| 2020-03-27 17:31:21 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20030166 |
| | 3/27/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET H-1: THE NOTES INDICATE THE APPLICABLE |
| | COMPLIANCE CODE SECTIONS FROM THE FLORIDA MECHANCIAL |
| | CODE- 2014 FIFTH EDITION FOR NON-LISTED COMMERCIAL |
| | KITCHEN HOOD, HOWEVER THERE IS NO EVIDENCE ON THE PLAN |
| | THAT THE HOOD TO BE INSTALLED MEETS THOSE COMPLIANCES |
| | ORE THE 2017 APPLICABLE CODE SECTIONS. PLEASE UP DATE |
| | THE CODE SECTIONSIN THE NOTES AND PROVIDE A SCHEMATIC |
| | DRAWING OF THE HOOD AND A EQUIPMENT SCHEDULE THAT |
| | INDICATES COMPLIANCE WITH SECTIONS 507.1.5, 507.2.3, |
| | 507.2.5, 507.2.8, & 507.4, & 507.5 FBC M. |
| | |
| | 2) H-1: INDICATE COMPLIANCE WITH SECTION 508.1.1 FBC M |
| | WHICH REQUIRES THE TEMPERATURE DIFFERENTIAL BETWEEN THE |
| | MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE TO NOT |
| | EXCEED 10 DEGREES F. |
| | |
| | 3) H-1: SHOW THE REQUIRED 18" CLEARANCE TO COMBUSTIBLES |
| | FOR THE GREASE EXHAUST DUCT INCLUDING THE PENETRATION |
| | THROUGH THE ROOF- SECTION 506.3.6 FBC M. |
| | |
| | 4) H-1: SHOW THE REQUIRED 18" CLEARANCE TO COMBUSTIBLES |
| | FOR THE GREASE HOOD IN COMPLIANCE WITH SECTION 507.2.6 |
| | FBC M. IF COMPLYING WITH THE EXCEPTION, PLEASE PROVIDE |
| | HOOD BACKING DIMENSIONS ON THE DRAWING TO SHOW PROPER |
| | EXTENSION COVERAGE. |
| | |
| | 5) THE $12,900.00 VALUE ON THE APPLICATION APPEARS LOW |
| | FOR THE ENTIRE SCOPE OF WORK. PLEASE PROVIDE COPIES AOF |
| | SIGNED CONTRACTS AND/OR ESTIMATES, INVOICES ETC. TO |
| | VERIFY THE TOTAL COST. PLEASE NOTE THAT PERMIT VALUE IS |
| | BASED ON LABOR, MATERIALS AND EQUIPMENT- SECTION 109.3 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |