Plan Review Details - Permit 20030673
Plan Review Stops For Permit 20030673
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-06-15 Cont ID  
Sent By jpearson Date 2020-06-15 Time 07:09 Rev Time 0.00
Received By jpearson Date 2020-06-15 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-06-10 Cont ID  
Sent By jpearson Date 2020-06-10 Time 09:57 Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-18 Cont ID  
Sent By jpearson Date 2020-05-18 Time 08:00 Rev Time 0.00
Received By jpearson Date 2020-05-18 Time 08:00 Sent To  
Notes
2020-05-18 08:00:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS RESPONSIBLE PERSON IS SHOWN IN THE TITLE
 BLOCK AS WILLIAM TRACY FROM MB DESIGN. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 (NOT
 CORRECTED.)
 2. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By jpearson Date 2020-03-24 Time 08:50 Rev Time 0.00
Received By jpearson Date 2020-03-24 Time 08:50 Sent To I
Notes
2020-03-24 08:50:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS RESPONSIBLE PERSON IS SHOWN IN THE TITLE
 BLOCK AS WILLIAM TRACY FROM MB DESIGN. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. PLAN IS PRINTED SO SMALL THAT IT IS DIFFICULT TO
 READ. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES. PROVIDE CORRECTION.
 WPB FBC 107.2.1.3
  
 FYI, YOU CAN SUBMIT THIS APPLICATION AND DRAWINGS
 ELECTRONICALLY. CONTACT [email protected] BY
 EMAIL FOR INFORMATION.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-06-16 Cont ID  
Sent By pleduc Date 2020-06-16 Time   Rev Time 0.00
Received By pleduc Date 2020-06-16 Time 12:38 Sent To  
Notes
2020-06-16 12:39:08THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED CALL BOX INSTALLATION SHALL NOT
 RESTRICT FREE EGRESS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-05-06 Cont ID  
Sent By pleduc Date 2020-05-06 Time   Rev Time 0.00
Received By pleduc Date 2020-05-06 Time 10:00 Sent To  
Notes
2020-05-06 10:04:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED CALL BOX INSTALLATION SHALL NOT
 RESTRICT FREE EGRESS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By pleduc Date 2020-03-23 Time   Rev Time 0.00
Received By pleduc Date 2020-03-23 Time 11:29 Sent To  
Notes
2020-03-23 11:30:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF
 EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT
 ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-16 Cont ID  
Sent By ccarvaja Date 2020-06-16 Time 13:15 Rev Time 0.00
Received By ccarvaja Date 2020-05-26 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-05 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-20 Time 14:44 Sent To  
Notes
2020-03-20 14:44:57ROUTED TO FIRE INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-15 Cont ID  
Sent By jpearson Date 2020-06-15 Time 07:09 Rev Time 0.00
Received By jpearson Date 2020-06-15 Time 07:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-06-12 Cont ID  
Sent By jpearson Date 2020-06-12 Time 14:24 Rev Time 0.00
Received By jpearson Date 2020-06-12 Time 14:24 Sent To  
Notes
2020-06-12 14:24:43PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-06-10 Cont ID  
Sent By jpearson Date 2020-06-10 Time 09:57 Rev Time 0.00
Received By jpearson Date 2020-06-10 Time 09:57 Sent To  
Notes
2020-06-10 09:56:58PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-18 Cont ID  
Sent By jpearson Date 2020-05-18 Time 08:01 Rev Time 0.00
Received By jpearson Date 2020-05-18 Time 08:01 Sent To  
Notes
2020-05-18 08:01:15PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481