| 2020-03-23 16:35:59 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER - 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE A PANEL SCHEDULE. |
| | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, |
| | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 2. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT |
| | CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. |
| | NEC 110.10 & FBC RE E3404.3 |
| | |
| | PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC |
| | 110.3, 110.9; FBC RE E3606.4 |
| | |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| | |
| | 3. PROVIDE OUTLET FOR REFREGERATOR. |
| | E3703.2 KITCHEN AND DINING AREA RECEPTACLES. |
| | |
| | 4. PROVIDE SMOKE DETECTORS. |
| | R314.1 GENERAL. |
| | SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION |
| | R314. |
| | |
| | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1.IN EACH SLEEPING ROOM. |
| | 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET |
| | (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A |
| | BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS |
| | WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY |
| | SECTION R314.3. |
| | |
| | 5. PROVIDE EXHAUST FAN FOR BATHROON NEXT TO BEDROOM #1. |
| | M1507.4LOCAL EXHAUST RATES. |
| | LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE |
| | CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE |
| | DETERMINED IN ACCORDANCE WITH TABLE M1507.4. |
| | |
| | 6. ENERGY CODE ? LUMINAIRES: |
| | PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |