Plan Review Details - Permit 20030563
| Plan Review Stops For Permit 20030563 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-03-24 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-03-24 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2020-03-24 14:11:26 | HAD SPOKE TO M SANCHEZ BUILDING ADDRESS HAD ALREADY | | | BEEN ESTABLISHED. HOWEVER STILL NEED A LIST OF THE | | | INDIVIDUAL UNIT NUMBERS. PLEASE COORDINATE WITH ME | | | [email protected] 561-805-6659 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2020-10-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-21 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-21 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2020-10-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-09 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-09 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2020-10-09 10:02:25 | NEW APT. BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) REVISED DRAWING (S7.1) SHOWS WIND DESIGN | | | CALCULATIONS USING ASCE 7-16 - SHOULD BE USING ASCE | | | 7-10 PER FBC CHAPTER 35 | | | | | | PROVISO: | | | A) SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE | | | REQUIRED FOR: | | | LIGHT POLES/SITE LIGHTING | | | PARKING LOT | | | DETACHED STRUCTURES - GAZEBO ETC. | | | B) PROVIDE FLOORING IIC AND STC ACOUSTICAL TEST REPORTS | | | FOR REVIEW FOR THE TILE FLOORING BEFORE FLOORING | | | INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-13 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-13 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2020-08-13 13:33:16 | NEW 3 STORY APT. BLDG. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 2ND REVIEW | | | 1) PRODUCT APPROVAL PROVIDED FOR THE DWELLING UNIT | | | INSWING EXTERIOR DOORS DOES NOT MEET THE WATER | | | INFILTRATION REQUIREMENTS OF FBC 1709.5.1 | | | 2) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH | | | WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1 | | | 3) PRODUCT APPROVAL 19-0219.11 FOR THE SLIDING GLASS | | | DOOR DOES NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 | | | (PLEASE PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL.) | | | 4) PRODUCT APPROVAL 17-0614.05 FOR THE FIXED GLASS DOES | | | NOT MEET THE IMPACT REQUIREMENTS FBC 1609.1.2 (PLEASE | | | PROVIDE A COMPLETE SHUTTER PRODUCT APPROVAL) | | | 5) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO | | | COMPLY WITH FBC 1207 AS NOTED BELOW (A, B AND C) (YOU | | | NEED TO PROVIDE THE ACOUSTICAL LAB TEST REPORTS) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NONCOMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-03 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-01 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2020-04-03 09:14:39 | NEW 3 STORY APT. BLDG. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE A SIGNED AND SEALED SURVEY SHOWING | | | THE BASE FLOOD ELEVATION PER THE LATEST FIRM. | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR DOORS AND WINDOWS. | | | 3) DOORS THAT OPEN INTO THE UNITS NEED TO COMPLY WITH | | | WATER INFILTRATION REQUIREMENTS PER FBC 1709.5.1 | | | 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE ROOFING SYSTEMS. | | | 5) SEPARATE PERMITS ARE REQUIRED FOR - PAVING/PARKING, | | | DUMPSTER, RETAINING WALLS, PAVILION ETC. PLEASE PROVIDE | | | NOTES TO VERIFY THE UNDERSTANDING OF SUCH. | | | 6) PLEASE SHOW THE FLOORING SOUND TRANSMISSION TO | | | COMPLY WITH FBC 1207 AS NOTED BELOW (A,B AND C) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. | | | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM | | | CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED | | | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-08-13 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-08-13 |
Time |
11:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-04-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-21 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-20 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2020-04-21 14:32:06 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING | | | PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK | | | IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS | | | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF | | | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY | | | OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1 | | | 2. RISER DIAGRAM SHOWS THREE SETS OF THREE 400 KCMIL | | | CONDUCTORS FOR THE FEEDERS FROM FPL. THIS WOULD | | | INDICATE THAT THIS IS A SINGLE PHASE SERVICE, BUT THE | | | RISER INDICATED THIS IS A THREE PHASE SERVICE. PROVIDE | | | CLARIFICATION AND/OR CORRECTIONS. NEC 215.5; WPB FBC | | | 107.2.1 | | | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL | | | LOADS. IT APPEARS FOR THE METER CENTER THAT NEC 220.84 | | | IS BEING USED, BUT THIS CODE SECTION IS NOT APPLIED | | | CORRECTLY. ALL LOADS AT 100% SHOULD BE ADDED TOGETHER | | | AND THEN THE DEMAND FACTOR OF 34% APPLIED TO THIS | | | AMOUNT BASED ON 26 DWELLING UNITS. IT ALSO APPEARS THAT | | | 100% OF THE LOADS FROM EACH UNIT IS NOT BEING USED | | | CORRECTLY. THIS SHOULD INCLUDE ALL ITEMS DETAILED IN | | | NEC 220.84(C), INCLUDING ONLY THE LARGER OF THE AC OR | | | HEAT LOAD. WHEN THIS NUMBER IS CALCULATED, THEN 100% OF | | | THE HOUSE LOAD WOULD BE ADDED TO THAT FOR THE FINAL VA | | | LOAD BASED ON NEC 220.84(B). NEC 220 | | | 4. BASED ON LOADS DETAILED IN THIS SUBMISSION, I HAVE | | | CALCULATED THE LOAD ON THE SERVICE TO BE 1078 AMPS, | | | WHICH IS LARGER THAN THE DESIGNED SERVICE SUPPLIED. | | | PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED FOR | | | SERVICE EQUIPMENT AND FEEDERS. NEC 215.2, 220.84, | | | 408.30, 408.36 | | | 5. PANEL SCHEDULE FOR EACH UNIT SHOW A DIFFERENT LOAD | | | THAN THE LOAD CALCULATION TABLES. IT APPEARS THAT THIS | | | IS DUE TO THE CORRECT TYPE OF LOAD CALCULATION FOR | | | DWELLING UNITS NOT BEING USED, WHICH WOULD INCLUDE 3VA | | | PER SQUARE FOOT. INFORMATION SHOULD BE CONSISTENT. | | | CORRECT DISCREPANCIES. WPB FBC 107.2.1; NEC 220 | | | 6. IF SERVICE OR FEEDER SIZES ARE CHANGED, PROVIDE | | | UPDATED AIC CALCULATIONS. NEC 110.9, 110.10 | | | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 8. UNITS 2A AND 2B ALL SHOW THE FOLLOWING CODE | | | VIOLATION. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT | | | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. | | | THIS CIRCUIT CAN BE USED FOR LIGHTING AND RECEPTACLE | | | OUTLETS IN ONE BATHROOM, BUT THEN CANNOT BE USED TO | | | FEED ANOTHER BATHROOM. OR, THIS CIRCUIT CAN FEED ONLY | | | THE RECEPTACLES IN MULTIPLE BATHROOMS. PROVIDE | | | CORRECTION. NEC 210.11(C)(3) | | | 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12 | | | 10. LIGHT FIXTURE SCHEDULE DOES NOT INDICATE FIXTURES | | | THAT ARE RATED FOR WET LOCATIONS FOR SHOWERS, OR HAVE | | | ENCLOSED LIGHT BULBS FOR CLOSETS. PROVIDE NOTE OF | | | COMPLIANCE FOR EACH LOCATION. NEC 410.10(D), 410.16 | | | 11. PROVIDE COMPLIANCE FOR DWELLING UNITS: A MINIMUM OF | | | 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED | | | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A | | | MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED | | | LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY | | | LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1, R404.1 | | | 12. AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS | | | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND | | | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH | | | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8, 210.12 | | | 13. THERE IS A DISCREPANCY WITH FLOOR PLAN, RISER | | | DIAGRAM AND LOAD CALCULATIONS. THE RISER SHOWS A UNIT | | | 1209, BUT THIS IS NOT INCLUDED IN LOAD CALCS OR FLOOR | | | PLAN. IT APPEARS THAT THE HOUSE PANEL HAS BEEN CONFUSED | | | FOR UNIT 1205. CORRECT DISCREPANCIES SO THAT ALL | | | INFORMATION IS CONSISTENT. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2020-08-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2020-08-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-08-19 07:55:50 | REVIEWED UNDER FORMAL ENGINEERING SUBMITTAL E19100032. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-30 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-30 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2020-04-30 07:07:24 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | IF YOU HAVE AN ISSUED ENGINEERING PERMIT, OR A PENDING | | | APPLICATION, PLEASE ADVISE VIA EMAIL ([email protected]) | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-07-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-07-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-07-16 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-03-30 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-03-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-03-27 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2020-03-27 16:25:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET FA 2.1 - THERE DOES NOT APPEAR TO BE | | | NOTIFICATION DEVICES WITHIN THE SLEEPING ROOMS | | | | | | PER NFPA 101, CH 30 | | | | | | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. | | | 30.3.4.1 GENERAL. | | | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN | | | HEIGHT OR | | | WITH MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE | | | MEETING THE | | | REQUIREMENTS OF 30.3.4.1.2, SHALL BE PROVIDED WITH A | | | FIRE ALARM | | | SYSTEM IN ACCORDANCE WITH SECTION 9.6, EXCEPT AS | | | MODIFIED BY | | | 30.3.4.2 THROUGH 30.3.4.5. | | | | | | 30.3.4.3 NOTIFICATION. | | | 30.3.4.3.1 OCCUPANT NOTIFICATION SHALL BE PROVIDED | | | AUTOMATICALLY | | | IN ACCORDANCE WITH SECTION 9.6, AND BOTH OF THE | | | FOLLOWING SHALL | | | ALSO APPLY: | | | (1) VISIBLE SIGNALS SHALL BE INSTALLED IN UNITS | | | DESIGNED FOR THE | | | HEARING IMPAIRED. | | | (2) POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH 9.6.3.4 | | | SHALL BE | | | PERMITTED. | | | | | | 9.6.3.5 UNLESS OTHERWISE PROVIDED IN 9.6.3.5.1 THROUGH | | | 9.6.3.5.8, | | | NOTIFICATION SIGNALS FOR OCCUPANTS TO EVACUATE SHALL BE | | | AUDIBLE, AND | | | VISIBLE SIGNALS IN ACCORDANCE WITH NFPA 72, NATIONAL | | | FIRE ALARM | | | AND SIGNALING CODE. AND ICC/ANSI A117.1, AMERICAN | | | NATIONAL | | | STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS AND | | | FACILITIES, OR | | | OTHER MEANS OF NOTIFICATION ACCEPTABLE TO THE AUTHORITY | | | HAVING | | | JURISDICTION SHALL BE PROVIDED. | | | | | | NFPA 72 | | | | | | 18.4.5 SLEEPING AREA REQUIREMENTS. | | | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO | | | PROVIDE | | | SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A SOUND | | | LEVEL OF AT | | | LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 | | | DB | | | ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT | | | LEAST | | | 60 SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, | | | WHICHEVER IS | | | GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA | | | REQUIRED TO BE | | | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). | | | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR | | | RETRACTABLE | | | PARTITION, IS LOCATED BETWEEN THE NOTIFICATION | | | APPLIANCE AND | | | THE PILLOW, THE SOUND PRESSURE LEVEL SHALL BE MEASURED | | | WITH THE | | | BARRIER PLACED BETWEEN THE APPLIANCE AND THE PILLOW. | | | | | | PLEASE REVIEW AND CORRECT OR PROVIDE SPECIFIC CODE | | | REFERENCES AND NARRATIVE AS TO WHY NOT. | | | | | | | | | | | | 1A) FOR INFORMATIONAL AND FALSE ALARM REDUCTION | | | PURPOSES THE LOCATION OF MAUNAL PULL STATIONS MAY BE | | | REDUCED PER NFPA 101, CH 9 | | | | | | 9.6.2.6* FOR FIRE ALARM SYSTEMS USING AUTOMATIC FIRE | | | DETECTION OR | | | WATERFLOW DETECTION DEVICES TO INITIATE THE FIRE ALARM | | | SYSTEM IN | | | ACCORDANCE WITH CHAPTERS 11 THROUGH 43, NOT LESS THAN | | | ONE MANUAL | | | FIRE ALARM BOX, LOCATED AS REQUIRED BY THE AUTHORITY | | | HAVING | | | JURISDICTION, SHALL BE PROVIDED TO INITIATE A FIRE | | | ALARM SIGNAL. | | | | | | A.9.6.2.6 THE MANUAL FIRE ALARM BOX REQUIRED BY 9.6.2.6 | | | IS INTENDED | | | TO PROVIDE A MEANS TO MANUALLY ACTIVATE THE FIRE ALARM | | | SYSTEM WHEN THE AUTOMATIC FIRE DETECTION SYSTEM OR | | | WATERFLOW DEVICES | | | ARE OUT OF SERVICE DUE TO MAINTENANCE OR TESTING, OR | | | WHERE | | | HUMAN DISCOVERY OF THE FIRE PRECEDES AUTOMATIC | | | SPRINKLER SYSTEM | | | OR AUTOMATIC DETECTION SYSTEM ACTIVATION. WHERE THE | | | FIRE ALARM | | | SYSTEM IS CONNECTED TO A MONITORING FACILITY, THE | | | MANUAL FIRE | | | ALARM BOX REQUIRED BY 9.6.2.6 SHOULD BE CONNECTED TO A | | | SEPARATE | | | CIRCUIT THAT IS NOT PLACED ?ON TEST? WHEN THE DETECTION | | | OR SPRINKLER | | | SYSTEM IS PLACED ON TEST. THE MANUAL FIRE ALARM BOX | | | SHOULD BE | | | LOCATED IN AN AREA THAT IS ACCESSIBLE TO OCCUPANTS OF | | | THE BUILDING | | | AND SHOULD NOT BE LOCKED. | | | | | | PLEASE REVIEW AND IF IN AGREEMENT, CONSULT WITH MY | | | OFFICE FOR A SUITABLE LOCATION | | | | | | PROVIDE AN APPLICABLE NOTE. | | | | | | | | | 2) SHEET FP 2 - NO FIRE SPRINKLER IN THE ELEVATOR PIT | | | | | | PER NFPA 13R | | | | | | 6.6.8 ALL SITUATIONS REGARDING SPRINKLER LOCATION AND | | | POSITION | | | THAT ARE NOT DIRECTLY DISCUSSED IN NFPA 13R SHALL BE IN | | | ACCORDANCE | | | WITH NFPA 13. | | | | | | 8.15.5 ELEVATOR HOISTWAYS AND MACHINE ROOMS. | | | 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED | | | AT THE BOTTOM | | | OF EACH ELEVATOR HOISTWAY NOT MORE THAN 2 FT (0.61 M) | | | ABOVE THE FLOOR OF THE PIT. | | | 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE | | | ELEVATOR | | | HOISTWAY BY 8.15.5.1 SHALL NOT BE REQUIRED FOR | | | ENCLOSED, NONCOMBUSTIBLE | | | ELEVATOR SHAFTS THAT DO NOT CONTAIN COMBUSTIBLE | | | HYDRAULIC FLUIDS. | | | 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE | | | REQUIRED IN ELEVATOR | | | MACHINE ROOMS, ELEVATOR MACHINERY SPACES, CONTROL | | | SPACES, OR | | | HOISTWAYS OF TRACTION ELEVATORS INSTALLED IN ACCORDANCE | | | WITH THE | | | APPLICABLE PROVISIONS IN NFPA 101, OR THE APPLICABLE | | | BUILDING | | | CODE, WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL | | | ROOM, CONTROL SPACE, OR HOISTWAY OF TRACTION ELEVATOR | | | IS | | | DEDICATED TO ELEVATOR EQUIPMENT ONLY. | | | (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY | | | SPACE, CONTROL ROOM, CONTROL SPACE, OR HOISTWAY OF | | | TRACTION | | | ELEVATORS ARE PROTECTED BY SMOKE DETECTORS, OR OTHER | | | AUTOMATIC | | | FIRE DETECTION, INSTALLED IN ACCORDANCE WITH NFPA72. | | | (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL | | | SPACE, | | | OR HOISTWAY OF TRACTION ELEVATORS IS SEPARATED FROM THE | | | REMAINDER | | | OF THE BUILDING BY WALLS AND FLOOR/CEILING OR ROOF/ | | | CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF | | | NOT LESS | | | THAN THAT SPECIFIED BY THE APPLICABLE BUILDING CODE. | | | (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE | | | PERMITTED | | | TO BE STORED IN ELEVATOR MACHINE ROOMS, MACHINERY | | | SPACES, CONTROL ROOMS, CONTROL SPACES, OR HOISTWAYS OF | | | TRACTION | | | ELEVATORS. | | | (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC | | | TYPE. | | | 8.15.5.4* AUTOMATIC SPRINKLERS IN ELEVATOR MACHINE | | | ROOMS OR | | | AT THE TOPS OF HOISTWAYS SHALL BE OF ORDINARY- OR | | | INTERMEDIATETEMPERATURE | | | RATING. | | | 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY | | | SPRINKLERS SHALL | | | BE INSTALLED AT THE TOP OF ELEVATOR HOISTWAYS. | | | 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE | | | ELEVATOR HOISTWAY | | | BY 8.15.5.5 SHALL NOT BE REQUIRED WHERE THE HOISTWAY | | | FOR PASSENGER | | | ELEVATORS IS NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE AND | | | THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS OF | | | ASME | | | A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS. | | | | | | 8.15.5.7 COMBUSTIBLE SUSPENSION IN ELEVATORS. | | | 8.15.5.7.1 SPRINKLERS SHALL BE INSTALLED AT THE TOP AND | | | BOTTOM OF | | | ELEVATOR HOISTWAYS WHERE ELEVATORS UTILIZE COMBUSTIBLE | | | SUSPENSION | | | MEANS SUCH AS NONCIRCULAR ELASTOMERIC-COATED OR | | | POLYURETHANECOATED | | | STEEL BELTS. | | | 8.15.5.7.2 THE SPRINKLERS IN THE ELEVATOR HOISTWAY | | | SHALL NOT BE | | | REQUIRED WHEN THE SUSPENSION MEANS PROVIDE NOT LESS | | | THAN AN | | | FT-1 RATING WHEN TESTED TO THE VERTICAL BURN TEST | | | REQUIREMENTS | | | OF UL 62, FLEXIBLE CORDS AND CABLES, AND UL 1581, | | | REFERENCE STANDARD | | | FOR ELECTRICAL WIRES, CABLES, AND FLEXIBLE CORDS. | | | | | | PLEASE REVIEW AND PROVIDE DETAILS OR CORRECT | | | | | | | | | | | | 3) SHEET 2.3 - THERE ARE INDICATIONS OF FIRE LINE | | | UNDERGROUND. | | | | | | ALL FIRE LAINE UNDERGROUND WORK SHALL BE DONE UNDER | | | SEPARATE PERMIT AND SHOP DRAWINGS IN COMPLIANCE WITH | | | NFPA 24, STANDARD FOR THE | | | INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND THEIR | | | APPURTENANCES,2013 EDITION | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 4) SHEET E 7.4 - THERE ARE INDICATIONS OF A BDA SYSTEM. | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS | | | ENHANCEMENT SYSTEMS. | | | 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE | | | PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF | | | FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH | | | 24.5.2.2.3. | | | 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE | | | EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S), | | | EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES, | | | STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE | | | LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE | | | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH | | | 99 PERCENT FLOOR AREA RADIO COVERAGE. | | | 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING | | | AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA | | | RADIO COVERAGE. | | | 24.5.2.3 SIGNAL STRENGTH. | | | 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH | | | OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE | | | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED | | | THROUGHOUT THE COVERAGE AREA. | | | 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH | | | OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH | | | AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL | | | BE PROVIDED FROM THE COVERAGE AREA. | | | | | | THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL | | | STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST | | | PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN | | | ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES | | | NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE | | | PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A | | | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH | | | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. | | | | | | | | | YOU SHALL MAKE CONTACT AND COORDINATE WITH MARK FILLA, | | | PALM BEACH COUNTY, PUBLIC SAFETY RADIO SYSTEMS MANAGER, | | | FOR ALL RADIO SIGNAL DETAILS, OUTBOUND SIGNAL STRENGTH | | | AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE ON THAT | | | SYSTEM. | | | [email protected] 561-233-0837 | | | | | | | | | ALL BDA WORK SHALL BE INSTALLED UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS BY A QUALIFIED FCC LIC CONTRACTOR, | | | LISTED EQUIPMENT AND SPEC SHEETS, WITH A COLOR HEAT | | | SPECTUM FLOOR PLAN. | | | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | | ACKNOWLEDGEMENT. | | | | | | | | | | | | 5) SHEET G 1.2 - THERE ARE INDICATIONS OF A GAZEBO WITH | | | A BBQ INSTALLED; HOWEVER, THERE IS NO INDICATION OF | | | WHAT TYPE OF GRILL AND IF IT IS OF PERMANENT MOUNTING | | | PER MANUFACTURES SPEC. | | | | | | PLEAE PROVIDE THE TYPE AND MANAFCATURES SPECS. | | | | | | | | | 5A) SHEET G 1.2 - THERE IS NO INDICATION OF A FIRE | | | EXTINGUISHER AT THE GAZEBO AREA. | | | | | | PLEASE PROIVDE AT LEAT A 5LB ABC FIRE EXTINGUISHER IN | | | THIS AREA THAT IS CERTIFIED AND TAG BY A THRID PARTY FE | | | COMPANY. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-10-27 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-10-20 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-10-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-10-20 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-09-18 |
Time |
07:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-08-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-20 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-07-15 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-30 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-24 |
Time |
13:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-11-19 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-04 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2020-10-27 11:07:01 | RECEIPT MU 2020-30332 - $137.895.20 - PAID | | 2020-09-18 07:00:01 | 08/04/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-13 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-13 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2020-08-13 13:53:11 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | | | 2020-08-04 15:30:15 | 8/4/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-03 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-03 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2020-04-03 09:15:36 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-28 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-28 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2020-09-28 12:07:41 | APPROVED WITH PRIVISO: | | | DRYER BOOSTER FANS MUST BE LISTED AND LABELED TO UL | | | 705. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-04 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-04 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2020-08-04 12:14:07 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT-20030563 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-6.2 (NOTE-2) INDICATES THE USE OF A DRYER | | | BOOSTER FAN, PLEASE PROVIDE THE SPECS FOR THIS DEVICE | | | ALONG WITH THE UL APPROVAL. FBC FS 107.2.1 | | | | | | 2) SHEET M-5.3 INDICATES A MFCU-1A FOR THE PET WASHING | | | ROOM AND A MFCU-1B FOR THE BICYCLE STORAGE ROOM. SHEET | | | M-7.1 DOES NOT HAVE THESE UNITS LISTED IN THE EQUIPMENT | | | SCHEDULE. PLEASE BE CONSISTENT ON BOTH SHEETS. FBC FS | | | 107.2.1 | | | | | | 3) SHEET M-5.3 AND SHEET M-7.1 DO NOT SHOW OUTSIDE AIR | | | PROVIDED FOR THE OCCUPIABLE PET WASH ROOM OR THE | | | BICYCLE STORAGE ROOM, PLEASE SHOW VENTILATION | | | CALCULATIONS FOR THESE AREAS ALONG WITH HOW OUTSIDE AIR | | | WILL BE BROUGHT INTO THESE AREAS. FBC M 401.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-03 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-31 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2020-04-03 15:05:53 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT- 20030563 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | 1) PLEASE SHOW HOW YOU ARE MEETING CHAPTER 4 OF THE FBC | | | M, ARE YOU USING NATURAL VENTILATION OR MECHANICAL? | | | 2) PLEASE PROVIDE VENTILATION CALCULATIONS TO SHOW YOU | | | ARE BRINGING THE MINIMUM REQUIRED OA INTO EACH AREA OF | | | THE APARTMENTS. FBC M 403.3.2 | | | 3) PLEASE PROVIDE INFORMATION FOR EACH AHU/CU. | | | INCLUDING MAX. AIR SUPPLIED, RETURN AIR VOLUME AND OA | | | NEEDED. . FBC WPB 107.2.1 | | | 4) PLEASE SHOW HOW YOU ARE PROVIDING EXHAUST FROM THE | | | KITCHENS. FBC M TABLE 430.3.1.1 | | | 5) SHEET M.4.1- PLEASE SHOW ROOF ACCESS ON THIS SHEET | | | OR GIVE A SHEET REFERENCE ON THIS SHEET SHOWING THE | | | ROOF ACCESS. FBC M 306.5 | | | 6) PLEASE PROVIDE A DRAWING SHOWING THE LOCATION OF THE | | | DRYER. FBC WPB 107.2.1 | | | 7) PLEASE PROVIDE DRYER DUCT LENGTHS FOR EACH UNIT. FBC | | | M 504.8.4.1 | | | 8) PLEASE SHOW DRYER DUCT MAKEUP AIR LOCATION AND SIZE | | | OF DUCT OR TRANSFER GRILL. FBC M 504.6 | | | 9) IF DRYER IS IN THE SAME CLOSET AS THE AHU SHOW HOW | | | THIS DESIGN MEETS FBC M 602 FOR PLENUMS. | | | 10) PLEASE PROVIDE CFM?S FOR ALL TRANSFER GRILLS AND | | | RETURNS. FBC M 601.5 NOTES (3)&(4). | | | 11) PLEASE PROVIDE A DETAILED DRAWING SHOWING THE MAKE | | | UP OF THE RAG FROM MASTER BEDROOM TO LIVING. FBC WPB | | | 107.2.1 | | | 12) WHEN YOU DOWNLOADED THE SHEETS INTO PROJECTDOX YOU | | | MISLABELED SHEET M5.2. THIS SHEET SHOULD REFERENCE UNIT | | | 1B AND 2B. IN PROJECTDOX THE PAGE IS SHOWING 1B & 2A. | | | 13) SHEET M-5.1 UNIT 1A PLEASE IDENTIFY THE AHU UNIT. | | | FBC WPB 107.2.1 | | | 14) SHEET M-5.1: UNIT 1A THE EXHAUST LOUVER THAT IS | | | LABELED DRYER VENT LOUVER IS GOING TO EF-1 IN THE | | | BATHROOM OFF FROM THE KITCHEN. PLEASE CORRECT THIS. FBC | | | WPB 107.2.1 | | | 15) SHEET M-5.1: UNIT 1A THE OTHER EXHAUST DUCT IS | | | GOING TO A LOCATION IN THE CLOSET WITH THE DOUBLE DOORS | | | AND APPEARS TO STOP. PLEASE PROVIDE A DETAIL DRAWING OF | | | WHERE THIS DUCT TERMINATES. FBC WPB 107.2.1 | | | 16) SHEET M-5.1: UNIT 1A PLEASE PROVIDE CFM?S FOR THE | | | RETURN. FBC WPB 107.2.1 | | | 17) SHEET M-5.1: PLEASE SHOW THAT ALL EXHAUST | | | TERMINATIONS FOR THIS PROJECT MEET FBC M 501.3.1. | | | 18) SHEET M-5.1: PLEASE SHOW THAT ALL O.A. INTAKES FOR | | | THIS PROJECT MEET FBC M 401.4. | | | 19) SHEET M-5.1: UNIT 2A IT APPEARS THAT THE DUCT | | | LABELED ?DRYER VENT? IS GOING INTO THE AHU/WATER HEATER | | | ROOM. DETAILS ON M6.1 DOES NOT SHOW A DRYER IN THIS | | | LOCATION. | | | 20) SHEET M-7.1: THERE ARE SEVERAL LOCATIONS ON THE | | | SHEET THAT ARE NOT INCLUDED IN THIS PROJECT. PLEASE | | | REMOVE ROOMS AND EQUIPMENT FROM THIS SHEET THAT ARE NOT | | | RELATED TO THIS PERMITTED PROJECT. | | | 21) SHEET M-5.2 SHOWS A UNIT 1B ON THE FIRST FLOOR. | | | SHEET M-7.1 DOES NOT MENTION A 1B1 IN THE LOCATIONS | | | COLUMN. PLEASE CORRECT THIS. . FBC WPB 107.2.1 | | | 22) PLEASE VERIFY ACTUAL AIR FLOW FROM SHEET M-7.1 | | | MATCHES THE INDIVIDUAL UNIT SHEETS. . FBC WPB 107.2. | | | 23) SHEET M-6.2 PLEASE SHOW THAT THE MINI-SPLIT UNITS | | | MEET SECTION 307.2.4.1 OF FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-10-21 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-10-21 |
Time |
04:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-10-20 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-10-08 |
|
|
Cont ID |
|
| Sent By |
lacrespo |
Date |
2020-10-08 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-10-06 |
Time |
05:11 |
Sent To |
|
|
| Notes |
| 2020-10-07 06:47:33 | 1) SUBMIT FIRE STOPPING DETAILS FOR NON-METALLIC PIPE | | | THROUGH FIRE RATE FLOORS.A DETAIL HAS BEN SUBMITTED FOR | | | WALLS BUT NOT FOR FLOORS AS PREIOUSLY REQUESTED.WPB | | | AMEND. TO FBC SEC. 107.3.5.1.1 (4). | | | 2) SHT.P7.4 - UNIT 2A - #1208 - RISER 2SA2 IS LABELED | | | AS 2S2A ON SHTS.P2.1 & P5.2. CLARIFY. 2ND REQUEST. | | | 3) SHT. P7.4 - UNIT 2A - #1208 THE WATER CLOSET AND THE | | | TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING | | | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A | | | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 4) SHT. P7.4 - UNIT 1A - #1207 - THE SHOWER AND WATER | | | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE | | | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT | | | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, | | | 5) SHT. P7.4 - UNIT 1A - #1207 - THE WATER CLOSET AND | | | THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A | | | SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 6) SHT. P7.4 - UNIT 1A - #1206 - THE WATER CLOSET AND | | | THE TUB ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A | | | SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 7) SHT. P7.4 - UNIT 2B - #1205 - THE SHOWER AND WATER | | | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE | | | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT | | | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, | | | 8) SHT. P7.4 - UNIT 2B - #1205 - THE WATER CLOSET AND | | | THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING | | | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A | | | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 9) SHT. P7..4 - UNIT 2B - #1204 - THE WATER CLOSET AND | | | THE TUB IN THE HALL BATH ARE NOT VENTED. FBC-PLUMBING | | | SEC.901.2, 901.2.1,SINCE THESE FIXTURES ARE ON A | | | SEPARATE FIXTURE BRANCH, A VENT IS RQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 10) SHT. P7.5 - UNIT2B - #1204 - THE SHOWER AND WATER | | | CLOSET IN THE MASTER BATHROOM ARE NOT VENTED.SINCE | | | THESE FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT | | | IS REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1, | | | 11) SHT. P7.5 - UNIT 1A - #1203 - THE WATER CLOSET AND | | | THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2, | | | 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE | | | BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2, | | | 901.2.1, | | | 12) SHT. P7.5 - UNIT 1A - #1202 - THE WATER CLOSET AND | | | THE TUB ARE NOT VENTED. FBC-PLUMBING SEC.901.2, | | | 901.2.1,SINCE THESE FIXTURES ARE ON A SEPARATE FIXTURE | | | BRANCH, A VENT IS RQUIRED. FBC-PLUMBING SEC.901.2, | | | 901.2.1, | | | 13) SHT. P7.5 - UNIT 2A - #1201 - THE TUB AND WATER | | | CLOSET IN THE HALL BATHROOM ARE NOT VENTED.SINCE THESE | | | FIXTURES ARE ON A SEPARATE FIXTURE BRANCH, A VENT IS | | | REQUIRED. FBC-PLUMBING SEC.901.2, 901.2.1. | | | 14) SHT. P7.5 - UNIT 2A - #1201 - THE SHOWER AND WATER | | | CLOSET IN THE MASTER BATH ARE NOT VENTED. THE LAVATORY | | | FIXTURE BRANCH SHALL BE LOCATED BETWEEN THE WATER | | | CLOSET AND THE SHOWER.FBC-PLUMBING SEC.901.2, 912.1. | | | 15) SHT. P7.6 - RISER S1A - THE TUB AND WATER CLOSET | | | ARE NOT VENTED. THE LAVATORY DRAIN AND VENT SHALL BE | | | LOCATED BETWEEN THE WATER CLOSET AND THE SHOWER. | | | FBC-PLUMBING SEC.901.2, 912.1. | | | 16) SHT. P7.7 - UNIT 2A - RISER S2A - THE TUB AND WATER | | | CLOSET ARE NOT VENTED.THE LAVATORY DRAIN AND VENT SHALL | | | BE LOCATED BETWEEN THE WATER CLOSET AND THE TUB. | | | FBC-PLUMBING SEC.901.2, 912.1. | | | 17) SHT. P7.7 - UNIT 2A - RISER 2S2A - THE SHOWER AND | | | WATER CLOSET ARE NOT VENTED. THE LAVATORY DRAIN AND | | | VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND THE | | | SHOWER. FBC-PLUMBING SEC.901.2, 912.1. | | | 18) SHT. P7.8 - UNIT 2B - RISER S2B - AS DRAWN, THE | | | WATER CLOSET AND TUB ARE NOT VENTED.THE LAVATORY DRAIN | | | AND VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET AND | | | THE TUB OR THE WATER CLOSET AND TUB SHALL BE INSTALLED | | | ON A HORIZONTAL WET VENT. FBC-PLUMBING SEC.901.2, | | | 912.1. | | | 19) SHT. P7.8 - UNIT 2B - RISER S2B - THE WATER CLOSET | | | AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE | | | ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 20) SHT. P7.8 - UNIT 1B - RISER S1B - THE WATER CLOSET | | | AND THE SHOWER ARE NOT VENTED. SINCE THESE FIXTURES ARE | | | ON A SEPARATE FIXTURE BRANCH, A VENT IS REQUIRED. | | | FBC-PLUMBING SEC.901.2, 901.2.1, | | | 21) SHT. P7.2 - DETAIL #1 - THE WATER CLOSET AND SHOWER | | | ARE NOT VENTED. SINCE THESE FIXTURES ARE ON A SEPARATE | | | FIXTURE BRANCH, A VENT IS REQUIRED. FBC-PLUMBING | | | SEC.901.2, 901.2.1, | | | 22) SHT. P7.2 - DETAIL #3 - THE DISHWASHER SHALL | | | DISCHARGE INDIRECTLY IN ACCORDANCE WITH FBC-PLUMBING | | | SEC.802.1.6. | | | | | | REVIEW IS INCOMPLETE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2020-08-10 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-08-10 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-08-05 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2020-08-10 05:43:03 | 1) SHT.A-0.1 - DETAIL #3 - UNIT 2A - THIS LAYOUT DOES | | | NOT COMPLY WITH THE FAIR HOUSING ACT DESIGN MANUAL, | | | CHAPTER 7, PAGE 7.56 & 7.57. THE ONLY FIXTURE PERMITTED | | | TO BE ADJACENT TO THE SHOWER IS A LAVATORY MOUNTED ON | | | THE CONTROL WALL BESIDE THE SHOWER AND MAY OVERLAP THE | | | CLEAR FLOOR SPACE BY A MAXIMUM OF 6 INCHES. THE PORTION | | | OF THE LAVATORY THAT OVERLAPS THE CLEAR FLOOR SPACE | | | MUST HAVE KNEE SPACE BELOW OR A REMOVABLE VANITY | | | CABINET. A 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR | | | SPACE MUST BE PROVIDED PARALLEL TO THE SHOWER AND FLUSH | | | WITH THE CONTROL WALL. 2ND REQUEST. | | | 2) THE PRESSURE CYLINDER FOR THE ELEVATOR SHALL BE | | | PROTECTED IN ACCORDANCE WITH 2017 FBC-BUILDING | | | SEC.3011. I COULD NOT FIND THIS DETAIL ON THE PLANS. | | | PLEASE SUBMIT THE SPECIFIC PAGE WHERE THIS DETAIL CAN | | | BE FOUND. 