| Plan Review Stops For Permit 20030483 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-06 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2020-08-06 16:17:57 | PROVISO: SOIL DENSITY TEST REQUIRED PRIOR TO FOUNDATION | | | INSPECTION. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-16 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-16 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2020-04-16 16:18:23 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, | | | SLIDING DOORS ETC. ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD. | | | 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT OR | | | PROVIDE A SOIL STATEMENT ON THE DRAWINGS STATING THE | | | SOIL BEARING CAPACITY. FBC R401.4 | | | 3) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVAL FOR THE ROOFING TO BE USED. 107.2.1.1 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-24 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-24 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2020-03-24 15:23:49 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, | | | SLIDING DOORS ETC. ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER | | | OF RECORD. | | | 2) PLEASE PROVIDE A SIGNED AND SEALED SOIL REPORT OR | | | PROVIDE A SOIL STATEMENT ON THE DRAWINGS STATING THE | | | SOIL BEARING CAPACITY. FBC R401.4 | | | 3) PLEASE PROVIDE A MIAMI DADE OR FLORIDA STATE PRODUCT | | | APPROVAL FOR THE ROOFING TO BE USED. 107.2.1.1 | | | 4) DRAWING A-3 TYP. WALL SECTION - SHOWS "ASPHALT TILE" | | | ON THE ROOF. WHAT IS ASPHALT TILE? SLOPE WILL NOT ALLOW | | | ASPHALT SHINGLES. FBC R905.2.2 | | | 5) DRAWING A-3 TYP. WALL SECTION - SHOWS SCREEN VENTS | | | AT 8 FOOT SPACING, SCREEN VENT SHOULD BE CONTINUOUS TO | | | ALLOW VENTILATION BETWEEN EACH JOIST. FBC R806.1 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-06 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-04-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-22 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-22 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-03-27 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-03-26 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2020-03-27 10:51:55 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1) SHEET A1 OF THE PLANS INDICATES THAT THE EXISTING | | | SERVICE IS TO BE MOVED. THE ELECTRICAL PLAN ON A4 SHOWS | | | THE SERVICE ON THE NEW BEDROOM ADDITION AND HAS IT | | | LABELED AS EXISTING. PLEASE CORRECT. PROVIDE RISER | | | DIAGRAM, SHOWING ALL DETAILS OF SERVICE EQUIPMENT, | | | UNDERGROUND OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES | | | FOR SERVICE AND FEED TO ANY SUB-PANEL(S). SHOW GEC SIZE | | | AND SYSTEM, SHOW INTERSYSTEM BONDING TERMINATION POINT. | | | NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1, | | | E3608.1, E3609.3; WPB FBC 107.2.1 | | | | | | 2) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | | | | 3) IDENTIFY THE REQUIRED BATHROOM RECEPTACLE CIRCUIT IN | | | THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. | | | PROVIDE CORRECTION. NEC 210.11(C)(3), FBC RE E3703.4 | | | | | | 4) IDENTIFY THE REQUIRED LAUNDRY RECEPTACLE CIRCUIT IN | | | THE PANEL SCHEDULE. A MINIMUM OF ONE 20 AMPERE BRANCH | | | CIRCUIT SHALL BE PROVIDED FOR RECEPTACLES LOCATED IN | | | THE LAUNDRY AREA AND SHALL SERVE ONLY RECEPTACLE | | | OUTLETS LOCATED IN THE LAUNDRY AREA. NEC 210.11(C) (2), | | | FBC RE E3703.3 | | | | | | 5) THE PANEL A LOAD CALCULATIONS ARE NOT ACCURATE (USE | | | RESIDENTIAL LOAD CALCUALTIONS). THE LOAD CALCULATIONS | | | PROVIDED TOTAL 173.3 AMPS AND THE MAIN BUS IS SPECIFIED | | | AS 150 AMPS. PROVIDE ACCURATE LOAD CALCULATION FOR | | | SERVICE, INCLUDE EXISTING AND NEW LOADS TO CONFIRM | | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, | | | 408.30; FBC RE E3602.2 | | | | | | 6) THE ONE BATHROOM RECEPTACLE SHOWN ON THE LEFT SIDE | | | OF THE TWO VANITY BASINS IS NOT ACCEPTABLE. A GFCI | | | PROTECTED RECEPTACLE OUTLET ON A 20 AMP CIRCUIT IS | | | REQUIRED WITHIN 3 FEET OF EACH BASIN. THE RECEPTACLE | | | OUTLET SHALL BE LOCATED ON A WALL OR PARTITION THAT IS | | | ADJACENT TO THE BASIN OR BASIN COUNTERTOP, LOCATED ON | | | THE COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE | | | BASIN CABINET. PROVIDE CORRECTION. NEC 210.11(C)(3), | | | 210.52(D); FBC RE E3901.6 | | | | | | 7) THE ROOF FRAMING PLAN LOCATED ON SHEET A3 IS | | | INCORRECTLY LABELED AS THE ELECTRICAL PLAN. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | ROBERT MCDOUGAL | | | COMBINATION PLANS EXAMINER | | | 561-805-6714 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-08-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-07 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-07-29 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2020-07-22 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2020-07-21 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2020-07-22 13:17:08 | I STOP COMPLETED TO STOP REVIEW PROCESS. | | | THE CUSTOMER IS PROVIDING NEW DRAWINGS AND WILL BRING | | | IN ORIGINALS FOR SIGNATURE. | | | NEW I STOP WILL BE CREATED ONCE THE DRAWINGS ARE IN | | | PROJECTDOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-04-30 |
Time |
08:44 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-04-13 |
Time |
13:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-03-27 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-03-10 |
Time |
13:13 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2020-08-10 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-10 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-06 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2020-08-10 13:56:41 | MU RECEIPT 2020-030109 - $393.79 - PAID | | 2020-08-06 16:17:27 | 8/6/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-06 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-06 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2020-08-06 11:37:29 | REVISED IMPACT FEE REVIEW FOR DIGITAL: | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-24 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-24 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2020-03-24 15:36:09 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-06 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2020-08-06 16:16:39 | SEPERATE MECHANICAL PERMIT REQUIRED. NO MECHANICAL | | | REVIEW PERFORMED UNDER THIS PERMIT. CT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-04-17 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-04-17 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-04-17 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2020-04-17 09:49:41 | 1ST CYCLE MECHANICAL COMMENTS WERE NOT ADDRESSED IN | | | THIS REVISED SUBMITTED PACKAGE. PLEASE REVIEW 1ST CYCLE | | | COMMENTS AND SUBMIT THE NEXT CYCLE. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-20 |
Time |
11:10 |
Rev Time |
|
| Received By |
medwards |
Date |
2020-03-20 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-20 11:11:15 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT- 20030483 | | | | | | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1. PROVIDE CODE COMPLIANT MECHANICAL PLAN. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. SEE FBC EC | | | R403.7.1 EQUIPMENT SIZING. FBC RES M1401.3 EQUIPMENT | | | AND APPLIANCE SIZING. | | | | | | EQUIPMENT SCHEDULE ON PLAN SHALL MATCH EQUIPMENT ON | | | MANUAL J. | | | | | | 2. PROVIDE ENERGY SUBMITTAL. | | | PROVIDE ENERGY GUAGE AND MANUAL J. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-06 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
12:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2020-07-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-07-22 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-07-22 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2020-07-22 12:34:35 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT #20030483 | | | 7/22/2020 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-2: THE WASHING MACHINE DRAIN CANNOT CONNECT | | | INTO THE SHOWER FIXTURE DRAIN, AND MUST MAKE CONNECTION | | | INTO THE MAIN 3" DRAIN DOWNSTREAM OF ALL OTHER BATH | | | FIXTURE DRAIN CONNECTIONS- PLEASE SEE SECTION P3108.1 | | | FBC RES HORIZONTAL WET VENT. THE WASHER DRAIN CANNOT BE | | | PART OF THE HORIZONTAL WET VENT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-04-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-04-30 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-04-30 |
Time |
07:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-03-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-26 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-03-26 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2020-03-26 15:46:29 | | | | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT #20030483 | | | 3/26/20 | | | | | | CODES IN EFFECT: | | | | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-2: THE WASHING MACHINE DRAIN CANNOT CONNECT | | | INTO THE SHOWER FIXTURE DRAIN, AND MUST MAKE CONNECTION | | | INTO THE 3" DRAIN DOWNSTREAM OF THE SHOWER AND ALL | | | OTHER BATH FIXTURES- PLEASE SEE SECTION P3108.1 FBC RES | | | HORIZONTAL WET VENT. THE WASHER DRAIN CANNOT BE PART OF | | | THE HORIZONTAL WET VENT AND SHALL BE INDIVIDUALLY | | | VENTED. | | | | | | 2) A-2; SHOW DOUBLE LAVATORY DRAINS AND LAV DRAIN SIZES | | | IN THE PLUMBING RISER DRAWING- SECTION P3005.4 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2020-08-07 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-06 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2020-08-06 16:19:03 | ROOFING SUB-PERMIT REQUIRED. | | | DEFERRAL: ROOFING SYSTEM PRODUCT APPROVALS SHALL BE | | | SUBMITTED FOR REVIEW PRIOR TO INSTALLATION. CT | | | DEFERRAL NOTE ON PLAN PAGE A3. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-04-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-04-16 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-04-16 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2020-04-16 16:20:26 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-03-24 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2020-03-24 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2020-03-24 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2020-03-24 15:36:43 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-08-06 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-08-06 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2020-08-06 11:49:25 | PAPER ORIGINALS RECEIVED | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-04-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-04-22 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-04-22 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2020-04-22 15:54:23 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ORIGINAL SIGNED AND SEALED SHEET A1 WAS PROVIDED | | | WITH PAPER SUBMITTAL. | | | | | | 2. PAGES A2, A3, A4 WERE RESUBMITTED VIA EMAIL AND ARE | | | NOT DIGITALLY SIGNED. EITHER EMAIL DIGITALLY SIGNED | | | PAGES TO ME, OR ONE PAPER ORIGINAL WILL BE REQUIRED TO | | | BE SUBMITTED AFTER ALL REVIEWS ARE COMPLETE. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-04-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-04-15 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-04-15 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2020-04-15 13:21:36 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ORIGINAL SIGNED AND SEALED SHEET A1 WAS PROVIDED | | | WITH PAPER SUBMITTAL. | | | | | | 2. PAGES A2, A3, A4 WERE RESUBMITTED VIA EMAIL AND ARE | | | NOT DIGITALLY SIGNED. EITHER EMAIL DIGITALLY SIGNED | | | PAGES TO ME, OR ONE PAPER ORIGINAL WILL BE REQUIRED TO | | | BE SUBMITTED AFTER ALL REVIEWS ARE COMPLETE. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-08-06 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-06 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2020-08-06 15:58:18 | ZONING APPROVED BY RF. STAMP ON SITE PLAN. CT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-04-23 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-04-23 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-04-23 |
Time |
17:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-03-16 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-03-16 |
Time |
15:59 |
Sent To |
I |
|
| Notes |
|
|