Plan Review Details - Permit 20030480
Plan Review Stops For Permit 20030480
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-09-29 Cont ID  
Sent By pvalenti Date 2020-09-29 Time 07:21 Rev Time 0.00
Received By pvalenti Date 2020-09-29 Time 07:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-08-08 Cont ID  
Sent By pvalenti Date 2020-08-08 Time 08:18 Rev Time 0.00
Received By pvalenti Date 2020-08-08 Time 08:18 Sent To  
Notes
2020-08-08 08:19:40PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.1 PLEASE PROVIDE THE WINDLOAD AND FOOTING
 DETAILS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By jleahy Date 2020-07-20 Time 14:20 Rev Time 0.00
Received By jleahy Date 2020-07-20 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By jleahy Date 2020-03-16 Time 08:17 Rev Time 0.00
Received By jleahy Date 2020-03-16 Time 08:00 Sent To  
Notes
2020-03-12 15:29:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER SHOWS 3 FUSES OTHER NOTES ON PLAN SHOWS
 BREAKERS, WHICH IS IT?
  
 2) FAULT CURRENT CALCULATION REQUIRED. 110.24
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-09-29 Cont ID  
Sent By pvalenti Date 2020-09-29 Time 07:25 Rev Time 0.00
Received By pvalenti Date 2020-09-17 Time 07:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-16 Cont ID  
Sent By lmarchan Date 2020-09-16 Time 13:25 Rev Time 0.00
Received By lmarchan Date 2020-08-26 Time 15:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-28 Cont ID  
Sent By shill Date 2020-07-28 Time 07:53 Rev Time 0.00
Received By shill Date 2020-06-30 Time 11:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-16 Cont ID  
Sent By jleahy Date 2020-03-16 Time 08:19 Rev Time 0.00
Received By jleahy Date 2020-03-10 Time 13:11 Sent To  
Notes
2020-03-11 13:11:17ROUTED TO ELECTRICAL INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-29 Cont ID  
Sent By pvalenti Date 2020-09-29 Time 07:21 Rev Time 0.00
Received By pvalenti Date 2020-09-29 Time 06:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-20 Cont ID  
Sent By jleahy Date 2020-07-20 Time 14:20 Rev Time 0.00
Received By jleahy Date 2020-07-20 Time 14:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By eschneid Date 2020-09-22 Time 10:18 Rev Time 0.25
Received By eschneid Date 2020-09-22 Time 10:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-24 Cont ID  
Sent By eschneid Date 2020-07-24 Time 15:53 Rev Time 0.25
Received By eschneid Date 2020-07-24 Time 15:53 Sent To  
Notes
2020-07-24 15:54:37FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY. THE SURVEY
 USED FOR THE ROW PERMIT APPROVAL MAY BE USED.
  
 2) PROVIDE VERIFICATION THAT THE PROPOSED WIRELESS
 FACILITY (POLE) MEETS THE CITY OF WEST PALM BEACH
 CONCEALMENT (STEALTH), STYLE OR HEIGHT REQUIREMENTS
 LISTED IN SECTIONS 78-411(E), 78-411(F) AND 78-411(G)
 OF THE CITY CODE. PROVIDE A POLE THAT MEETS THE CITY
 CODE REQUIREMENTS. NOTE: AT&T HAS SHOWN POLES ON OTHER
 APPLICATIONS THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-12 Cont ID  
Sent By eschneid Date 2020-03-12 Time 16:11 Rev Time 0.25
Received By eschneid Date 2020-03-12 Time 16:11 Sent To E
Notes
2020-03-12 16:19:37FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE PALM BEACH COUNTY APPROVAL IF
 THE SURVEY SHOWS THE PROPOSED WITELESS COMMUNICATION
 FACILITY IN THE RIGHT-OF-WAY.
  
 3) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH),
 STYLE OR HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: AT&T HAS SHOWN POLES ON OTHER APPLICATIONS THAT
 MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]