Plan Review Details - Permit 20030701
Plan Review Stops For Permit 20030701
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-08 Cont ID  
Sent By rmcdouga Date 2020-04-08 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2020-04-08 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By rmcdouga Date 2020-03-20 Time 19:12 Rev Time 0.00
Received By rmcdouga Date 2020-03-20 Time 17:36 Sent To  
Notes
2020-03-20 17:42:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FS 553.73 (10) (E) EXEMPTS MOBILE OR MODULAR
 STRUCTURES USED AS TEMPORARY OFFICES FROM THE FLORIDA
 BUILDING CODE, EXCEPT THAT THE PROVISIONS OF PART II
 RELATING TO ACCESSIBILITY BY PERSONS WITH DISABILITIES
 APPLY TO SUCH MOBILE OR MODULAR STRUCTURES.
  
 2) SHOW THE ACCESSIBLE ROUTE TO THE BUILDING AND THE
 ACCESSIBLE ENTRANCE TO THE TEMPORARY OFFICE TRAILER.
 FBC ACCESSIBILITY CHAPTERS 2 AND 4
  
 3) SHOW THE LOCATION OF THE ACCESSSIBLE BATHROOMS. FBC
 ACCESSIBILITY CHAPTERS 2
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-01 Cont ID  
Sent By jpearson Date 2020-04-01 Time 13:15 Rev Time 0.00
Received By jpearson Date 2020-04-01 Time 10:57 Sent To  
Notes
2020-04-01 13:15:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By jleahy Date 2020-03-23 Time 16:54 Rev Time 0.00
Received By jleahy Date 2020-03-23 Time 16:54 Sent To  
Notes
2020-03-23 16:55:49ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRIC SHOWN JLEAHY
  
 PLEASE SHOW LOCATION OF SERVICE AND PANEL FOR TEMPORARY
 OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2020-04-03 Cont ID  
Sent By sathomas Date 2020-04-03 Time 00:00 Rev Time 0.00
Received By sathomas Date 2020-04-03 Time 00:00 Sent To B
Notes
2020-04-03 09:53:57TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 THERE IS NO SCOPE OF WORK TO BE DONE INCLUDING, NOT
 LIMITED TO THE DURATION OF THE STRUCTURE'S PLACEMENT.
  
 S. THOMAS
 561-804-4728
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-18 Cont ID  
Sent By pleduc Date 2020-03-18 Time   Rev Time 0.00
Received By pleduc Date 2020-03-18 Time 12:04 Sent To  
Notes
2020-03-18 12:09:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS NO SITE PLAN INDICATING WHERE THIS TRALIER
 WILL BE LOCATED.
  
 PLEASE PROVIDE AND INDICATED ALL DIMENSIONS TO ALL
 OTHER BUILDINGS/STRUCTURES/PROPERTY LINES
  
  
  
 2) THERE ARE NO INDICATIONS OF ELECTRICAL POWER
 SOURCES.
  
 WILL THERE BE POWER PROVIDED AND WHAT TYPEI.E. FPL,
 GENERATOR AND LOCATION OF SOURCE?
  
  
  
 3) THERE IS NO INDICATION OF A EXIT SIGN WITHIN THE
 TRAILER.
  
 PLEASE PROVIDE DETAILS.
  
  
 4) THERE IS NO INDICASTION OF A FIRE EXTIGUISHER WITHIN
 THE TRAILER.
  
 PLEASE PROVIDE AT LEAST 5LB ABC.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-08 Cont ID  
Sent By rmcdouga Date 2020-04-08 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2020-03-31 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 10:01 Rev Time 0.00
Received By shill Date 2020-03-13 Time 11:48 Sent To  
Notes
2020-03-17 11:48:30B05

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-02 Cont ID  
Sent By shill Date 2020-04-02 Time 10:50 Rev Time 0.00
Received By shill Date 2020-04-02 Time 10:50 Sent To  
Notes
2020-04-02 10:50:5820030701 2271 PALM BEACH LAKES BLVD
  
 PLUMBING COMMENTS: APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20030701 2271 PALM BEACH LAKES BLVD
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-24 Cont ID  
Sent By jesmith Date 2020-03-24 Time 10:01 Rev Time 0.00
Received By shill Date 2020-03-23 Time 16:27 Sent To  
Notes
2020-03-23 16:27:2320030701 2271 PALM BEACH LAKES BLVD
  
 PLUMBING COMMENTS: APPROVED
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-03 Cont ID  
Sent By shill Date 2020-04-03 Time 07:41 Rev Time 0.00
Received By shill Date 2020-04-03 Time 07:41 Sent To  
Notes
2020-04-03 07:41:31UPLOADED A DIGITALLY SIGNED PDF WHICH INCLUDES THE
 TRAILER DRAWINGS
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-03 Cont ID  
Sent By rfalcone Date 2020-04-03 Time 16:14 Rev Time 0.00
Received By rfalcone Date 2020-04-03 Time 16:14 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By rfalcone Date 2020-03-24 Time 08:16 Rev Time 0.00
Received By rfalcone Date 2020-03-24 Time 08:16 Sent To I
Notes
2020-03-24 08:24:57ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 3/24/2020
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PROVIDE A SURVEY OF THE SUBJECT SITE AND SHOW THE
 SETBACKS OF THE PORTABLE TO THE PROPERTY LINES.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF THE FORM IS TEMPORARILY UNAVAILABLE, PLEASE REQUEST
 THAT IT BE SENT TO YOU BY EMAILING [email protected]
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1442
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  