Plan Review Details - Permit 20030565
Plan Review Stops For Permit 20030565
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2020-10-25 Cont ID  
Sent By cpuell Date 2020-10-25 Time 11:20 Rev Time 0.00
Received By cpuell Date 2020-10-25 Time 11:20 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2020-03-24 Cont ID  
Sent By cpuell Date 2020-03-24 Time 14:24 Rev Time 0.00
Received By cpuell Date 2020-03-24 Time 14:24 Sent To  
Notes
2020-03-24 14:25:03HAD SPOKE TO M SANCHEZ BUILDING ADDRESS HAD ALREADY
 BEEN ESTABLISHED. HOWEVER STILL NEED A LIST OF THE
 INDIVIDUAL UNIT NUMBERS. PLEASE COORDINATE WITH ME
 [email protected] 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-10-21 Cont ID  
Sent By mcphers Date 2020-10-21 Time 07:40 Rev Time 0.00
Received By rmcphers Date 2020-10-21 Time 07:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-10-09 Cont ID  
Sent By rmcphers Date 2020-10-09 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2020-10-09 Time 09:09 Sent To  
Notes
2020-10-09 10:24:57PROVISO:
 A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 PARKING LOT
 DETACHED STRUCTURES - GAZEBO ETC.
 B) PROVIDE FLOORING IIC AND STC ACOUSTICAL TEST REPORTS
 FOR REVIEW FOR THE TILE FLOORING BEFORE FLOORING
 INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-14 Cont ID  
Sent By rmcphers Date 2020-08-14 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2020-08-13 Time 14:05 Sent To  
Notes
2020-08-14 08:13:16NEW 3 STORY APT. BLDG.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 2ND REVIEW
 1) PRODUCT APPROVAL PROVIDED FOR THE DWELLING UNIT
 INSWING EXTERIOR DOORS DOES NOT MEET THE WATER
 INFILTRATION REQUIREMENTS OF FBC 1709.5.1
 2) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH
 WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1
 3) PRODUCT APPROVAL 19-0219.11 FOR THE SLIDING GLASS
 DOOR DOES NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2
 (PLEASE PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL.)
 4) PRODUCT APPROVAL 17-0614.05 FOR THE FIXED GLASS DOES
 NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 (PLEASE
 PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL)
 5) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO
 COMPLY WITH FBC 1207 AS NOTED BELOW (A, B AND C) (YOU
 NEED TO PROVIDE THE ACOUSTICAL LAB TEST REPORTS)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NONCOMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcphers Date 2020-04-02 Time 14:29 Rev Time 0.00
Received By rmcphers Date 2020-04-01 Time 08:52 Sent To  
Notes
2020-04-02 13:25:44NEW 3 STORY APT. BLDG.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING
 THE BASE FLOOD ELEVATION PER THE LATEST FIRM.
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND WINDOWS.
 3) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH
 WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEMS.
 5) SEPARATE PERMITS ARE REQUIRED FOR - PAVING/PARKING,
 DUMPSTER,RETAINING WALLS, PAVILION ETC. PLEASE PROVIDE
 NOTES TO VERIFY THE UNDERSTANDING OF SUCH.
 6) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO
 COMPLY WITH FBC 1207 AS NOTED BELOW (A,B AND C)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-17 Cont ID  
Sent By jleahy Date 2020-08-17 Time 10:23 Rev Time 0.00
Received By jleahy Date 2020-08-17 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-20 Cont ID  
Sent By jpearson Date 2020-04-20 Time 15:30 Rev Time 0.00
Received By jpearson Date 2020-04-17 Time 09:45 Sent To  
Notes
2020-04-20 15:27:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
 2. RISER DIAGRAM SHOWS THREE SETS OF THREE 400 KCMIL
 CONDUCTORS FOR THE FEEDERS FROM FPL. THIS WOULD
 INDICATE THAT THIS IS A SINGLE PHASE SERVICE, BUT THE
 RISER INDICATED THIS IS A THREE PHASE SERVICE. PROVIDE
 CLARIFICATION AND/OR CORRECTIONS. NEC 215.5; WPB FBC
 107.2.1
 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. IT APPEARS FOR THE METER CENTER THAT NEC 220.84
 IS BEING USED, BUT THIS CODE SECTION IS NOT APPLIED
 CORRECTLY. ALL LOADS AT 100% SHOULD BE ADDED TOGETHER
 AND THEN THE DEMAND FACTOR OF 35% APPLIED TO THIS
 AMOUNT BASED ON 25 DWELLING UNITS. I SEE A 34% FACTOR
 IN THE METER CENTER LOAD CALCULATION. IT ALSO APPEARS
 THAT 100% OF THE LOADS FROM EACH UNIT IS NOT BEING USED
 CORRECTLY. THIS SHOULD INCLUDE ALL ITEMS DETAILED IN
 NEC 220.84(C), INCLUDING ONLY THE LARGER OF THE AC OR
 HEAT LOAD. WHEN THIS NUMBER IS CALCULATED, THEN 100% OF
 THE HOUSE LOAD WOULD BE ADDED TO THAT FOR THE FINAL VA
 LOAD BASED ON NEC 220.84(B). NEC 220
 4. BASED ON LOADS DETAILED IN THIS SUBMISSION, I HAVE
 CALCULATED THE LOAD ON THE SERVICE TO BE 1062 AMPS,
 WHICH IS LARGER THAN THE DESIGNED SERVICE SUPPLIED.
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED FOR
 SERVICE EQUIPMENT AND FEEDERS. NEC 215.2, 220.84,
 408.30, 408.36
 5. PANEL SCHEDULE FOR EACH UNIT SHOW A DIFFERENT LOAD
 THAN THE LOAD CALCULATION TABLES. IT APPEARS THAT THIS
 IS DUE TO THE CORRECT TYPE OF LOAD CALCULATION FOR
 DWELLING UNITS NOT BEING USED, WHICH WOULD INCLUDE 3VA
 PER SQUARE FOOT. INFORMATION SHOULD BE CONSISTENT.
 CORRECT DISCREPANCIES. WPB FBC 107.2.1; NEC 220
 6. IF SERVICE OR FEEDER SIZES ARE CHANGED, PROVIDE
 UPDATED AIC CALCULATIONS. NEC 110.9, 110.10
 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 8. UNITS 2A, 2B, 2C, AND 2D ALL SHOW THE FOLLOWING CODE
 VIOLATION. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 THIS CIRCUIT CAN BE USED FOR LIGHTING AND RECEPTACLE
 OUTLETS IN ONE BATHROOM, BUT THEN CANNOT BE USED TO
 FEED ANOTHER BATHROOM. OR, THIS CIRCUIT CAN FEED ONLY
 THE RECEPTACLES IN MULTIPLE BATHROOMS. PROVIDE
 CORRECTION. NEC 210.11(C)(3)
 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 10. LIGHT FIXTURE SCHEDULE DOES NOT INDICATE FIXTURES
 THAT ARE RATED FOR WET LOCATIONS FOR SHOWERS, OR HAVE
 ENCLOSED LIGHT BULBS FOR CLOSETS. PROVIDE NOTE OF
 COMPLIANCE FOR EACH LOCATION. NEC 410.10(D), 410.16
 11. PROVIDE COMPLIANCE FOR DWELLING UNITS: A MINIMUM OF
 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1, R404.1
 12. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2020-08-19 Cont ID  
Sent By rrossano Date 2020-08-19 Time   Rev Time 0.00
Received By rrossano Date 2020-08-19 Time   Sent To  
Notes
2020-08-19 07:58:47REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19100032.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-04-30 Cont ID  
Sent By shill Date 2020-04-30 Time 07:08 Rev Time 0.00
Received By shill Date 2020-04-30 Time 07:08 Sent To  
Notes
2020-04-30 07:08:24CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
 IF YOU HAVE AN ISSUED ENGINEERING PERMIT, OR A PENDING
 APPLICATION, PLEASE ADVISE VIA EMAIL ([email protected])
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-16 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-30 Cont ID  
Sent By pleduc Date 2020-03-30 Time   Rev Time 0.00
Received By pleduc Date 2020-03-25 Time 14:13 Sent To  
Notes
2020-03-27 15:14:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FA 2.1 - THERE DOES NOT APPEAR TO BE
 NOTIFICATION DEVICES WITHIN THE SLEEPING ROOMS
  
