Plan Review Details - Permit 20030557
Plan Review Stops For Permit 20030557
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-06-03 Cont ID  
Sent By rmcphers Date 2020-06-03 Time 14:28 Rev Time 0.00
Received By rmcphers Date 2020-06-03 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 11:31 Sent To  
Notes
2020-04-29 11:31:50CARPORT ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 THE ENCLOSURE FRAMING CANNOT BE BUILT USING CODE
 PERSCRIPTIVE FRAMING AND CONNECTIONS - YOU WILL NEED TO
 PROVIDE THE WIND DESIGN CALCULATIONS FOR THE ENCLOSURE
 USING WIND SPEEDS 170MPH, EXPOSURE "B" "C" OR "D" AS
 APPLICABLE.
 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY
 WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609
 FBC R301.2.1.1 WIND LIMITATIONS AND WIND DESIGN
 REQUIRED.
 THE PRESCRIPTIVE PROVISIONS OF THIS CODE FOR WOOD
 CONSTRUCTION, COLD-FORMED STEEL LIGHT-FRAME
 CONSTRUCTION, AND MASONRY CONSTRUCTION SHALL NOT APPLY
 TO THE DESIGN OF BUILDINGS WHERE THE ULTIMATE DESIGN
 WIND SPEED, VULT, FROM FIGURE R301.2(4) EQUALS OR
 EXCEEDS 115 MILES PER HOUR (51 M/S).
 FBC 1609.1.1DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE
 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN
 SECTION 1609.6
 PLEASE SHOW THE COMPLETE CALCULATIONS FOR THE WIND
 DESIGN FOR THE ENCLOSURE.
 2) WIND DESIGN PRESSURE ENGINEERING PROVIDED FOR THE
 WINDOW OPENINGS NEEDS HAVE A DIGITAL SIGNATURE PROVIDED
 BY THE ARCHITECT OR ENGINEER TO BE USED IN ELECTRONIC
 PLAN REVIEW. PLEASE CONTACT THE ENGINEER OR ARCHITECT
 AND ASK FOR THE ENGINEERING TO BE DIGITALLY SIGNED. A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF E-SIGNATURE.
 WHEN PROVIDED IT CANNOT BE PRINTED OUT IT WILL LOSE THE
 DIGITAL SIGNATURE ? IT MUST TRAVEL IN THE COMPUTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-14 Cont ID  
Sent By rmcphers Date 2020-04-14 Time 15:39 Rev Time 0.00
Received By rmcphers Date 2020-04-14 Time 15:31 Sent To  
Notes
2020-04-14 15:39:39CARPORT ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY
 WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609
 FBC R301.2.1.1WIND LIMITATIONS AND WIND DESIGN
 REQUIRED.
 THE PRESCRIPTIVE PROVISIONS OF THIS CODE FOR WOOD
 CONSTRUCTION, COLD-FORMED STEEL LIGHT-FRAME
 CONSTRUCTION, AND MASONRY CONSTRUCTION SHALL NOT APPLY
 TO THE DESIGN OF BUILDINGS WHERE THE ULTIMATE DESIGN
 WIND SPEED, VULT, FROM FIGURE R301.2(4) EQUALS OR
 EXCEEDS 115 MILES PER HOUR (51 M/S).
 FBC 1609.1.1DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE
 7 OR PROVISIONS OF THE ALTERNATE ALL-HEIGHTS METHOD IN
 SECTION 1609.6
 PLEASE SHOW THE COMPLETE CALCULATIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 12:39 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 09:39 Sent To  
Notes
2020-03-23 12:04:43CARPORT ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE WIND LOAD CALCULATIONS TO COMPLY
 WITH THE WIND LOADS OR HAVE THE DRAWINGS SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER. FBC 1609
 2) PLEASE SHOW THE WIND LOAD DESIGN CRITERIA USED FOR
 DESIGN PER FBC 1609.3
 3) THE PRODUCT APPROVAL SUPPLIED FOR THE SINGLE HUNG
 WINDOWS IS APPROVED FOR SMALL MISSILE IMPACT - WINDOWS
 BELOW 30 FEET FROM GRADE NEED TO COMPLY WITH LARGE
 MISSILE IMPACT. PLEASE PROVIDE THE PRODUCT APPROVAL FOR
 THE REQUIRED SHUTTERS. FBC R301.2.1.2
 4) MEANS OF EGRESS TREAD DEPTH IS A MIN. OF 10 INCHES -
 FBC R311.7.5.2
 5) MEANS OF EGRESS MAX. RISER HEIGHT IS 7 3/4 INCHES -
 FBC R311.7.5.1
 6) PLEASE SHOW THE CEILING HEIGHT TO COMPLY WITH FBC
 R305.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-04 Cont ID  
Sent By jleahy Date 2020-05-04 Time 08:07 Rev Time 0.00
Received By jleahy Date 2020-05-04 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By jleahy Date 2020-04-15 Time 08:23 Rev Time 0.00
Received By jleahy Date 2020-04-15 Time 08:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-24 Cont ID  
Sent By jleahy Date 2020-03-24 Time 13:25 Rev Time 0.00
Received By jleahy Date 2020-03-24 Time 13:25 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:42 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:42 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-04-10 Cont ID  
Sent By fmittner Date 2020-04-10 Time 10:59 Rev Time 0.00
Received By fmittner Date 2020-04-10 Time 10:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By fmittner Date 2020-03-27 Time 16:44 Rev Time 0.00
Received By fmittner Date 2020-03-27 Time 16:44 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-03-17 Cont ID  
Sent By fmittner Date 2020-03-17 Time 15:38 Rev Time 0.00
Received By fmittner Date 2020-03-17 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-06-25 Cont ID  
Sent By cpuell Date 2020-06-25 Time 15:31 Rev Time 0.00
Received By cpuell Date 2020-05-28 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-04 Cont ID  
Sent By jleahy Date 2020-05-04 Time 08:07 Rev Time 0.00
Received By jleahy Date 2020-04-20 Time 09:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-15 Cont ID  
Sent By jleahy Date 2020-04-15 Time 08:23 Rev Time 0.00
Received By jleahy Date 2020-04-09 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 15:31 Rev Time 0.00
Received By shill Date 2020-03-11 Time 13:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-07-01 Cont ID  
Sent By lmarchan Date 2020-07-01 Time 09:46 Rev Time 0.00
Received By lmarchan Date 2020-06-25 Time 16:54 Sent To  
Notes
2020-06-30 12:06:12MU2020-23145 - $1043.60 - PAID
2020-06-25 16:54:576/25/20 SENT EMAIL TO IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 12:41 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 12:39 Sent To  
Notes
2020-03-23 12:41:37PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-04-22 Cont ID  
Sent By medwards Date 2020-04-22 Time 13:58 Rev Time 0.00
Received By medwards Date 2020-04-22 Time 12:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2020-04-10 Time   Rev Time 0.00
Received By medwards Date 2020-04-10 Time 14:13 Sent To  
Notes
2020-04-10 15:57:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20030557
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MANUAL J CALCULATIONS DO NOT LIST THE EXISTING
 UNITS OR ANY UNITS. THIS CALCULATION IS TO PROVE THAT
 THE EXISTING UNIT IS SIZED TO CONDITION THE NEW
 ADDITIONAL LOAD OF THE CARPORT CONVERSION INTO NEW
 CONDITION SPACE. FBC FS 107.2.1
 2) THE LISTED ACTUAL AIRFLOW IN THE CALCULATIONS IS
 1226 CFM. THIS NUMBER IS CONSISTENT WITH THE CFM?S OF
 THE SUPPLY GRILLES FOR THE EXISTING HOUSE. THEY DO NOT
 REFLECT THE ADDITIONAL 287 CFM?S IN THE NEW ADDITION.
 PLEASE SHOW THAT THE EXISTING UNIT IS SIZED TO
 CONDITION THE TOTAL AREA. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-26 Cont ID  
Sent By jbaker Date 2020-03-26 Time 09:57 Rev Time 0.00
Received By shill Date 2020-03-26 Time 07:50 Sent To  
Notes
2020-03-26 09:57:51FAILED
  
 MECHANICAL COMMENTS:
  
 1. PROVIDE ENERGY CALCS AND HEATING AND COOLING
 CALCULATIONS. 2017 FBC ENERGY CODE.
 2. PROVIDE EVIDENCE THAT EXISTING AIR HANDLING UNIT HAS
 ADEQUATE HEATING CAPACITY TO HEAT THE PORCH WITH 230
 CFM INDICATED. 2017 FRC R303.10 REQUIRED HEATING.
  
 PLEASE PROVIDE A COMMENT/RESPONSE LETTER WITH YOUR
 RESUBMITTAL FOR EXPEDITIOUS REVIEW.
  
 THANK YOU,
  
 JIM BAKER, P.E., PX, LEED AP
 [email protected]
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By medwards Date 2020-03-17 Time 13:47 Rev Time 0.00
Received By medwards Date 2020-03-16 Time 11:20 Sent To  
Notes
2020-03-17 13:49:021ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20030557
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 R303.10 REQUIRED HEATING.
 DESIGN TEMP. WEST PALM BEACH FLORIDA ? 45 DEGREES -
 WINTER
  
 FBC RESIDENTIAL, CHAPTER 3 BUILDING PLANNING, SECTION
 R303.10 REQUIRED HEATING. WHERE THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A ROOM TEMPERATURE OF
 NOT LESS THAN 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
 TABLE R301.2 (1), WINTER DESIGN TEMP. (E) ?THE OUTDOOR
 DESIGN DRY-BULB TEMPERATURE SHALL BE SELECTED FROM THE
 COLUMNS OF 971/2 PERCENT VALUES FOR WINTER??.
 2017 FBC EXISTING BUILDING, CHPT. 11, ADDITIONS,
 SECTION 1101.1 SCOPE. ?AN ADDITION TO A BUILDING OR
 STRUCTURE SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AS ADOPTED FOR NEW CONSTRUCTION??
 SECTION 1106 ENERGY CONSERVATION, 1106.1 MINIMUM
 REQUIREMENTS. ADDITIONS TO EXISTING BUILDINGS OR
 STRUCTURES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, ENERGY.
  
 2017 FBC ENERGY, CHAPTER 5 (RE), EXISTING BUILDINGS,
 SECTION R502 ADDITIONS, ?ADDITIONS TO AN EXISTING
 BUILDING, BUILDING SYSTEM OR PORTION THEREOF SHALL
 CONFORM TO THE PROVISIONS OF THIS CODE AS THOSE
 PROVISIONS RELATE TO NEW CONSTRUCTION??.
 SECTION R502.1.1.2 HEATING AND COOLING SYSTEMS. NEW
 HEATING, COOLING AND DUCT SYSTEMS THAT ARE PART OF THE
 ADDITION SHALL COMPLY WITH SECTIONS RE403.1, RE403.2,
 RE403.3, R403.5 AND R403.6.
 FBC PLUMBING, APPENDIX D, DEGREE DAY AND DESIGN
 TEMPERATURES, TABLE D101, DESIGN TEMPERATURE, WINTER,
 97 ?% = 45 DEGREES DESIGN TEMP.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2020-04-14 Cont ID  
Sent By ccole Date 2020-04-14 Time 15:24 Rev Time 0.00
Received By ccole Date 2020-04-14 Time 15:14 Sent To  
Notes
2020-04-14 15:26:17NO PLUMBING PLANS AND NO PLUMBING WORK INDICATED ON
 TOTHER DRAWINGS- SEPARATE PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-26 Cont ID  
Sent By jbaker Date 2020-03-26 Time 07:50 Rev Time 0.00
Received By shill Date 2020-03-26 Time 07:19 Sent To  
Notes
2020-03-26 07:50:14REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 12:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-06-03 Cont ID  
Sent By rmcphers Date 2020-06-03 Time 14:29 Rev Time 0.00
Received By rmcphers Date 2020-06-03 Time 14:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-29 Cont ID  
Sent By rmcphers Date 2020-04-29 Time 11:53 Rev Time 0.00
Received By rmcphers Date 2020-04-29 Time 11:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-14 Cont ID  
Sent By rmcphers Date 2020-04-14 Time 15:40 Rev Time 0.00
Received By rmcphers Date 2020-04-14 Time 15:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By rmcphers Date 2020-03-23 Time 12:42 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 12:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2020-06-25 Cont ID  
Sent By fmittner Date 2020-06-25 Time 15:01 Rev Time 0.00
Received By fmittner Date 2020-06-25 Time 15:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2020-04-24 Cont ID  
Sent By fmittner Date 2020-04-24 Time 16:42 Rev Time 0.00
Received By fmittner Date 2020-04-24 Time 16:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-10 Cont ID  
Sent By fmittner Date 2020-04-10 Time 10:59 Rev Time 0.00
Received By fmittner Date 2020-04-10 Time 10:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By fmittner Date 2020-03-27 Time 16:44 Rev Time 0.00
Received By fmittner Date 2020-03-27 Time 16:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-17 Cont ID  
Sent By fmittner Date 2020-03-17 Time 15:38 Rev Time 0.00
Received By fmittner Date 2020-03-17 Time 15:38 Sent To  
Notes
***NONE***