Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-04-29 Cont ID  
Sent By tklarge Date 2020-04-29 Time 10:00 Rev Time 0.00
Received By tklarge Date 2020-04-29 Time 10:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-03-25 Cont ID  
Sent By abelisle Date 2020-03-25 Time 15:03 Rev Time 0.00
Received By abelisle Date 2020-03-25 Time 14:24 Sent To I
Notes
2020-03-25 15:04:103/25/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
  
 1) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL
 CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2) SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471.
  
 3) THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING
 PERMIT VALUATIONS.
  
 4) A PORTION OF PLUMBING SHEET 1 IS ILLEGIBLE. SUBMIT
 TWO COPIES OF CLEAR AND LEGIBLE PLANS FOR REVIEW. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS
  
 5) THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 7) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 8) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9) TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 10) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
  
 11) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017
 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 12) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 13) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FUEL GAS SEC. 402.2 OR 2017
 FBC FUEL GAS RES. SEC. G2413.2.
  
 14) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS.
 502 THRU 505 OR 2017 FBC FUEL GAS RES. SECS. G2426 THRU
 G2429.1
  
 15) SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR
 2017 FBC FUEL GAS RES. SEC. G2408.1.
  
 16) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 17) SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS SEC. 402.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2413.3
  
 18) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 19) SHUTOFF VALVES SHALL BE OF AN APPROVED TYPE; SHALL
 BE CONSTRUCTED OF MATERIALS COMPATIBLE WITH THE PIPING;
 AND SHALL COMPLY WITH THE STANDARD THAT IS APPLICABLE
 FOR THE PRESSURE AND APPLICATION, IN ACCORDANCE WITH
 TABLE 409.1.1.
  
 20) EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF
 VALVE IN ACCORDANCE WITH SECTION 409.5.1, 409.5.2 OR
 409.5.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By abelisle Date 2020-03-10 Time 18:57 Rev Time 0.00
Received By abelisle Date 2020-03-10 Time 18:52 Sent To  
Notes
2020-03-10 19:11:063/10/2020 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1-SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS DRYER. THE GAS DRYER SHALL BE LISTED AND LABELED
 PER THE 2017 FBC FUEL GAS SEC.301.3 OR 2017 FBC FUEL
 GAS RES. SEC. G2404.3. THE MANUFACTURER'S
 SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING
 EXHAUSTED BY THE DRYER.
  
 2-GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.5 (9) COMMERCIAL GAS
  
 3-SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR? 2017 FGC
 SEC.304.9.3 OR 2017 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 4-THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING
 PERMIT VALUATIONS.
  
 5-I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND THERE
 IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF ANY
 GAS ON THIS ADDRESS. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 6-SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-29 Cont ID  
Sent By tklarge Date 2020-04-29 Time 10:00 Rev Time 0.00
Received By tklarge Date 2020-04-29 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-30 Cont ID  
Sent By lmarchan Date 2020-03-30 Time 10:09 Rev Time 0.00
Received By lmarchan Date 2020-03-23 Time 15:53 Sent To  
Notes
2020-03-23 15:53:17RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-06 Time 13:25 Sent To  
Notes
2020-03-09 13:25:20PLUMB <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-03-24 Cont ID  
Sent By ccole Date 2020-03-24 Time 15:55 Rev Time 0.00
Received By ccole Date 2020-03-24 Time 15:55 Sent To G
Notes
2020-03-24 15:57:04MECHANICAL REVIEW IS UNDER PERMIT #20030359.
 CCOLE-3/24/20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By ccole Date 2020-03-13 Time 08:15 Rev Time 0.00
Received By ccole Date 2020-03-13 Time 08:15 Sent To I
Notes
2020-03-13 08:17:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20030358
 3/12/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE NEW DRYERS SHALL BE INSTALLED AND EXHAUSTED IN
 ACCORDANCE WITH THE MANUFACTURER'S GUIDELINES- SECTION
 504.1 FBC M. PLEASE SUBMIT TWO COMPLETE COPIES OF THE
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS.
  
 2) IN ORDER TO VERIFY THAT THE EXISTING DRYER EXHAUST
 DUCTS ARE 8" DIAMETER ACCORDING TO THE GUIDELINES, AND
 THAT ADEQUATE COMBUSTION AND MAKEUP AIR IS BEING
 PROVIDED TO THE DRYERS, PLEASE SUBMIT DRAWINGS AND
 DETAILS SHOWING THE FOLLOWING ITEMS:
  
 A) THE TYPE AND SIZE OF EXISTING EXHAUST DUCTS
 INCLUDING THEIR TOTAL LENGTH RUNS AND TERMINATION
 LOCATIONS- SECTION 504.8- 504.8.4.2 FBC M.
  
 B) COMBUSTION AIR CALCULATIONS AND HOW COMBUSTION AIR
 IS BEING PROVIDED- WHCH METHOD IS BEING USED- SEE
 SECTION 304 FBC FG. PLEASE NOTE THE SUBMITTED SPECS
 REQUIRE 1.5 SQ. FT. OF MAKE UP AIR OPENING FOR EACH
 STACK DRYER.
  
 C) REQUIRED CLEARANCES AT THE BACK AND SIDES OF THE
 DRYERS PER THE SPECS.
  
 3) COMPLY WITH THE GAS REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  