 PER NFPA 101, CH 30
  
 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 30.3.4.1 GENERAL.
 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR
 WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE
 MEETING THE
 REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A
 FIRE ALARM
 SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS
 MODIFIED BY
 30.3.4.2 THROUGH 30.3.4.5.
  
 30.3.4.3 NOTIFICATION.
 30.3.4.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED
 AUTOMATICALLY
 IN ACCORDANCE WITH SECTION 9.6, AND BOTH OF THE
 FOLLOWING SHALL
 ALSO APPLY:
 (1) VISIBLE SIGNALS SHALL BE INSTALLED IN UNITS
 DESIGNED FOR THE
 HEARING IMPAIRED.
 (2) POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH 9.6.3.4
 SHALL BE
 PERMITTED.
  
 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH
 9.6.3.5.8,
 NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE
 AUDIBLE, AND
 VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM
 AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN
 NATIONAL
 STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND
 FACILITIES, OR
 OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY
 HAVING
 JURISDICTION SHALL BE PROVIDED.
  
 NFPA 72
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE
 SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND
 LEVEL OF AT
 LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5
 DB
 ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT
 LEAST
 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA,
 WHICHEVER IS
 GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA
 REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE
 PARTITION, IS LOCATED BETWEEN THE NOTIFICATION
 APPLIANCE AND
 THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED
 WITH THE
 BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE
 REFERENCES AND NARRATIVE AS TO WHY NOT.
  
  
  
 1A) FOR INFORMATIONAL AND FALSE ALARM REDUCTION
 PURPOSES THE LOCATION OF MAUNAL PULL STATIONS MAY BE
 REDUCED PER NFPA 101, CH 9
  
 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE
 DETECTION OR
 WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM
 SYSTEM IN
 ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN
 ONE MANUAL
 FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY
 HAVING
 JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE
 ALARM SIGNAL.
  
 A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6
 IS INTENDED
 TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM
 SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR
 WATERFLOW DEVICES
 ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR
 WHERE
 HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC
 SPRINKLER SYSTEM
 OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE
 FIRE ALARM
 SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE
 MANUAL FIRE
 ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A
 SEPARATE
 CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION
 OR SPRINKLER
 SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX
 SHOULD BE
 LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF
 THE BUILDING
 AND SHOULD NOT BE LOCKED.
  
 PLEASE REVIEW AND IF IN AGREEMENT, CONSULT WITH MY
 OFFICE FOR A SUITABLE LOCATION
  
 PROVIDE AN APPLICABLE NOTE.
  
  
 2) SHEET FP 2 - NO FIRE SPRINKLER IN THE ELEVATOR PIT
  
 PER NFPA 13R
  
 6.6.8 ALL SITUATIONS REGARDING SPRINKLER LOCATION AND
 POSITION
 THAT ARE NOT DIRECTLY DISCUSSED IN NFPA 13R SHALL BE IN
 ACCORDANCE
 WITH NFPA 13.
  
 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS.
 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED
 AT THE BOTTOM
 OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M)
 ABOVE THE FLOOR OF THE PIT.
 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE
 ELEVATOR
 HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR
 ENCLOSED, NONCOMBUSTIBLE
 ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE
 HYDRAULIC FLUIDS.
 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE
 REQUIRED IN ELEVATOR
 MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL
 SPACES, OR
 HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE
 WITH THE
 APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE
 BUILDING
 CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL
 ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR
 IS
 DEDICATED TO ELEVATOR EQUIPMENT ONLY.
 (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY
 SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF
 TRACTION
 ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER
 AUTOMATIC
 FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72.
 (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL
 SPACE,
 OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE
 REMAINDER
 OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/
 CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF
 NOT LESS
 THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE.
 (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE
 PERMITTED
 TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY
 SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF
 TRACTION
 ELEVATORS.
 (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC
 TYPE.
 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE
 ROOMS OR
 AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR
 INTERMEDIATETEMPERATURE
 RATING.
 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY
 SPRINKLERS SHALL
 BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS.
 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE
 ELEVATOR HOISTWAY
 BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY
 FOR PASSENGER
 ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND
 THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF
 ASME
 A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS.
  
