| 2020-03-20 10:07:02 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT- 20030695 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | SHEET 7 OF 14: LEVEL 2- PLEASE SHOW THE LOCATION OF THE |
| | MAIN RETURN GRILL, INCLUDE SIZE AND CFM?S. |
| | SHEET 7 OF 14: LEVEL 2- RETURN AIR OPENINGS MUST MEET |
| | FBC RES M1602.2 (4) RETURN AIR SHALL NOT BE TAKEN FROM |
| | A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE, |
| | MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR |
| | UNCONDITIONED ATTIC. |
| | SHEET 13 OF 14: LEVEL 1- PLEASE SHOW RETURN CFM IN THE |
| | CONDITIONED AREA. ALSO SHOW THE SUPPLY AND RETURN |
| | DUCTWORK WITH SIZES. SHEET 14 OF 14: PLEASE SHOW BOTH |
| | SUPPLY AND RETURN REGISTERS AND CFM?S FOR EACH. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |