Plan Review Details - Permit 20030640
Plan Review Stops For Permit 20030640
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-03-26 Cont ID  
Sent By cpuell Date 2020-03-26 Time 12:19 Rev Time 0.00
Received By cpuell Date 2020-03-26 Time 12:19 Sent To  
Notes
2020-03-26 12:20:52CREATED NEW UNIT FOR KIOSK # 125

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 14:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-14 Cont ID  
Sent By rmcphers Date 2020-04-14 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2020-04-14 Time 11:09 Sent To  
Notes
2020-04-14 11:17:55KIOSK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) KIOSK DRAWINGS GL1 THROUGH GL13 - GENERAL NOTE
 NUMBER 5 SAYS "PERIMETER FASTENERS SHALL BE AS NOTED
 HEREON" . DRAWINGS DO NOT SHOW FASTENER TYPE, SIZE,
 AMOUNT, ON CENTER SPACING ETC. THIS INFORMATION NEEDS
 TO BE ON THE DRAWINGS.
 2) NEED COMPLETE (FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS) COPIES OF THE PRODUCT APPROVALS THAT ARE
 MENTIONED ON THE DRAWINGS.
 3) PLEASE REMOVE ALL NOTES THAT SAY "PRE FAB BUILDING"
 FROM ALL DRAWINGS.
 4) KIOSK DRAWINGS GL1 THRU GL13 DO NOT SHOW AS
 ELECTRONICALLY SIGNED IN "ADOBE".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By rmcphers Date 2020-03-26 Time 16:01 Rev Time 0.00
Received By rmcphers Date 2020-03-26 Time 13:52 Sent To  
Notes
2020-03-26 15:47:45PRE FAB KIOSK
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE STATE APPROVED MANUFACTURED BUILDING
 DRAWINGS (MARKED REVIEWED AND APPROVED BY A 3RD PARTY)
 OR PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVAL FOR THE ENTIRE BUILDING. FBC WPB AMENDMENTS
 107.3 EXCEPTIONS.
 2) IF THE BUILDING IS BEING BUILT ON SITE THE DRAWINGS
 WILL NEED TO SHOW ALL CONNECTIONS, COLUMN AND BEAM
 DESIGNATIONS, PROVIDE ALL PRODUCT APPROVALS FOR ALL
 STOREFRONT GLAZING, DOORS AND WINDOWS.
 3) DRAWING A1.1.1 SHOWS COUNTER HEIGHT AT 34 INCHES -
 DRAWING A3.0.1 SHOWS COUNTER HEIGHT AT 36 INCHES -
 PLEASE CLARIFY TO COMPLY WITH FBC ACCESSIBILITY.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-26 Cont ID  
Sent By jleahy Date 2020-03-26 Time 17:48 Rev Time 0.00
Received By jleahy Date 2020-03-26 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-06-25 Cont ID  
Sent By pleduc Date 2020-06-25 Time   Rev Time 0.00
Received By pleduc Date 2020-06-25 Time 14:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By pleduc Date 2020-04-10 Time   Rev Time 0.00
Received By pleduc Date 2020-04-10 Time 12:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-25 Cont ID  
Sent By pleduc Date 2020-03-25 Time   Rev Time 0.00
Received By pleduc Date 2020-03-25 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-01 Cont ID  
Sent By lmarchan Date 2020-07-01 Time 09:53 Rev Time 0.00
Received By lmarchan Date 2020-06-24 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-14 Cont ID  
Sent By rmcphers Date 2020-04-14 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2020-04-09 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-27 Cont ID  
Sent By lmarchan Date 2020-03-27 Time 16:06 Rev Time 0.00
Received By lmarchan Date 2020-03-24 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By medwards Date 2020-04-10 Time 08:49 Rev Time 0.00
Received By medwards Date 2020-04-10 Time 08:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By medwards Date 2020-03-27 Time 09:44 Rev Time 0.00
Received By medwards Date 2020-03-27 Time 09:02 Sent To  
Notes
2020-03-27 09:45:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030640
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) PLEASE PROVIDE THE ENERGY GAUGE AND MANUAL S
 CALCULATIONS. FBC EC 101.5.1.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-30 Cont ID  
Sent By rmcphers Date 2020-06-30 Time 14:11 Rev Time 0.00
Received By rmcphers Date 2020-06-30 Time 14:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-14 Cont ID  
Sent By rmcphers Date 2020-04-14 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2020-04-14 Time 11:28 Sent To  
Notes
2020-04-14 11:28:49THE GL DRAWINGS DO NOT SHOW IN "ADOBE" AS
 ELECTRONICALLY SIGNED. DRAWINGS NEED TO BE
 ELECTRONICALLY SIGNED TO BE USED IN ELECTRONIC PLAN
 REVIEW.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By rmcphers Date 2020-03-26 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2020-03-26 Time 15:55 Sent To  
Notes
2020-03-26 15:59:49THE ARCHITECTURAL AND THE GL DRAWINGS DO NOT SHOW IN
 "ADOBE" AS ELECTRONICALLY SIGNED. DRAWINGS NEED TO BE
 ELECTRONICALLY SIGNED TO BE USED IN ELECTRONIC PLAN
 REVIEW.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-01 Cont ID  
Sent By eschneid Date 2020-07-01 Time 08:52 Rev Time 0.25
Received By eschneid Date 2020-07-01 Time 08:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-10 Cont ID  
Sent By eschneid Date 2020-04-10 Time 16:59 Rev Time 0.25
Received By eschneid Date 2020-04-10 Time 16:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By eschneid Date 2020-03-27 Time 16:00 Rev Time 0.50
Received By eschneid Date 2020-03-27 Time 16:00 Sent To  
Notes
***NONE***