 8.15.5.7 COMBUSTIBLE SUSPENSION IN ELEVATORS.
 8.15.5.7.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP AND
 BOTTOM OF
 ELEVATOR HOISTWAYS WHERE ELEVATORS UTILIZE COMBUSTIBLE
 SUSPENSION
 MEANS SUCH AS NONCIRCULAR ELASTOMERIC-COATED OR
 POLYURETHANECOATED
 STEEL BELTS.
 8.15.5.7.2 THE SPRINKLERS IN THE ELEVATOR HOISTWAY
 SHALL NOT BE
 REQUIRED WHEN THE SUSPENSION MEANS PROVIDE NOT LESS
 THAN AN
 FT-1 RATING WHEN TESTED TO THE VERTICAL BURN TEST
 REQUIREMENTS
 OF UL 62, FLEXIBLE CORDS AND CABLES, AND UL 1581,
 REFERENCE STANDARD
 FOR ELECTRICAL WIRES, CABLES, AND FLEXIBLE CORDS.
  
 PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT
  
  
  
 3) SHEET 2.3 - THERE ARE INDICATIONS OF FIRE LINE
 UNDERGROUND.
  
 ALL FIRE LAINE UNDERGROUND WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH
 NFPA 24, STANDARD FOR THE
 INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR
 APPURTENANCES,2013 EDITION
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) SHEET E 7.4 - THERE ARE INDICATIONS OF A BDA SYSTEM.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
  
 YOU SHALL MAKE CONTACT AND COORDINATE WITH MARK FILLA,
 PALM BEACH COUNTY, PUBLIC SAFETY RADIO SYSTEMS MANAGER,
 FOR ALL RADIO SIGNAL DETAILS, OUTBOUND SIGNAL STRENGTH
 AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE ON THAT
 SYSTEM.
 [email protected] 561-233-0837
  
  
 ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT
 AND SHOP DRAWINGS BY A QUALIFIED FCC LIC CONTRACTOR,
 LISTED EQUIPMENT AND SPEC SHEETS, WITH A COLOR HEAT
 SPECTUM FLOOR PLAN.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-10-27 Cont ID  
Sent By ccarvaja Date 2020-10-27 Time 11:25 Rev Time 0.00
Received By ccarvaja Date 2020-10-20 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-10-20 Cont ID  
Sent By lmarchan Date 2020-10-20 Time 06:39 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-20 Cont ID  
Sent By shill Date 2020-08-20 Time 17:32 Rev Time 0.00
Received By shill Date 2020-07-15 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-30 Cont ID  
Sent By shill Date 2020-04-30 Time 07:08 Rev Time 0.00
Received By shill Date 2020-03-24 Time 14:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-10-27 Cont ID  
Sent By rmcphers Date 2020-10-27 Time 11:25 Rev Time 0.00
Received By ccarvaja Date 2020-08-04 Time 07:03 Sent To  
Notes
2020-10-27 11:24:52RECEIPT - MU 2020-30337 - $146,066.51 - PAID. CC
2020-09-18 07:03:2308/04/20 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-08-14 Cont ID  
Sent By rmcphers Date 2020-08-14 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2020-08-14 Time 08:13 Sent To  
Notes
2020-08-14 08:14:29PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
2020-08-04 15:32:108/4/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcphers Date 2020-04-02 Time 14:27 Rev Time 0.00
Received By rmcphers Date 2020-04-02 Time 14:27 Sent To  
Notes
2020-04-02 14:29:26PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-09-28 Cont ID  
Sent By medwards Date 2020-09-28 Time 14:13 Rev Time 0.00
Received By medwards Date 2020-09-28 Time 13:57 Sent To  
Notes
2020-09-28 14:13:48APPROVED WITH PRIVISO:
 DRYER BOOSTER FANS MUST BE LISTED AND LABELED TO UL
 705.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-08-04 Cont ID  
Sent By medwards Date 2020-08-04 Time 15:50 Rev Time 0.00
Received By medwards Date 2020-08-04 Time 15:50 Sent To  
Notes
2020-08-04 15:51:012ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20030565
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE 1ST CYCLE REVIEW COMMENTS 12,13,14 AND
 MAKE SURE THIS HAS BEEN COMPLETED. PLEASE UPLOAD THE
 CORRECT DOCUMENTS FOR BUILDING B ONLY; ELEVATOR MACHINE
 ROOM LOAD CALS STILL SHOW BIKE ROOM AND BUILDING A;
 UNIT 1A1 LOAD CALCS V2 IN PROJECT INFORMATION (NOTES)
 STILL SHOWS BUILDING A-UNIT 1A 1ST FLOOR. UNIT 1A2 LOAD
 CALCS V2 SHEET 3 UNDER PROJECT INFORMATION (NOTES)
 PLEASE SHOW THE CORRECT BUILDING (B).UNIT 2A1 EWN LOAD
 CALCS- PLEASE IDENTIFY WHICH BUILDING. PLEASE RECHECK
 ALL LOAD CALCULATION SHEETS AND ENERGY CALCULATION
 SHEETS TO VERIFY THEY HAVE THE CORRECT BUILDING (B).
 FBC FS 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-04-08 Cont ID  
Sent By medwards Date 2020-04-08 Time 16:44 Rev Time 0.00
Received By medwards Date 2020-08-04 Time 14:21 Sent To  
Notes
2020-04-08 16:47:161ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030565
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE VENTILATION CALCULATIONS FOR ENTIRE
 BUILDING. ARE YOU USING FBC M 402 FOR NATURAL
 VENTILATION OR 403 FOR MECHANICAL?
 2) PLEASE SHOW HOW THE MECHANICAL ROOM IN EACH LIVING
 SPACE MEETS SECTION 602 OF THE FBC M FOR PLENUMS.
 3) PLEASE PROVIDE A DETAIL DRAWING OF THE DRYER AND
 DRYER DUCT CONNECTION IN THE AHU CLOSET. THE DRYER DUCT
 APPEARS TO STOP IN THE CEILING. FBC FS 107.2.1
 4) PLEASE SHOW CFM?S FOR ALL RETURN GRILLES AND
 TRANSFER GRILLES. FBC M 601.5(3)
 5) PLEASE SHOW RETURN PATH BACK TO THE AHU. ARE THE
 DOUBLE DOORS LOUVERED? IF SO THEN PLEASE PROVIDE DETAIL
 AND SHEET NUMBER. FBC FS 107.2.1
 6) PLEASE SHOW EACH KITCHEN WILL COMPLY WITH FBC M
 TABLE 403.3.2.3.
 7) PLEASE SHOW THE EXHAUST TERMINATIONS MEET SECTION
 501.3(3) OF THE FBC M.
 8) PLEASE SHOW THE INTAKE OPENING LOCATIONS MEET
 SECTION 401.4 OF THE FBC M.
 9) PLEASE IDENTIFY ALL LOAD CALCULATIONS AS YOU DID IN
 ?UNIT 2B1 LOAD CALCS? UNDER PROJECT INFORMATION, THIS
 IDENTIFIES THE BUILDING OR BUILDINGS WHERE THIS UNIT IS
 LOCATED.
 10) DOCUMENTS UPLOADED TITLED ? ELEVATOR MACHINE ROOM
 LOAD CALCS.PDF? ARE FOR ? BUILDING A-BIKE ROOM?. PLEASE
 UPLOAD THE CORRECT DOCUMENT FOR THIS BUILDING B
 ELEVATOR MACHINE ROOM LOAD CALCS.PDF.
 11) DOCUMENTS UPLOADED TITLED ?INIT 1A1 LOAD
 CALCULATIONS PDF? ARE FOR BUILDING A. PLEASE UPLOAD
 LOAD CALCULATIONS FOR THE CORRECT BUILDING (B).
 12) PLEASE IDENTIFY BUILDING B ON ALL OF THE ENERGY
 CALCULATIONS.
 13) PLEASE IDENTIFY EACH LOAD CALCULATION AS TO THE
 BUILDING IT IS LOCATED IN. EITHER BUILDING A OR
 BUILDING B.
 14) DOCUMENTS UPLOADED TITLED ?UNIT 1A2 LOAD CALCS.PDF?
 ARE FOR BUILDING A. PLEASE UPLOAD CALCULATIONS FOR
 BUILDING B.
 15) UNDER ?MECHANICAL VENTILATION? IN THE ENERGY
 CALCULATIONS PLEASE SHOW BATHROOM AND KITCHEN EXHAUST
 CFM. IT APPEARS THE CFM?S SHOWN ARE ONLY FOR THE
 BATHROOMS. FBC FS 107.2.1; FBC M TABLE 403.3.2.2
 16) SHEET M-4.1: PLEASE SHOW ROOF ACCESS. FBC M 306.5
 17) SHEET M-4.1: PLEASE SHOW EQUIPMENT ON THE ROOF
 MEETS FBC M 304.11 (GUARDS)
 18) SHEET M-5.3: THE RETURN AIR TRANSFER FOR THE
 BEDROOM IS NOT INSIDE THE ROOM. PLEASE SHOW THIS RETURN
 AIR TRANSFER IN THE CORRECT LOCATION. FBC FS 107.2.1
 19) SHEET M-5.4: PLEASE SHOW THE REQUIRED DAMPERS IN
 ALL PENETRATIONS OF THE 2 HR RATED WALL AT THE
 ELECTRICAL ROOM.
 20) SHEET M-5.4: PLEASE PROVIDE A DETAIL DRAWING OF THE
 AHU ROOM SHOWING THE AHU?S, THE RETURN AIR DUCT AND HOW
 IT RETURNS TO THE AHU AND THE O/A DUCT AND LOCATION IT
 ENTERS THE AHU?S. FBC FS 107.2.1
 21) . FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF
 CERTIFY DIGITAL SIGATURES AND SEALS PER FBC FS 668.003.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-10-21 Cont ID  
Sent By lcrespo Date 2020-10-21 Time 06:46 Rev Time 0.00
Received By tklarge Date 2020-10-21 Time 04:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-10-07 Cont ID  
Sent By lacrespo Date 2020-10-07 Time 15:32 Rev Time 0.00
Received By lcrespo Date 2020-10-06 Time 13:32 Sent To  
Notes
2020-10-07 15:32:5310/07/20 3RD PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SANITARY RISER DIAGRAM, SOME ITEMS NEED
 CORRECTIONS AS FOLLOW;
  
 A. SHEET P 7.5 2VD, 2V2C, 2V2D, V1A, AND V2A BATHROOM
 SHOWER IS NOT VENTED CORRECTLY, PLEASE REFER TO 2V2A
 FOR A CORRECT METHOD, PER THE 2017 FBC SEC. P910.1.
  
 B. SHEET P7.6 SHOWER ON S2A AND 2SA2 NEED TO BE VENTED
 BETWEEN SHOWER AND WATER CLOSET WITH LAV RISER PER THE
 2017 FBC SEC. P910.1.
  
 C. SHEET P7.7 SHOWER ON 2V2A NEEDS TO BE VENTED BETWEEN
 SHOWER AND WATER CLOSET WITH LAV RISER, REFER TO S1A
 FOR A CORRECT METHOD, PER THE 2017 FBC SEC. P910.1.
  
 D. SHEET P7.8 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON 2S2B AND S2B PER THE 2017 FBC
 SEC. P706.1. SHOWER ON 2S2B AND S2B NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1.
  
 E. SHEET P7.9 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON S2C AND 2S2C PER THE 2017 FBC
 SEC. P706.1. SHOWER ON S2C AND 2S2C NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1.
  
 F. SHEET P7.10 THE DIRECTION OF FLOW FROM BRANCH TO THE
 SHOWER IS NOT CORRECT ON S2D AND 2S2D PER THE 2017 FBC
 SEC. P706.1. SHOWER ON S2D AND 2S2D NEED TO BE VENTED
 BETWEEN THE SHOWER AND WATER CLOSET WITH A LAV RISER
 PER THE 2017 FBC SEC. P910.1. SHOWER S2D WAS CHANGED ON
 THE 2ND FLOOR BUT NOT ON 3RD AND IT NEEDS TO BE MOVED
 TO THE BATHROOM GROUP OF V2D PER THE 2017 FBC. SEC.
 P706.1.
  
 2. SHEET P7.3 THEIR OS A DRY VENT AT THE END OF THE
 BATHROOM UPSTREAM FROM WATER FOUNTAIN THAT IS NOT
 REQUIRED AS IT CAN NOT BE MADE A WET VENT YOU CAN
 DELETE IT PER THE 2017 FBC SEC. P317.
  
 PLEASE NOTE IF YOU WOULD SEND ME YOUR CORRECTION BY
 EMAIL I WILL REVIEW AND REDLINE BEFORE YOU UPLOAD THEM
 TO PROJECTDOC TO HAVE CORRECTIONS REFLECT WHAT THE
 COMMENT REQUEST.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-14 Cont ID  
Sent By lcrespo Date 2020-08-17 Time 06:32 Rev Time 0.00
Received By lcrespo Date 2020-08-06 Time 09:22 Sent To  
Notes
2020-08-14 13:23:1708/14/20 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ELEVATOR A IS HYDRAULIC TYPE AND IT REQUIRES A
 PUMP WHERE OIL IS PRESENT OR ALARM, PLEASE DETAILS
 LOCATION AND WHERE DRAINED PER THE 2017 FBC SEC. P
 712.3. IF A SUMP PUMP WILL BE INSTALLED IN THE ELEVATOR
 SUMP, THE INSTALLATION SHALL COMPLY WITH FBC-PLUMBING
 SEC.1003.4.
  
 2. IN THE UNDERGROUND SANITARY RISER DIAGRAM, SOME
 ITEMS NEED CORRECTIONS AS FOLLOW;
  
 A. SHEET. P7.2 - DETAIL #1 - A MAXIMUM OF 10 FIXTURE
 UNITS SHALL BE VENTED BY A 1 1/2 INCH VENT PER
 FBC-PLUMBING TABLE 906.1. AS DRAWN, 15 FIXTURE UNITS
 ARE BEING VENTED BY THE 1 1/2 INCH VENT. REFER TO
 FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT VALUE FOR A
 BATHROOM GROUP, TAG VENT RISER ON TYPICAL #3 IF
 APPLICABLE.
  
 B. SHEET P 7.3 DIRECTION OF FLOW ON RISER 4" WHICH IS
 ALSO MISSING A TAG ON 2- 4" AND 1 1/2" (SANITARY AND
 WATER) PER THE 2017 FBC SEC. 706.1. THE DRINKING
 FOUNTAIN ON WATER RISER REQUIRES A HAMMER ARRESTOR PER
 THE 2017 FBC SEC. P604.9. THE LINE TO FEED THE DRINKING
 FOUNTAIN IS 1 1/2" AND IT SHOULD SAY 1/2" PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. SHEET P 7.5 DIRECTION OF FLOW FROM S2A TO 2V2C/2VB.
 SHOWER ON 4" S2D NEEDS TO BE MOVED TO THE BATHROOM
 GROUP OF V2D PER THE 2017 FBC SEC. P706.1. KITCHEN SINK
 K1A ON BOTH SIDES NEEDS TO BE DOWNSTREAM FROM BATHROOM
 GROUP WET VENT PER THE 2017 FBC SEC. P915.1. SHOWER ON
 2V2A NEEDS TO BE VENTED BETWEEN SHOWER AND WATER CLOSET
 WITH LAV RISER PER THE 2017 FBC SEC. P910.1.
  
 D. SHEET P 7.6 P SHOWER ON A2A NEEDS TO BE VENTED
 BETWEEN SHOWER AND WATER CLOSET WITH LAV RISER PER THE
 2017 FBC SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. SHEET P 7.7 SHOWER ON S1A NEEDS TO BE VENTED BETWEEN
 SHOWER AND WATER CLOSET WITH LAV RISER PER THE 2017 FBC
 SEC. P910.1. PLEASE LABEL ALL RE-VENTS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 F. SHEET P 7.8 DIRECTION OF FLOW FROM S2B RISER GOING
 TO BATHROOM GROUP PER THE 2017 FBC SEC. P706.1. SHOWER
 ON 2V2B NEEDS TO BE VENTED BETWEEN SHOWER AND WATER
 CLOSET WITH LAV RISER PER THE 2017 FBC SEC. P910.1.
 PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 G. SHEET P 7.10 SHOWER S2D NEEDS TO BE MOVED TO THE
 BATHROOM GROUP OF V2D PER THE 2017 FBC SEC. P706.1.
 PLEASE LABEL ALL RE-VENTS PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE IDENTIFY THE TUBS AS TUBS ON THE RISER
 DIAGRAMS AND NOT AS SHOWERS.
  
 4. PLEASE CHECK ALL THE RISER TAGS ON THE PLAN VIEW
 SHEETS AGAINST THE SANITARY RISER DIAGRAMS TO ENSURE
 THE RISER TAGS CORRELATE THROUGH EACH FLOOR. REFER TO
 SHEETS P7.3, P7.4, P7.5, P7.6 & P7.7, 7.8, P7.9, AND
 7.10 PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1. THERE
 TOO MANY TO MENTION SO PLEASE RECTIFY TO PREVENT
 FURTHER REVIEWS, THANK YOU.
  
 5. FLOOR DRAIN REQUIRES A TRAP PRIMER PLEASE PROVIDE
 HOW YOU ARE GOING TO PROTECT THE TRAP SEAL PER THE 2017
 FBC SEC. 1002.4.1.
  
 6. PLEASE PROVIDE INFORMATION ON SHEET P 5.6 ON THE
 COFFEE MAKER OF A VACUUM BREAKER OF A DUAL CHECK VALVE
 THAT COMPLIES WITH ASSE 1024 PER THE 2017 FBC SEC.
 P608.16.10.
  
 7. PLEASE NOTE ON SHEET P 5.6 MOP SINK WALLS SHALL BE
 IMPERVIOUS 18? PER THE 2017 FBC B 1210.2.2.
  
 8. SHEET P 5.6 TEMPERED WATER IS REQUIRED TO THE
 LAVATORY IN THE COMMON AREA TOILET ROOM PER 2017 FBC
 PLUMBING SEC. 416.5, 607.1, A NOTE WAS PUT IN FOR
 INSTANT HOT. THE TEMPERED WATER MUST BE A DEVICE THAT
 COMPLIES WITH ASSE 1070 PER THE 2017 FBC SEC. P607.1.2,
 PLEASE UPDATE THE NOTE.
  
 9. THE 1 1/2" VENT FOR TOILET AND LAV IS DRY NEEDS TO
 BE A WET VENT PER 2017 FBC SEC. P912.2.
  
 10. PLEASE PROVIDE A RISER FOR PAN AND CONDENSATE LINE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING AND 2017 FBC SEC. P317.
  
 11. DRINKING FOUNTAIN LOCATION SHALL HAVE ACCESS TO
 RESIDENCE AND VISITORS WITH AN UNRESTRICTED OPEN AREA
 PLEASE SHOW A LOCATION OPEN TO ALL PATRIATES PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 12. FIRESTOPPING DETAILS HAVE BEEN SUBMITTED FOR METAL
 PIPE THROUGH RATED WALLS AND FLOORS. IF PVC PIPE IS TO
 BE INSTALLED, SUBMIT FIRE-STOPPING ASSEMBLY DETAILS FOR
 THE PVC PIPE THROUGH RATED FLOORS AND WALLS PER THE WPB
 AMEND. TO FBC SEC. 107.2.1, 107.3.5.1.1.
  
