Plan Review Details - Permit 20030291
Plan Review Stops For Permit 20030291
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-12 Cont ID  
Sent By jgomez Date 2020-03-12 Time 17:19 Rev Time 0.00
Received By jgomez Date 2020-03-12 Time 15:15 Sent To  
Notes
2020-03-12 17:31:19BUILDING REVIEW COMMENTS FOR SUBMITTAL ADDRESSING
 BUILDING REVIEW PROVISO.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 COMPLETE SET OF DRAWINGS WERE SUBMITTED ALONG WITH THIS
 REVISION. PLANS ARE APPROVED, SINCE THERE SEEM TO BE NO
 CHANGES ON THE PLANS. THE INFORMATION REQUESTED ON THE
 PROVISO WAS SUBMITTED AND REVIEWED. THE ONLY THING THAT
 WAS NOT ADDRESSED WAS THE REVISION OF THE ENERGY
 CALCULATIONS . SEE COMMENTS BELOW.
  
  
 PROVISO ORIGINAL COMMENTS:
 1-REVISE ENERGY CALCULATIONS: A) REVISE ADDRESS TO
 MATCH PLANS.
 B) REVISE # OF BEDROOMS AND CONDITIONED FLOOR AREA TO
 MATCH PLANS.
 C) PROVIDE THE BUILDER'S NAME.
 D) REVISE DOORS INFORMATION. THERE ARE NO DOORS ON THE
 WEST SIDE AND THERE ARE NO WOOD DOORS.
 E) REVISE WINDOWS ORIENTATION AND AREA TO MATCH PLANS.
  
 RESPONSE:
 ENERGY CALCULATIONS WERE NOT REVISED. SAME ENERGY
 CALCULATIONS WERE RE-SUBMITTED. NEED TO ADDRESS ALL THE
 COMMENTS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 2- OK.
  
 3- OK.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-18 Cont ID  
Sent By cthroop Date 2020-03-18 Time 10:29 Rev Time 0.00
Received By jpearson Date 2020-03-18 Time 10:29 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-18 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-05 Time 14:07 Sent To  
Notes
2020-03-06 14:07:31R33

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By cthroop Date 2020-03-17 Time 14:59 Rev Time 0.00
Received By medwards Date 2020-03-17 Time 14:22 Sent To  
Notes
2020-03-17 15:00:141ST REVIEW FBC-2017 MECHANICAL
 PERMIT- 20030291
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) NEED TO REVISE THE ENERGY CALCULATIONS TO MATCH THE
 5 BEDROOM PLANS. FBC EC R101.5.1.1.2; FBC RES RE403.7
  
 2) NEED TO PROVIDE A MECHANICAL SHEET OF THE CORRECT 5
 BEDROOM PLAN. FBC FAC 107.1
  
 MECHANICAL PLAN MUST MATCH THE A SHEETS: A SHEETS AND
 PERMIT IS FOR A 5 BEDROOM HOUSE, THE MECHANICAL SHEET
 IS A 4 BEDROOM HOUSE AND SO ARE THE ENERGY
 CALCULATIONS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-12 Cont ID  
Sent By jgomez Date 2020-03-12 Time 17:04 Rev Time 0.00
Received By jgomez Date 2020-03-12 Time 17:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-16 Cont ID  
Sent By rfalcone Date 2020-03-16 Time 15:53 Rev Time 0.00
Received By rfalcone Date 2020-03-16 Time 15:53 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved