Plan Review Details - Permit 20030726
Plan Review Stops For Permit 20030726
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-02 Cont ID  
Sent By jleahy Date 2020-04-02 Time 14:36 Rev Time 0.00
Received By jleahy Date 2020-04-02 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By jleahy Date 2020-03-24 Time 08:25 Rev Time 0.00
Received By jleahy Date 2020-03-24 Time 08:25 Sent To  
Notes
2020-03-24 08:28:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) SEPARATE PERMIT REQUIRED FOR ACCESS CONTROL, AND
 REQUIRES FIRE REVIEW.
  
 2) VALUE OF THE WORK SHOWN IS LOW PLEASE SUBMIT A
 SIGNED CONTRACT FOR THE WORK INVOLVED. VALUE TO INCLUDE
 ALL LABOR , MATERIAL ECT, ECT.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-03 Cont ID  
Sent By pleduc Date 2020-04-03 Time   Rev Time 0.00
Received By pleduc Date 2020-04-03 Time 10:07 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-25 Cont ID  
Sent By pleduc Date 2020-03-25 Time   Rev Time 0.00
Received By pleduc Date 2020-03-25 Time 09:10 Sent To I
Notes
2020-03-25 09:20:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
2020-03-24 08:39:22SENT PLAN TO FIRE FOR ACCESS CONTROL. JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-03 Cont ID  
Sent By lmarchan Date 2020-04-03 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2020-04-01 Time 10:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-25 Cont ID  
Sent By lmarchan Date 2020-03-25 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2020-03-16 Time 12:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-03 Cont ID  
Sent By lmarchan Date 2020-04-03 Time 11:01 Rev Time 0.00
Received By lmarchan Date 2020-04-03 Time 11:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 14:06 Rev Time 0.00
Received By shill Date 2020-03-24 Time 14:06 Sent To  
Notes
***NONE***