 13. THIS IS A 2ND REQUEST THE PRESSURE CYLINDER FOR THE
 ELEVATOR SHALL BE PROTECTED IN ACCORDANCE WITH 2017
 FBC-BUILDING SEC.3011. I COULD NOT FIND THIS DETAIL ON
 THE PLANS. PLEASE SUBMIT THE SPECIFIC PAGE WHERE THIS
 DETAIL CAN BE FOUND.
  
 14. SHT.A-0.1 - DETAIL #3 - UNIT 2A - THIS LAYOUT DOES
 NOT COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL,
 CHAPTER 7, PAGE 7.56 & 7.57. THE ONLY FIXTURE PERMITTED
 TO BE ADJACENT TO THE SHOWER IS A LAVATORY MOUNTED ON
 THE CONTROL WALL BESIDE THE SHOWER AND MAY OVERLAP THE
 CLEAR FLOOR SPACE BY A MAXIMUM OF 6 INCHES. THE PORTION
 OF THE LAVATORY THAT OVERLAPS THE CLEAR FLOOR SPACE
 MUST HAVE KNEE SPACE BELOW OR A REMOVABLE VANITY
 CABINET. A 30 INCH WIDE BY 48 INCHES DEEP CLEAR FLOOR
 SPACE MUST BE PROVIDED PARALLEL TO THE SHOWER AND FLUSH
 WITH THE CONTROL WALL THIS IS A 2ND REQUEST.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-04-05 Cont ID  
Sent By tklarge Date 2020-04-05 Time 09:20 Rev Time 0.00
Received By tklarge Date 2020-04-05 Time 08:39 Sent To  
Notes
2020-04-05 06:48:29PLUMBING:
 1) SHT. A-0.1 - DETAILS #1, #2 & #3 - SHOWS THE
 CENTERLINE OF THE WATER CLOSET FROM THE EDGE OF THE TUB
 AND/OR SHOWER AS ONE- FOOT SEVEN INCHES, ONE- FOOT NINE
 INCHES AND ONE- FOOT EIGHT INCHES RESPECTIVELY. THE
 DISTANCE SHALL BE 0NE -FOOT SIX INCHES ( 18" ) ABSOLUTE
 AS REQUIRED BY THE FAIR HOUSING ACT DESIGN MANUAL,
 CHAPTER 6, PG. 6.7. THESE DIMENSIONS MUST ALSO BE
 CHANGED ON THE ELEVATION DRAWINGS.
 2) SHT. A-0.1 - DETAIL #7 - SHOW THE WIDTH OF THE
 PROPOSED REINFORCEMENT FOR THE TUB. THE LENGTH IS SHOWN
 AS 48 INCHES.WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A-0.1 - THE UNITS THAT HAVE A SHOWER DO NOT
 COMPLY WITH THE REQUIREMNT FOR THE CLEAR FLOOR SPACE
 THAT IS REQUIRED BY THE FHA DESIGN MANUAL CHAPTER 7,
 PG.7.56. AS PROPOSED, THIS LAYOUT DOES NOT COMPLY WITH
 HAVING THE WATER CLOSET NEXT TO THE SHOWER.A 30 INCH
 WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE MUST BE PROVIDED
 AT SHOWER STALLS, PARALLEL TO THE FIXTURE AND FLUSH
 WITH THE CONTROL WALL. FHA DESIGN MANUAL PART TWO,
 CHAPTER 7, PART B, PG. 7.56..
 4) SHT. A-0.1 - DETAIL #3 NOTES "SEE DETAIL #6 FOR GRAB
 BAR REINFORCEMENT AT SHOWER." DETAIL #6 SHOWS
 REINFORCEMENT AT TOILETS.REVISE THE NOTE TO REFER TO
 DETAIL #8.
 5) SHT. A-0.1 - DETAIL #3 NOTES " SEE DETAIL #8 FOR
 REINFORCEMENT AT TOILET." DETAIL #8 SHOWS REINFORCEMENT
 AT SHOWERS. REVISE THE NOTE TO REFER TO DETAIL #6.
 6) SHT. A-0.1 - DETAIL #8 - THE SHOWER REINFORCEMENT
 THAT IS SHOWN FOR A FUTURE SHOWER SEAT DOES NOT COMPLY
 WITH THE FAIR HOUSING ACT DESIGN MANUAL. THE
 REINFORCING MUST START AT THE FLOOR AND RISE TO A
 MINIMUM HEIGHT OF 24 INCHES, NOT START 6 INCHES ABOVE
 THE FLOOR PER PART TWO, CHAPTER 6, PG. 6.13 OF THE FAIR
 HOUSING ACT DESIGN MANUA. REVISE THE DETAIL.
 7) SHT. A-1.8 - SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE
 LAVATORY. COMPLY WITH 2017 FBC-ACCESS. SECS. 604.3.1,
 606.2.
 8) SHT. A-1.3 - DETAIL #5 - CLARIFY THE CLEARANCES FOR
 THE WATER CLOSET FROM THE EDGE OF THE VANITY AND THE
 TUB/SHOWER. COMPLY WITH FHA DESIGN MANUAL.
 9) SHT. A-1.4 - INTERIOR ELEVATION #6 - THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 18 INCHES PER THE FHA
 DESIGN MANUAL.. THE PLANS SHOWS ONE FOOT NINE INCHES
 (21 INCHES).
 10) SHT.A-1.5 - INTERIOR ELEVATIONS #5 & #9 - THE
 CENTERLINE TO THE WATER CLOSET SHALL BE 18 INCHES TO
 THE CENTERLINE, NOT 20 INCHES AS SHOWN.FHA DESIGN
 MANUAL, PART TWO, CHAPTER 7, PART B PG. 7.43.
 11) SHT. A-1.8 - SHOW THE CLEAR INSIDE DIMENSIONS ( L X
 W ) OF THE ACCESSIBLE TOILET ROOM. WPB AMEND. TO FBC
 SEC. 107.2.1.
 12) SUBMIT ADDITIONAL INFORMATION ON THE RAINWATER
 CALCULATIONS. SHOW HOW YOU ARRIVED AT THE FINAL
 RESULTS. THE PARAPET WALL MUST BE INCLUDED IN THE
 RAINWATER CALCULATIONS PER THE 2017 FBC-PLUMBING
 SECS.1106.4, 1106.5.SEE SHT. A-3.
 13) IS THE ELEVATOR A TRACTION TYPE OR HYDRAULIC TYPE?
 IF OF A HYDRAULIC TYPE , THE PRESSURE CYLINDER SHALL BE
 PROTECTED IN ACCORDANCE WITH 2017 FBC -BUILDING
 SEC.3011.
