION 2017
 FBC FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE ORIGINAL REVIEWERS NOTE FOR THE NEW
 LOUVER. SHEET A1 OF 2-(NOTE H) INDICATES THE NEW
 ALUMINUM LOUVER, SEE MECHANICAL DRAWINGS. PLEASE
 PROVIDE THE MENTIONED MECHANICAL DRAWING. FBC FS
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By pvalenti Date 2020-03-27 Time 09:36 Rev Time 0.00
Received By pvalenti Date 2020-03-27 Time 09:36 Sent To  
Notes
2020-03-27 09:41:14PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 FBC B 107, PROVIDE PRODUCT APPROVAL FOR LOUVER.
 INFORMATION IS REQUIRED FROM THE INTERIOR SIDE AS TO
 THE EXISTING FIRE RATING AND EQUIPMENT RELATED TO THE
 LOUVER.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-09-29 Cont ID  
Sent By rmcphers Date 2021-09-29 Time 07:39 Rev Time 0.00
Received By rmcphers Date 2021-09-29 Time 07:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 10:07 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 10:07 Sent To  
Notes
2021-08-30 10:10:49SIGNATURES
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED -
 THE FOLLOWING SHEETS NEED TO BE DIGITALLY SIGNED: A1,
 A2, S-100.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. - OR -
 IF YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-05-04 Cont ID  
Sent By medwards Date 2021-05-04 Time 12:33 Rev Time 0.00
Received By medwards Date 2021-05-04 Time 12:33 Sent To  
Notes
2021-05-04 12:34:37PLEASE SEE 2ND CYCLE COMMENTS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-02-10 Cont ID  
Sent By medwards Date 2021-02-10 Time 15:20 Rev Time 0.00
Received By medwards Date 2021-02-10 Time 15:20 Sent To  
Notes
2021-02-10 15:22:36THE FOLLOWING SHEETS NEED TO BE DIGITALLY SIGNED:
 LS1.0, A1, A2, S-100.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 10:31 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 10:31 Sent To  
Notes
2020-09-22 10:31:23PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  