2ND REQUEST. | | | 3) FIRESTOPPING DETAILS HAVE BEEN SUBMITTED FOR METAL | | | PIPE THROUGH RATED WALLS AND FLOORS. IF PVC PIPE IS TO | | | BE INSTALLED, SUBMIT FIRESTOPPING ASSEMBLY DETAILS FOR | | | THE PVC PIPE THROUGH RATED FLOORS AND WALLS.WPB AMEND. | | | TO FBC SEC. 107.2.1, 107.3.5.1.1. | | | 4) SHT. P7.2 - DETAIL #1 - A MAXIMUM OF 10 FIXTURE | | | UNITS SHALL BE VENTED BY A 1 1/2 INCH VENT PER | | | FBC-PLUMBING TABLE 906.1.AS DRAWN, 15 FIXTURE UNITS ARE | | | BEING VENTED BY THE 1 1/2 INCH VENT. REFER TO | | | FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT VALUE FOR A | | | BATHROOM GROUP. | | | 5) SHT. P7.3 - THE HOSE BIBBS SHALL BE EQUIPPED WITH | | | SEPARATE SHUTOFF VALVES PER FBC-PLUMBING SEC.606.2 (2). | | | 6) SHT. P7.3 - PROVIDE RISER TAGS FOR THE 1 1/2 INCH | | | LINE UP TO THE 2ND & 3RD FLOOR UNITS AND FOR THE 4 INCH | | | SANITARY FROM THE 2ND & 3RD FLOOR UNITS. WPB AMEND. TO | | | FBC SEC. 107.3.5.1.3. | | | 7) SHT. P7.4 - UNIT 2A - #1208 - RISER 2SA2 APPEARS TO | | | BE LABELED AS 2S2A ON SHT. P5.2.. CLARIFY. | | | 8) SHT. P7.4 - UNIT 2A - #1208 - RISER 2V2A APPEARS TO | | | BE LABELED AS 2V2D ON SHT. P2.1. CLARIFY. | | | 9) SHT.P7.4 - UNIT 1A - #'S 1206 & 1207 - FIRST FLOOR | | | SANITARY - THE KITCHEN SINK IS DISCHARGING INTO THE | | | HORIZONTAL WET VENT. ONLY FIXTURES WITHIN THE BATHROOM | | | GROUP SHALL CONNECT TO THE WET VENTED HORIZONTAL BRANCH | | | DRAIN. THE KITCHEN SINK SHALL CONNECT TO THE 4 INCH | | | HORIZONTAL DRAIN DOWNSTREAM OF THE SHOWER.FBC-PLUMBING | | | SEC.912.1. | | | 10) SHT. P7.4 - UNIT 2B - #1205 - FIRST FLOOR SANITARY | | | - THE SHOWER AND WATER CLOSET ARE NOT VENTED.THE | | | LAVATORY DRAIN & VENT SHALL BE LOCATED BETWEEN THE | | | WATER CLOSET AND THE SHOWER. FBC PLUMBING SEC. 901.2, | | | 11) SHT. P7.4 - THE 2 INCH SANITARY LINE FOR THE PET | | | WASH GOES NOWHERE. SHOW THE CONTINUATION AND | | | TERMINATION POINT OF THIS LINE AND IDENTIFY IT WITH A | | | RISER TAG IF APPLICABLE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 12) SHT. P7.4 - VENT RISER V1B SHOWN AT THE PET WASH IS | | | NOT SHOWN ON SHT. P2.1 - CLARIFY. | | | 13) SHT. P7.4 - UNIT 2B - #1204 - MASTER BATH - VENT | | | VTB APPEARS TO BE LABELED AS 2V2B ON SHT. P2.1. | | | CLARIFY. | | | 14) SHT. P7.4 - UNIT 2B - #1205 - HALL BATH - RISER | | | 2V2B APPEARS TO BE LABELED AS V2B ON SHT. P2.1.THIS | | | ALSO OCCURS ON THE 2ND AND 3RD FLOOR PLAN ON P2.1. | | | CLARIFY. | | | 15) SHT. P7.5 - UNIT 2B -#1204 - HALL BATH - RISER 2V2B | | | APPEARS TO BE LABELED AS V2B ON SHT. P2.1. THIS ALSO | | | OCCURS ON THE 2ND AND 3RD FLOOR PLAN ON P2.1. CLARIFY. | | | 16) SHT. P7.5 - UNIT 2B - #1204 - RISER S2B IS NOT | | | SHOWN ON SHT. P2.1 - CLARIFY. | | | 17) SHT. P7.5 - UNIT 2B -#1204 - HALL BATH - FIRST | | | FLOOR SANITARY - THE SHOWER AND WATER CLOSET ARE NOT | | | VENTED.THE LAVATORY DRAIN & VENT SHALL BE LOCATED | | | BETWEEN THE WATER CLOSET AND THE SHOWER. FBC PLUMBING | | | SEC. 901.2, | | | 18) SHT. P7.5 - UNIT 2A -#1201 - MASTER BATH - RISER | | | LABELED AS V2A APPEARS TO BE LABELED AS 2V2D ON SHT. | | | P2.1. CLARIFY. | | | 19) SHT. P7.5 - UNIT 2A - #1201 -MASTER BATH - RISER | | | LABELED AS S2A APPEARS TO BE LABELED AS 2S2A ON SHT. | | | P2.1. THIS ALSO OCCURS ON THE 2ND & 3RD FLOORS. ALSO, | | | THE VENT RISER FOR MASTER BATH LAVATORY IS NOT SHOWN ON | | | THE PLAN VIEW FOR THE 2ND AND 3RD FLOORS. CLARIFY | | | 20) SHT. P7.5 - UNIT 2A - #1201 - HALL BATH - THE | | | SHOWER AND WATER CLOSET ARE NOT VENTED.THE LAVATORY | | | DRAIN & VENT SHALL BE LOCATED BETWEEN THE WATER CLOSET | | | AND THE SHOWER. FBC PLUMBING SEC. 901.2, | | | 21) SHT. P7.5 - UNIT 2A - #1201 - HALL BATH - RISER | | | LABELED AS 2V2A APPEARS TO BE LABELED AS V2A ON SHT | | | P2.1. THIS ALSO OCCURS ON THE 2ND AND 3RD FLOORS. | | | CLARIFY. | | | 22) SHT. P7.5 - UNIT 2A - #1201 - RISER LABELED AS 2S2A | | | APPEARS TO BE LABELED AS S2A ON SHT. P2.1. THIS ALSO | | | OCCURS IN THE SAME UNIT ON THE 2ND & 3RD FLOORS. | | | CLARIFY. | | | 23) SHT. P7.6 - RISER S1A - THE SHOWER AND WATER CLOSET | | | ARE NOT VENTED.THE LAVATORY DRAIN & VENT SHALL BE | | | LOCATED BETWEEN THE WATER CLOSET AND THE SHOWER. FBC | | | PLUMBING SEC. 901.2, | | | 24) SHT. P7.7 - UNIT 2A - RISER S2A - THE SHOWER AND | | | WATER CLOSET ARE NOT VENTED.THE LAVATORY DRAIN & VENT | | | SHALL BE LOCATED BETWEEN THE WATER CLOSET AND THE | | | SHOWER. FBC PLUMBING SEC. 901.2. | | | 25) SHT. P7.7 - UNIT 2A - RISER 2SA2 FOR THE MASTER | | | BATH APPEARS TO BE LABELED AS 2S2A ON SHT. P5.2 - | | | CLARIFY. | | | 26) CHECK ALL THE RISER TAGS ON THE PLAN VIEW SHEETS | | | AGAINST THE SANITARY RISER DIAGRAMS TO ENSURE THE RISER | | | TAGS CORRELATE THROUGH EACH FLOOR. REFER TO SHEETS | | | P2.1, P7.4, P7.5, P7.6 & P7.7. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 27) SHT. P7.8 - UNIT 2B - RISER S2B - 2ND & 3RD FLOOR - | | | THE SHOWER AND WATER CLOSET IN THE HALL BATH ARE NOT | | | VENTED.THE LAVATORY DRAIN & VENT SHALL BE LOCATED | | | BETWEEN THE WATER CLOSET AND THE SHOWER. FBC PLUMBING | | | SEC. 901.2, | | | 28) SHT. P7.8 - UNIT 2B - RISER S2B - THE KITCHEN SINK | | | IS DISCHARGING INTO THE HORIZONTAL WET VENT. ONLY | | | FIXTURES WITHIN THE BATHROOM GROUP SHALL CONNECT TO THE | | | WET VENTED HORIZONTAL BRANCH DRAIN. THE KITCHEN SINK | | | SHALL CONNECT TO THE 4 INCH HORIZONTAL DRAIN DOWNSTREAM | | | OF THE SHOWER.FBC-PLUMBING SEC.912.1. | | | 29) SHT.P7.8 - DETAIL #1 - RISERS 2V2B & V2B - A | | | MAXIMUM OF 10 FIXTURE UNITS SHALL BE VENTED BY A 1 1/2 | | | INCH VENT PER FBC-PLUMBING TABLE 906.1.AS DRAWN, 15 | | | FIXTURE UNITS ARE BEING VENTED BY THE 1 1/2 INCH VENT. | | | REFER TO FBC-PLUMBING TABLE 709.1 FOR FIXTURE UNIT | | | VALUE FOR A BATHROOM GROUP. | | | 30) PLEASE IDENTIFY THE TUBS AS TUBS ON THE RISER | | | DIAGRAMS AND NOT AS SHOWERS. | | | 31) SUBMIT A CONDENSATE RISER FOR REVIEW. SIZING SHALL | | | COMPLY WITH FBC-PLUMBING SEC.314. | | | 32) THE SANITARY RISERS SHOW THE DIRECTION OF FLOW AT | | | SEVERAL AREAS OF THE RISERS. REVISE THE RISERS TO | | | REFLECT CORRECT DIRECTION OF FLOW. | | | 33) SUBMIT A WATER HEATER PAN DRAIN RISER FOR | | | REVIEW.WPB AMEND. TO FBC SEC. 107.2.1. | | | 34) IF A SUMP PUMP WILL BE INSTALLED IN THE ELEVATOR | | | SUMP, THE INSTALLATION SHALL COMPLY WITH FBC-PLUMBING | | | SEC.1003.4. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-04-05 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-04-04 |