 14) SUBMIT FIRESTOPPING DETAILS FOR PIPE PENETRATIONS
 THROUGH FRAMED RATED WALLS. THE SUBMITTED DETAIL IS FOR
 PENETRATIONS THROUGH A CONCRETE FLOOR OR A BOLCK WALL.
 WPB AMEND. TO FBC SEC. 107.3.5.1.1.
 15) SHT. P-1.0 - IDENTIFY ALL RISERS ON THE PLUMBING
 SHEETS.. PROVIDE RISER TAG NUMBERS FOR EACH RISER (
 WATER & SANITARY).WPB AMEND. TO FBC SEC.107.3.5.1.3.
 16) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER
 DIAGRAM SHOWING ALL SANITARY RISERS AND PROVIDE RISER
 TAG NUMBERS SO THE RISERS WILL CORRELATE WITH RISERS
 THAR ARE TO BE SHOWN ON THE FLOOR PLAN. WPB AMEND. TO
 FBC SEC. 107.3.5.1.3.
 17) SHT. P-2.1 - THE FIRST FLOOR PLAN SHOWS TRENCH
 DRAINS BY THE ELEVATORS.AND THE PLAN REFERS TO THE
 CIVIL DRAWINGS. THESE DRAINS ARE NOT SHOWN ON THE CIVIL
 DRAWINGS. CLEARLY SHOW THE LOCATION OF THESE DRAINS ON
 THE PLANS AND SPECIFY THE SPECIFIC SHEET WHERE THEY ARE
 LOCATED. WPB AMEND. TO FBC SEC. 107.1, 107.3.5.1.3.
 18) SHT. P-2.1 - THERE ARE NO PIPE SIZES ON THE PIPES
 AND THE RISERS NEED TO HAVE RISER TAGS AND IDENTIFIED
 AS TO THE USE. WPB AMEND. TO FBC SEC. 107.2.1.REFER TO
 THE SPECIFIC CIVIL DRAWING WHERE THE REQUIRED
 INFORMATION CAN BE FOUND.
 19) THE UNITS WITH THE HALL BATH HAVE THE HALL BATH
 MISSING FROM THE SANITARY AND WATER RISER. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 20) SHTS. P-5.1 & P-5.2 - KEYNOTE #2 IS NOT SHOWN ON
 THE PLANS. CLARIFY.
 21) SHT. P-7.1 - A FULL OPEN VALVE IS REQUIRED AT THE
 BASE OF THE WATER RISER PER 2017 FBC-PLUMBING SEC.606.1
 (4).
 22) SUBMIT A COMPLETE WATER RISER FOR THE 2 BATH UNIT.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 23) SHT. P-7.2 - DETAIL #3 - THE KITCHEN SINKS ARE NOT
 VENTED. 2017 FBC-PLUMBING SECS.901.2,901.2.1.
 24) THE WATER VALVES FOR THE STACKED WASHER SHALL BE
 PROVIDED WITH ACCESS IN ACCORDANCE WITH 2017
 FBC-PLUMBING SEC.606.3.27)
 25) THE PLUMBING SHEETS NOTE" SEE PLANS FOR
 CONTINUATION" OF PLUMBING LINES. LIST THE SPECIFIC
 SHEET WHERE THESE CONTINUATION LINES CAN BE FOUND. WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
 26) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE
 COMMON AREA TOILET ROOM PER 2017 FBC-PLUMBING SECS.
 416.5, 607.1,
 27) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 COFFEE MAKER PER 2017 FBC-PLUMBING SEC.608.16.10.
 28) SHT. P-8.1 - PLUMBING FIXTURE CONNECTION SCHEDULE -
 NOTE #3 STATES " FIXTURES SHALL BE IN COMPLIANCE WITH
 MIAMI-DADE COUNTY WATER USE EFFICIENCY STANDARDS.
 CLARIFY.
 29) SHT. P-8.1 - PIPE MATERIAL SCHEDULE - NOTE #6
 REFERS TO THE 2007 FLORIDA PLUMING CODE. THE CODE THAT
 IS IN EFFECT IS THE 2017 EDITION. REVISE THE NOTE.
 30) SEPARATE PEMITS WILL BE REQUIRED FOR ALL BACKFLOW
 PREVENTION DEVICES.
 31) SUBMIT IRRIGATION PLANS IF A NEW IRRIGATION SYSTEM
 IS GOING TO BE INSTALLED. WPB AMEND. TO FBC SEC.
 107.2.1.
 32) SHT. P-1.0 - KEYED NOTE #3 REFERS TO THE CIVIL
 DRAWINGS FOR THE CONTINUATION OF THE DRAIN LINE FROM
 THE ROOF. THESE LINES ARE NOT SHOWN ON CIVIL DRAWING
 C-2.1. CLARIFY.
 33) SHT. P-7.3 - DETAIL #1 - THE DRINKING FOUNTAIN IS
 REQUIRED TO BE TRAPPED AND VENTED IN ACCORDANCE WITH
 2017 FBC-PLUMBING SECS.901.2, 901.2.1 , 1002.1.
 34) SHT. P-7.3 - DETAIL#1- THE LAVATORY IS REQUIRED TO
 BE VENTED.2017 FBC-PLUMBING SECS. 901.2, 901.2.1.
 35) SHT. P-7.3 - DETAIL # 1 - THE MOP SINK IS REQUIRED
 TO BE TRAPPED AND VENTED PER FBC-PLUMBING SECS.901.2,
 901.2.1 , 1002.1.
 36) THE DRINKING FOUNTAIN CANNOT DISCHARGE INTO A WET
 VENT PER 2017 FBC-PLUMBING SEC.912.1.
 37) PROVISIONS SHALL BE MADE FOR THERRMAL EXPANSION
 CONTRO IN THE WATER PIPING SYSTEML IN ACCORDANCE WITH
 2017 FBC-PLUMBING SEC.607.3.
 38) SUBMIT THE OCCUPANT LOAD FOR THE FITNESS CENTER,
 LOBBY, MAIL ROOM, OFFICE AND MAINTENANCE ROOM. A SECOND
 TOILET ROOM MAY BE REQUIRED IN ACCORDANCE WITH TABLE
 403.1 OF THE 2017 FBC-PLUMBING.
 39) THE DRINKING FOUNTAIN SHALL BE AVAILABLE FOR USE BY
 PERSONS OTHER THAN THOSE IN THE FITNESS CENTER.
 40) SHT. P-7.3 - DETAIL # 2 - THE WATER RISER SHOWS AN
 1 1/2 INCH LINE TO THE COFFEE MACHINE & DRINKING
 FOUNTAIN. CLARIFY.
  
