Plan Review Details - Permit 20030353
Plan Review Stops For Permit 20030353
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 08:02 Rev Time 0.00
Received By rmcphers Date 2020-03-17 Time 16:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-01 Cont ID  
Sent By jleahy Date 2020-04-01 Time 10:18 Rev Time 0.00
Received By jleahy Date 2020-03-31 Time 08:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-21 Cont ID  
Sent By fgiaquin Date 2020-03-21 Time 16:23 Rev Time 0.00
Received By fgiaquin Date 2020-03-21 Time 13:53 Sent To  
Notes
2020-03-21 16:23:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. DISCONNECT WITH OVERCURRENT PROTECTION NEEDED
 BETWEEN COMBINER BOX AND METER/MAIN COMBO. ELECTRIC
 POWER PRODUCTION SYSTEM MUST HAVE OCP WITHIN 10FT WHEN
 INTERCONNECTING TO PRIMARY POWER SUPPLY ON LOAD SIDE OF
 SERVICE DISCONNECTING MEANS. NEC 705.31
  
 2. BACK FED PV BREAKER IN METER/MAIN COMBO MUST BE AT
 OPPOSITE END OF BUS BAR. NEC 705.12(D)(2)(3)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-07 Cont ID  
Sent By lmarchan Date 2020-04-07 Time 10:39 Rev Time 0.00
Received By lmarchan Date 2020-03-26 Time 12:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-21 Cont ID  
Sent By fgiaquin Date 2020-03-21 Time 16:23 Rev Time 0.00
Received By fgiaquin Date 2020-03-10 Time 10:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-01 Cont ID  
Sent By jleahy Date 2020-04-01 Time 10:20 Rev Time 0.00
Received By jleahy Date 2020-04-01 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By rmcphers Date 2020-03-18 Time 08:02 Rev Time 0.00
Received By rmcphers Date 2020-03-18 Time 08:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By rfalcone Date 2020-04-07 Time 10:37 Rev Time 0.00
Received By rfalcone Date 2020-04-07 Time 10:37 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By hdanfort Date 2020-03-13 Time 13:56 Rev Time 0.00
Received By hmtribou Date 2020-03-13 Time 13:56 Sent To  
Notes
2020-03-13 13:58:30PROVIDE VERIFICATION THAT ALL SOLAR PANELS WILL NOT
 EXTEND PAST THE ROOF?S SURFACE BY PROVIDING DIMENSIONS
 OF THE PANELS AND THE ROOF.