| Plan Review Stops For Permit 20030292 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-05-22 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-05-22 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2020-05-22 11:28:40 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, THE ADDRESS ON THE EPL DISPLAY CARD AND | | | ENERGY EFFICIENT CODE FOR BUILDING CONSTRUCTION DOES | | | NOT MATCH THE ADDRESS ON RECORD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-03-17 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-03-17 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2020-03-17 09:25:17 | BUILDING REVIEW COMMENTS FOR SUBMITTAL ADDRESSING | | | BUILDING REVIEW PROVISO. | | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | | | NOTE: | | | COMPLETE SET OF DRAWINGS WERE SUBMITTED ALONG WITH THIS | | | REVISION. PLANS ARE APPROVED, SINCE THERE SEEM TO BE NO | | | CHANGES ON THE PLANS. THE INFORMATION REQUESTED ON THE | | | PROVISO WAS SUBMITTED AND REVIEWED. THE ONLY THING THAT | | | WAS NOT ADDRESSED WAS THE REVISION OF THE ENERGY | | | CALCULATIONS . SEE COMMENTS BELOW. | | | | | | | | | PROVISO ORIGINAL COMMENTS: | | | 1-REVISE ENERGY CALCULATIONS: A) REVISE ADDRESS TO | | | MATCH PLANS. | | | B) REVISE # OF BEDROOMS AND CONDITIONED FLOOR AREA TO | | | MATCH PLANS. | | | C) PROVIDE THE BUILDER'S NAME. | | | D) REVISE DOORS INFORMATION. THERE ARE NO DOORS ON THE | | | WEST SIDE AND THERE ARE NO WOOD DOORS. | | | E) REVISE WINDOWS ORIENTATION AND AREA TO MATCH PLANS. | | | | | | RESPONSE: | | | ENERGY CALCULATIONS WERE NOT REVISED. SAME ENERGY | | | CALCULATIONS WERE RE-SUBMITTED. NEED TO ADDRESS ALL THE | | | COMMENTS. | | | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. | | | | | | 2- OK. | | | | | | 3- OK. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-18 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-18 |
Time |
12:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-05-22 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-05-21 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-03-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-03-21 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-03-05 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-05-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-05-22 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-05-22 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2020-05-22 10:56:31 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | 2ND MECHANICAL REVIEW DENIED: | | | | | | 1. FBC B 107.2.1, THE REVISED ADDRESS INDICATED ON THE | | | EPL CARD AND ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION DOES NOT MATCH THE CORRECT ADDRESS. | | | 2. FBC B 107,1, MISSING PAGE AC-1 FROM ONE OF THE PLAN | | | SETS. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-03-13 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-13 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-12 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2020-03-13 10:55:40 | CODES IN EFFECT: | | | | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED | | | | | | ORIGINAL PERMIT # 19091103 SHOWED A 4 BEDROOM HOUSE. | | | THE ENERGY CALCULATIONS AND THE MECHANICAL SHEET | | | MATCHED. THIS REVISION #20030292 NOW SHOWS A 5 BEDROOM | | | HOUSE. THE ROOMS NOW DO NOT MATCH THE ENERGY | | | CALCULATIONS. THE DUCT SIZES DO NOT MATCH, THERE ISN?T | | | A WALKIN CLOSET BUT THE ENERGY CALCULATIONS CALLS OUT A | | | DUCT IN THE MASTER CLOSET. PLEASE PROVIDE AN ENERGY | | | CALCULATION THAT MATCHES THIS 5 BEDROOM HOUSE. | | | | | | CODE SECTION: FBC EC 107.2 CONSTRUCTION DOCUMENTS. | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2020-03-16 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2020-03-16 |
Time |
17:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2020-03-19 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2020-03-19 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2020-03-19 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-19 14:13:34 | *********************ZONING | | | PROVISO******************(FROM MASTER PERMIT # | | | 19091103) | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANY, THE | | | FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | LANDSCAPE INSPECTION. | | | | | | ALANA WOOTEN | | | ASSOCIATE PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] |
|
|