 FIRE PROTECTION:
 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 SPRINKLER HEADS TO BE INSTALLED IN THE LIGHT HAZARD AND
 ORDINARY HAZARD AREAS. NFPA 13R SEC. 8.1.7 (12).
 2) SHT. FP-1 REFERS TO FP-1 FOR THE POINT OF SERVICE.
 THE POINT OF SERVICE IS NOT SHOWN ON FP-1. CLARIFY.SHOW
 THE POINT OF SERVICE ON SHT. C-2.3 PER FL. STATUTE
 633.021.
 3) THERE IS NO SPRINKLER HEAD SHOWN IN THE ELEVATOR
 PIT. COMPLY WITH NFPA 13 SEC. 8.15.5.
 4) SUBMIT A KEYNOTE LEGEND FOR THE KEYNOTES ON SHT.
 FP-1, BUILDING A RISER DIAGRAM.
 5) SHT. FP-1 - BUILDING A RISER DIAGRAM SHOWS THE BASE
 OF THE RISER TAG AS BEING ON THE THIRD FLOOR. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2020-12-09 Cont ID  
Sent By rgathrig Date 2020-12-09 Time 09:38 Rev Time 0.00
Received By rgathrig Date 2020-12-09 Time 09:37 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2020-11-23 Cont ID  
Sent By rgathrig Date 2020-11-23 Time 11:22 Rev Time 0.00
Received By rgathrig Date 2020-11-23 Time 11:21 Sent To  
Notes
2020-11-23 11:21:58PRIVATE PROVIDER REVIEW FOR INSPECTIONS IS FAILED
  
 NOTICE TO BUILDING OFFICIAL NAMES GFA INTERNATIONAL AS
 THE FIRM AND GEORGE DIXON AS THE PRIVATE PROVIDER.
 LICENSE NUMBERS FOR BUILDING CODE ADMINISTRATOR AND
 INSPECTOR WERE SUBMITTED FOR MR. DIXON. NO ADDITIONAL
 INFORMATION WAS SUBMITTED FOR ANY DULY AUTHORIZED
 REPRESENTATIVE. IS MR. DIXON GOING TO BE THE ONLY
 PERSON MAKING THE INSPECTIONS N THIS PROJECT?
  
 THE CERTIFICATE OF INSURANCE DOES NOT STATE THAT
 PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE
 FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER,
 AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS
 REQUIRED. ( FOUND IN 553.791 (4) )
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561-805-6679
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2020-08-14 Cont ID  
Sent By rmcphers Date 2020-08-14 Time 08:13 Rev Time 0.00
Received By rmcphers Date 2020-08-14 Time 08:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcphers Date 2020-04-02 Time 14:24 Rev Time 0.00
Received By rmcphers Date 2020-04-02 Time 14:24 Sent To  
Notes
2020-04-02 14:25:08SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2020-10-21 Cont ID  
Sent By rmcphers Date 2020-10-21 Time 07:42 Rev Time 0.00
Received By rmcphers Date 2020-10-21 Time 07:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-09-28 Cont ID  
Sent By medwards Date 2020-09-28 Time 14:33 Rev Time 0.00
Received By medwards Date 2020-09-28 Time 14:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-14 Cont ID  
Sent By rmcphers Date 2020-08-14 Time 08:25 Rev Time 0.00
Received By rmcphers Date 2020-08-14 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-16 Cont ID  
Sent By shill Date 2020-05-16 Time 14:29 Rev Time 0.00
Received By shill Date 2020-05-16 Time 14:29 Sent To  
Notes
2020-05-16 14:29:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVISO: FUTURE PERMITS WILL REQUIRE 3RD PARTY
 SIGNATURE (JAMES KHALIL, PE)
  
 2. PROVIDE ORIGINAL S&S SURVEY
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-02 Cont ID  
Sent By rmcphers Date 2020-04-02 Time 14:23 Rev Time 0.00
Received By medwards Date 2020-04-08 Time 16:44 Sent To  
Notes
2020-04-08 16:45:56MECHANICAL SHEETS- . FLORIDA PROFESSIONAL ENGINEERS MAY
 NOT SELF CERTIFY DIGITAL SIGATURES AND SEALS PER FBC FS
 668.003.
2020-04-02 14:24:30SURVEY NEEDS TO BE ELECTRONICALLY SIGNED AND SEALED

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2020-04-10 Cont ID  
Sent By shill Date 2020-04-10 Time 10:56 Rev Time 0.00
Received By shill Date 2020-04-10 Time 10:56 Sent To  
Notes
2020-04-10 10:56:47RESIDENT INSPECTOR NOT REQUIRED PER KEN CONRAD
  

Review Stop Z ZONING
Rev No 4 Status P Date 2020-10-27 Cont ID  
Sent By ajones Date 2020-10-27 Time 09:49 Rev Time 0.00
Received By ajones Date 2020-10-27 Time 09:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2020-10-14 Time   Rev Time 0.00
Received By ajones Date 2020-10-14 Time 10:46 Sent To  
Notes
2020-10-14 10:50:3310/14/20- FAILED. ELEVATIONS DO NOT MATCH THE PLANS
 APPROVED IN THE MINOR AMENDMENT.
  
 ANGELLA VANN
 [email protected]
 561-822-1441

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-19 Cont ID  
Sent By ajones Date 2020-08-19 Time 13:18 Rev Time 0.00
Received By ajones Date 2020-08-19 Time 13:18 Sent To  
Notes
2020-08-19 13:19:238/19/20- FAILED- WAITING ON MINOR AMENDMENT APPROVAL
  
 ANGELLA VANN
 [email protected]
 561-822-1441
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-04-28 Cont ID  
Sent By avann Date 2020-04-28 Time 11:51 Rev Time 0.00
Received By ajones Date 2020-04-28 Time 11:51 Sent To  
Notes
2020-04-28 11:51:124/28/2020- FAILED
 1. THE SITE PLAN DOES NOT MATCH THE APPROVED SITE PLAN
 ON FILE WITH THE PLANNING DIVISION.
 2. THERE SEEMS TO BE CHANGES IN THE ELEVATIONS
 (WINDOWS) THAN WHAT IS ON FILE WITH THE PLANNING
 DIVISION
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441