Time |
02:01 |
Sent To |
|
|
| Notes |
| 2020-04-04 11:47:32 | PLUMBING: | | | 1) SHT. A-0.1 - DETAILS #1, #2 & #3 - SHOWS THE | | | CENTERLINE OF THE WATER CLOSET FROM THE EDGE OF THE TUB | | | AND/OR SHOWER AS ONE- FOOT SEVEN INCHES, ONE- FOOT NINE | | | INCHES AND ONE- FOOT EIGHT INCHES RESPECTIVELY. THE | | | DISTANCE SHALL BE 0NE -FOOT SIX INCHES ( 18" ) ABSOLUTE | | | AS REQUIRED BY THE FAIR HOUSING ACT DESIGN MANUAL, | | | CHAPTER 6, PG. 6.7. THESE DIMENSIONS MUST ALSO BE | | | CHANGED ON THE ELEVATION DRAWINGS. | | | 2) SHT. A-0.1 - DETAIL #7 - SHOW THE WIDTH OF THE | | | PROPOSED REINFORCEMENT FOR THE TUB. THE LENGTH IS SHOWN | | | AS 48 INCHES.WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SHT. A-0.1 - THE UNITS THAT HAVE A SHOWER DO NOT | | | COMPLY WITH THE REQUIREMNT FOR THE CLEAR FLOOR SPACE | | | THAT IS REQUIRED BY THE FHA DESIGN MANUAL CHAPTER 7, | | | PG.7.56. AS PROPOSED, THIS LAYOUT DOES NOT COMPLY WITH | | | HAVING THE WATER CLOSET NEXT TO THE SHOWER.A 30 INCH | | | WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE MUST BE PROVIDED | | | AT SHOWER STALLS, PARALLEL TO THE FIXTURE AND FLUSH | | | WITH THE CONTROL WALL. FHA DESIGN MANUAL PART TWO, | | | CHAPTER 7, PART B, PG. 7.56.. | | | 4) SHT. A-0.1 - DETAIL #3 NOTES "SEE DETAIL #6 FOR GRAB | | | BAR REINFORCEMENT AT SHOWER." DETAIL #6 SHOWS | | | REINFORCEMENT AT TOILETS.REVISE THE NOTE TO REFER TO | | | DETAIL #8. | | | 5) SHT. A-0.1 - DETAIL #3 NOTES " SEE DETAIL #8 FOR | | | REINFORCEMENT AT TOILET." DETAIL #8 SHOWS REINFORCEMENT | | | AT SHOWERS. REVISE THE NOTE TO REFER TO DETAIL #6. | | | 6) SHT. A-0.1 - DETAIL #8 - THE SHOWER REINFORCEMENT | | | THAT IS SHOWN FOR A FUTURE SHOWER SEAT DOES NOT COMPLY | | | WITH THE FAIR HOUSING ACT DESIGN MANUAL. THE | | | REINFORCING MUST START AT THE FLOOR AND RISE TO A | | | MINIMUM HEIGHT OF 24 INCHES, NOT START 6 INCHES ABOVE | | | THE FLOOR PER PART TWO, CHAPTER 6, PG. 6.13 OF THE FAIR | | | HOUSING ACT DESIGN MANUA. REVISE THE DETAIL. | | | 7) THE PLANS REFER TO A GYM. I DID NOT SEE A GYM | | | LOCATED ON THE PLANS. CLARIFY. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 8) SHT. A-1.3 - DETAIL #5 - CLARIFY THE CLEARANCES FOR | | | THE WATER CLOSET FROM THE EDGE OF THE VANITY AND THE | | | TUB/SHOWER. COMPLY WITH FHA DESIGN MANUAL. | | | 9) SHT. A-1.4 - INTERIOR ELEVATION #6 - THE CENTERLINE | | | OF THE WATER CLOSET SHALL BE 18 INCHES PER THE FHA | | | DESIGN MANUAL.. THE PLANS SHOWS ONE FOOT NINE INCHES | | | (21 INCHES). | | | 10) SHT.A-1.5 - INTERIOR ELEVATIONS #5 & #9 - THE | | | CENTERLINE TO THE WATER CLOSET SHALL BE 18 INCHES TO | | | THE CENTERLINE, NOT 20 INCHES AS SHOWN.FHA DESIGN | | | MANUAL, PART TWO, CHAPTER 7, PART B PG. 7.43. | | | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE PET | | | WASH UNIT. WPB AMEND. TO FBC SEC. 107.2.1. | | | 12) SUBMIT ADDITIONAL INFORMATION ON THE RAINWATER | | | CALCULATIONS. SHOW HOW YOU ARRIVED AT THE FINAL | | | RESULTS. THE PARAPET WALL MUST BE INCLUDED IN THE | | | RAINWATER CALCULATIONS PER THE 2017 FBC-PLUMBING | | | SECS.1106.4, 1106.5.SEE SHT. A-3. | | | 13) IS THE ELEVATOR A TRACTION TYPE OR HYDRAULIC TYPE? | | | IF OF A HYDRAULIC TYPE , THE PRESSURE CYLINDER SHALL BE | | | PROTECTED IN ACCORDANCE WITH 2017 FBC -BUILDING | | | SEC.3011. | | | 14) THE PLANS SHOW A BBQ GRILL. SUBMIT DETAILS ON THE | | | GRILL AND ANY VENTILATION REQUIREMENTS. IS THIS A GAS | | | GRILL OR A CHARCOAL BURNING GRILL. CLARIFY ON THE | | | PLANS. | | | 15) SUBMIT GAS RISER DIAGRAM AND MANUFACTURER'S | | | SPECIFICATIONS FOR THE GRILL IF IT UTILIZES GAS.WPB | | | AMEND. TO FBC SEC. 107.3.5.1.6. | | | 16) SUBMIT FIRESTOPPING DETAILS FOR PIPE PENETRATIONS | | | THROUGH FRAMED RATED WALLS. THE SUBMITTED DETAIL IS FOR | | | PENETRATIONS THROUGH A CONCRETE FLOOR OR A BOLCK WALL. | | | WPB AMEND. TO FBC SEC. 107.3.5.1.1. | | | 17) SHT. P-1.0 - IDENTIFY ALL RISERS ON THE PLUMBING | | | SHEETS.. PROVIDE RISER TAG NUMBERS FOR EACH RISER ( | | | WATER & SANITARY).WPB AMEND. TO FBC SEC.107.3.5.1.3. | | | 18) SUBMIT A COMPLETE UNDERGROUND SANITARY RISER | | | DIAGRAM SHOWING ALL SANITARY RISERS AND PROVIDE RISER | | | TAG NUMBERS SO THE RISERS WILL CORRELATE WITH RISERS | | | THAR ARE TO BE SHOWN ON THE FLOOR PLAN. WPB AMEND. TO | | | FBC SEC. 107.3.5.1.3. | | | 19) SHT. P-2.1 - THE FIRST FLOOR PLAN SHOWS TRENCH | | | DRAINS BY THE ELEVATORS.AND THE PLAN REFERS TO THE | | | CIVIL DRAWINGS. THESE DRAINS ARE NOT SHOWN ON THE CIVIL | | | DRAWINGS. CLEARLY SHOW THE LOCATION OF THESE DRAINS ON | | | THE PLANS AND SPECIFY THE SPECIFIC SHEET WHERE THEY ARE | | | LOCATED. WPB AMEND. TO FBC SEC. 107.1, 107.3.5.1.3. | | | 20) SHT. P-2.1 - THERE ARE NO PIPE SIZES ON THE PIPES | | | AND THE RISERS NEED TO HAVE RISER TAGS AND IDENTIFIED | | | AS TO THE USE. WPB AMEND. TO FBC SEC. 107.2.1.REFER TO | | | THE SPECIFIC CIVIL DRAWING WHERE THE REQUIRED | | | INFORMATION CAN BE FOUND. | | | 21) THE UNITS WITH THE HALL BATH HAVE THE HALL BATH | | | MISSING FROM THE SANITARY AND WATER RISER. WPB AMEND. | | | TO FBC SEC. 107.3.5.1.3. | | | 22) SHTS. P-5.1 & P-5.2 - KEYNOTE #2 IS NOT SHOWN ON | | | THE PLANS. CLARIFY. | | | 23) SHT. P-7.1 - A FULL OPEN VALVE IS REQUIRED AT THE | | | BASE OF THE WATER RISER PER 2017 FBC-PLUMBING SEC.606.1 | | | (4). | | | 24) SUBMIT A COMPLETE WATER RISER FOR THE 2 BATH UNIT. | | | WPB AMEND. TO FBC SEC. 107.3.5.1.3. | | | 25) SHT. P-7.2 - DETAIL #3 - THE KITCHEN SINKS ARE NOT | | | VENTED. 2017 FBC-PLUMBING SECS.901.2,901.2.1. | | | 26) SHT. P-7.3 - DETAIL #1 - THE FLOOR DRAINS ARE NOT | | | VENTED. 