Plan Review Details - Permit 20030756
Plan Review Stops For Permit 20030756
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-06 Cont ID  
Sent By jbrooks Date 2020-08-06 Time 11:32 Rev Time 0.00
Received By jbrooks Date 2020-08-06 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-31 Cont ID  
Sent By jbrooks Date 2020-03-31 Time 09:57 Rev Time 0.00
Received By jbrooks Date 2020-03-31 Time 09:57 Sent To  
Notes
2020-03-31 09:57:40JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. PLEASE ADDRESS ZONING COMMENTS.
 2. 61G15-23.001. F.A.C. (B). ENGINEERING SPECIFICATIONS
 AND CALCULATIONS. AN INDEX SHEET SHALL BE USED AND
 SHALL BE SIGNED, DATED AND SEALED BY EACH PROFESSIONAL
 ENGINEER WHO IS IN RESPONSIBLE CHARGE OF ANY PORTION OF
 THE ENGINEERING SPECIFICATIONS OR CALCULATIONS. THE
 INDEX SHEET MUST BE SIGNED, DATED AND SEALED BY THOSE
 PROFESSIONAL ENGINEERS IN RESPONSIBLE CHARGE OF THE
 PRODUCTION AND PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATIONS OR CALCULATIONS, WITH
 SUFFICIENT INFORMATION ON THE INDEX SHEET SO THAT THE
 USER WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS OR CALCULATIONS FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By ppetty Date 2020-03-23 Time 13:12 Rev Time 0.00
Received By ppetty Date 2020-03-23 Time 13:12 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-06 Cont ID  
Sent By jbrooks Date 2020-08-06 Time 11:32 Rev Time 0.00
Received By jbrooks Date 2020-07-18 Time 08:39 Sent To  
Notes
2020-08-04 13:53:31ROUTED TO BLDG. MISC 1
2020-07-18 08:39:14ROUTING TO ZONING BIN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By jbrooks Date 2020-03-31 Time 09:57 Rev Time 0.00
Received By jbrooks Date 2020-03-16 Time 14:02 Sent To  
Notes
2020-03-17 17:48:44ROUTED TO ELECTRICAL INBOX
2020-03-16 14:02:26ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-07-29 Cont ID  
Sent By rthermid Date 2020-07-29 Time   Rev Time 0.00
Received By rthermid Date 2020-07-29 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By rfalcone Date 2020-03-17 Time 15:18 Rev Time 0.00
Received By rfalcone Date 2020-03-17 Time 15:18 Sent To I
Notes
2020-03-17 15:31:04ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03/17/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE
 LOCATION OF THE PROPOSED DIRECTIONAL SIGN.
 2. INDICATE IF THE PROPOSED SIGN IS A PARKING AREA
 INSTRUCTIONAL SIGN.
  
 PURUSANT ZLDR SEC. 94-407(5)PARKING AREA IDENTIFICATION
 SIGNS. LOW-FREESTANDING SIGNS WITH ONE OR TWO FACES AND
 WALL MOUNTED SIGNS WITH ONE FACE SHALL BE PERMITTED
 SUBJECT TO THE FOLLOWING CONTROLS:
 A. PERMITTED CONTENT: DESIGNATION OF ENTRANCE AND EXIT
 POINTS, INCLUDING DIRECTIONAL ARROWS.
 B. MAXIMUM AREA: FOUR SQUARE FEET PER SIGN FACE.
 C. MAXIMUM NUMBER: ONE PER ENTRANCE AND EXIT.
 D. LOCATION: ON THE SAME LOT AS THE PARKING AREA TO
 WHICH IT IS ACCESSORY.
 E. MINIMUM SETBACKS:
 1.FROM LOT LINE OF ANOTHER LOT: 20 FEET.
 2.FROM PUBLIC RIGHTS-OF-WAY: ZERO FEET.
 3. FROM INTERSECTIONS OF STREETS WITH OTHER STREETS AND
 WITH ACCESS DRIVES: AS REQUIRED BY SUBSECTION
 94-305(E).
 F. MAXIMUM HEIGHT:
 1. LOW-FREESTANDING: SIX FEET.
 2. WALL-MOUNTED: 12 FEET.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  