Plan Review Details - Permit 20030648
Plan Review Stops For Permit 20030648
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-07-30 Cont ID  
Sent By jbrooks Date 2020-07-30 Time 13:14 Rev Time 0.00
Received By jbrooks Date 2020-07-30 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By cthroop Date 2020-03-23 Time 15:56 Rev Time 0.00
Received By cthroop Date 2020-03-20 Time 14:49 Sent To  
Notes
2020-03-23 15:59:46PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER - 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REVISION SCOPE OF WORK IS TO COMPLETE INTERIOR
 FINISHES. PROVIDE A FINISH SCHEDULE,
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. LOCATE FRONT DOOR (EGRESS) ON PLAN. I ASSUME IT'S BY
 THE EXTERIOR LIGHT REQUIRED FOR EXIT ILLUMINATION.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-06 Cont ID  
Sent By ppetty Date 2020-08-06 Time 09:09 Rev Time 0.00
Received By ppetty Date 2020-08-06 Time 09:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By cthroop Date 2020-03-23 Time 15:59 Rev Time 0.00
Received By cthroop Date 2020-03-20 Time 14:49 Sent To  
Notes
2020-03-23 16:35:59PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER ? BUILDING - PX3169
 PLANS EXAMINER - 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A PANEL SCHEDULE.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 2. PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT
 CURRENT AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE.
 NEC 110.10 & FBC RE E3404.3
  
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
  
 3. PROVIDE OUTLET FOR REFREGERATOR.
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
  
 4. PROVIDE SMOKE DETECTORS.
 R314.1 GENERAL.
 SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION
 R314.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3.ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS AND NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3.
  
 5. PROVIDE EXHAUST FAN FOR BATHROON NEXT TO BEDROOM #1.
 M1507.4LOCAL EXHAUST RATES.
 LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE
 DETERMINED IN ACCORDANCE WITH TABLE M1507.4.
  
 6. ENERGY CODE ? LUMINAIRES:
 PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-06 Cont ID  
Sent By jbrooks Date 2020-08-06 Time 09:09 Rev Time 0.00
Received By ppetty Date   Time   Sent To  
Notes
2020-08-05 08:45:05ROUTED TO ELECTRICAL BIN
2020-07-22 08:00:11ROUTED TO BLDG. MISC 1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By cthroop Date 2020-03-23 Time 16:36 Rev Time 0.00
Received By cthroop Date 2020-03-12 Time 11:18 Sent To I
Notes
2020-03-13 11:18:23REVISION ROUTED TO CTHROOP