2017 FBC-PLUMBING SEC.901.2,901.2.1. | | | 27) A TRAP AND VENT IS REQUIRED ON THE PET WASH | | | DRAIN.2017 FBC-PLUMBING SEC. 1002.1, SECS.901.2,901.2.1 | | | 28) THE PLUMBING SHEETS NOTE" SEE PLANS FOR | | | CONTINUATION" OF PLUMBING LINES. LIST THE SPECIFIC | | | SHEET WHERE THESE CONTINUATION LINES CAN BE FOUND. WPB | | | AMEND. TO FBC SEC. 107.3.5.1.3. | | | 29) A SEPARATE SHUTOFF VALE IS REQUIRED ON THE WATER | | | SUPPLY TO THE PET RINSE AREA. 2017 FBC-PLUMBING | | | SEC.606.2 (1) (3). | | | 30) SHT. P-7.3 - IDENTIFY THE LOCATION OF THE TWO FLOOR | | | DRAINS. WPB AMEND. TO FBC SEC. 107.2.1. | | | 31) SHT. P-8.1 - PLUMBING FIXTURE CONNECTION SCHEDULE - | | | NOTE #3 STATES " FIXTURES SHALL BE IN COMPLIANCE WITH | | | MIAMI-DADE COUNTY WATER USE EFFICIENCY STANDARDS. | | | CLARIFY. | | | 32) SHT. P-8.1 - PIPE MATERIAL SCHEDULE - NOTE #6 | | | REFERS TO THE 2007 FLORIDA PLUMING CODE. THE CODE THAT | | | IS IN EFFECT IS THE 2017 EDITION. REVISE THE NOTE. | | | 33) SEPARATE PEMITS WILL BE REQUIRED FOR ALL BACKFLOW | | | PREVENTION DEVICES. | | | 34) SUBMIT IRRIGATION PLANS IF A NEW IRRIGATION SYSTEM | | | IS GOING TO BE INSTALLED. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 35) SHT. P-1.0 - KEYED NOTE #3 REFERS TO THE CIVIL | | | DRAWINGS FOR THE CONTINUATION OF THE DRAIN LINE FROM | | | THE ROOF. THESE LINES ARE NOT SHOWN ON CIVIL DRAWING | | | C-2.1. CLARIFY. | | | 36) THE WATER VALVES FOR THE STACKED WASHER SHALL BE | | | PROVIDED WITH ACCESS IN ACCORDANCE WITH 2017 | | | FBC-PLUMBING SEC.606.3. | | | | | | FIRE PROTECTION: | | | 1) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE | | | SPRINKLER HEADS TO BE INSTALLED IN THE LIGHT HAZARD AND | | | ORDINARY HAZARD AREAS. NFPA 13R SEC. 8.1.7 (12). | | | 2) SHT. FP-1 REFERS TO FP-1 FOR THE POINT OF SERVICE. | | | THE POINT OF SERVICE IS NOT SHOWN ON FP-1. CLARIFY.SHOW | | | THE POINT OF SERVICE ON SHT. C-2.3 PER FL. STATUTE | | | 633.021. | | | 3) THERE IS NO SPRINKLER HEAD SHOWN IN THE ELEVATOR | | | PIT. COMPLY WITH NFPA 13 SEC. 8.15.5. | | | 4) SUBMIT A KEYNOTE LEGEND FOR THE KEYNOTES ON SHT. | | | FP-1, BUILDING A RISER DIAGRAM. | | | 5) SHT. FP-1 - BUILDING A RISER DIAGRAM SHOWS THE BASE | | | OF THE RISER TAG AS BEING ON THE THIRD FLOOR. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
P |
Date |
2020-12-09 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2020-12-09 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2020-12-09 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2020-11-23 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2020-11-23 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2020-11-23 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2020-11-23 11:18:44 | PRIVATE PROVIDER REVIEW FOR INSPECTIONS IS FAILED | | | | | | NOTICE TO BUILDING OFFICIAL NAMES GFA INTERNATIONAL AS | | | THE FIRM AND GEORGE DIXON AS THE PRIVATE PROVIDER. | | | LICENSE NUMBERS FOR BUILDING CODE ADMINISTRATOR AND | | | INSPECTOR WERE SUBMITTED FOR MR. DIXON. NO ADDITIONAL | | | INFORMATION WAS SUBMITTED FOR ANY DULY AUTHORIZED | | | REPRESENTATIVE. IS MR. DIXON GOING TO BE THE ONLY | | | PERSON MAKING THE INSPECTIONS N THIS PROJECT? | | | | | | THE CERTIFICATE OF INSURANCE DOES NOT STATE THAT | | | PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE | | | FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER, | | | AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS | | | REQUIRED. ( FOUND IN 553.791 (4) ) | | | | | | RICHARD GATHRIGHT | | | ASSISTANT BUILDING OFFICIAL | | | 561-805-6679 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2020-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-08-13 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-08-13 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-03 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-03 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2020-04-03 09:16:13 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2020-10-21 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-10-21 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-10-21 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-09-28 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-09-28 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-09-28 |
Time |
12:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-08-04 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-08-04 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2020-08-10 12:46:16 | PLUMBING SHEETS APPEAR TO BE OK. T.LARGE 8/10/2020. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-04-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-03 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-03 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2020-04-03 09:17:10 | SURVEY NEEDS TO BE ELECTRONICALLY SIGNED AND SEALED |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
N |
Date |
2020-04-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-10 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-10 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2020-04-10 10:56:05 | NOT REQUIRED PER KEN CONRAD | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2020-10-27 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-10-27 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-10-27 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-10-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-10-14 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2020-10-14 10:51:19 | 10/14/20- FAILED. ELEVATIONS DO NOT MATCH THE PLANS | | | APPROVED IN THE MINOR AMENDMENT. | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2020-08-19 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2020-08-19 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-08-19 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2020-08-19 13:20:13 | 8/19/20- FAILED- WAITING ON MINOR AMENDMENT APPROVAL | | | | | | ANGELLA VANN | | | [email protected] | | | 561-822-1441 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-04-28 |
|
|
Cont ID |
|
| Sent By |
avann |
Date |
2020-04-28 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2020-04-28 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2020-04-28 11:50:37 | 4/28/2020- FAILED | | | 1. THE SITE PLAN DOES NOT MATCH THE APPROVED SITE PLAN | | | ON FILE WITH THE PLANNING DIVISION. | | | 2. THERE SEEMS TO BE CHANGES IN THE ELEVATIONS | | | (WINDOWS) THAN WHAT IS ON FILE WITH THE PLANNING | | | DIVISION | | | | | | ANGELLA VANN, AICP | | | [email protected] | | | 561-822-1441 |
|
|
|