Plan Review Details - Permit 20030157
Plan Review Stops For Permit 20030157
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-07-28 Cont ID  
Sent By rmcphers Date 2020-07-28 Time 10:26 Rev Time 0.00
Received By rmcphers Date 2020-07-28 Time 09:53 Sent To  
Notes
2020-07-28 10:09:23ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING A300 SHOWS CEILING HEIGHT AT 6 FOOT 8
 INCHES. PLEASE SHOW CEILING HEIGHT TO COMPLY WITH FBC
 R305.1 (SPACE IS HABITABLE MINIMUM CEILING HEIGHT 7
 FEET)
 2) PLEASE SHOW CEILING INSULATION TYPE AND "R" VALUE.
 FBC ENERGY R401.1
 3) DRAWING A300 SHOWS SOFFIT SCREEN VENT AT 8-FOOT OC.
 SHOULD BE A CONTINUOUS SCREEN VENT FOR ENCLOSED RAFTER
 SPACES FBC R806
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOOR AND WINDOWS.
 5) PLEASE SHOW THE BUILDING SET BACK FROM THE PROPERTY
 LINE AT THE NORTH EAST CORNER OF THE BUILDING. FBC
 TABLE R302.1 (NEEDED TO DETERMINE THE FIRE RATING - IF
 ANY)
 6) SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By rmcphers Date 2020-03-17 Time 10:31 Rev Time 0.00
Received By rmcphers Date 2020-03-17 Time 09:18 Sent To  
Notes
2020-03-17 10:31:47ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE WIND LOAD CALCULATIONS BASED ON WIND
 SPEED OF 170MPH OR SIGNED AND SEALED DETAILS FROM AN
 ARCHITECT OR ENGINEER TO COMPLY WITH THE WIND LOAD
 REQUIREMENTS FBC R301.2.1.1
 2) PLEASE SHOW WALL FRAMING AND CLADDING DETAILS TO
 COMPLY WITH THE WIND LOADS PER FBC R301.2.1.1
 3) PLEASE SHOW ALL HURRICANE STRAPPING AND STRAP
 NAILING REQUIREMENTS FBC R602.3.5
 4) PLEASE SHOW CEILING HEIGHT TO COMPLY WITH FBC R305.1
 5) PLEASE SHOW WALL AND CEILING INSULATION TYPE AND "R"
 VALUE. FBC ENERGY R401.1
 6) PLEASE PROVIDE A CLEAR FLOOR PLAN SHOWING THE ROOM
 USE, ROOM DIMENSIONS, SIZE AND LOCATION OF WINDOWS,
 SIZE AND LOCATION OF DOORS ETC.
 7) FOR BEDROOMS PLEASE SHOW THE EMERGENCY EGRESS TO
 COMPLY WITH FBC R310
 8) PLEASE SHOW ALL EXISTING ELEMENTS AND ATTACHMENTS OF
 NEW WORK TO EXISTING ELEMENTS ( ROOF, FOUNDATION,
 COLUMNS, BEAMS, ETC.). FBC WPB AMENDMENTS 107
 9) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOOR AND WINDOWS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 11:34 Rev Time 0.00
Received By cthroop Date 2020-07-30 Time 10:58 Sent To  
Notes
2020-07-30 11:37:29PLAN REVIEW - ELECTRICAL
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 2ND REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 COMMENTS FROM 1ST ELECTRICAL REVIEW HAVE NOT BEEN
 ADDRESSED. I HAVE ATTACHED THEM HERE FOR YOUR REVIEW.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) PLANS ARE ILLEGIBLE. THE SUBMITTED FLOOR PLAN IS
 UNACCEPTABLE. PLEASE REVIEW THE FOLLOWING SECTIONS FROM
 THE WEST PALM BEACH AMENDMENTS TO THE FBC: FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) THE $1500.00 VALUE IS TOO LOW. THE VALUE USED FOR
 PERMITTING IS THE COMPLETE REPLACEMENT COST FOR ALL
 MATERIALS AND LABOR. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 4) PROVIDE ELECTRICAL PLAN FOR REVIEW THAT IS DESIGNED
 BY AND SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR DESIGNED BY AND SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 5) PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 6) PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 7) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 8) PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 9) SHOW THE LOCATIONS OF THE EXISTING SERVICE RISER AND
 PANEL ON THE FLOOR PLANS. WPB FBC 107.2.1
  
 10) PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 11) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 NOTE ON PLANS. NEC 210.12; FBC RE E3902.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 ROBERT MCDOUGAL
 COMBINATION PLANS EXAMINER
 561-805-6714
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By rmcdouga Date 2020-03-25 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2020-03-25 Time 17:49 Sent To I
Notes
2020-03-25 18:15:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) PLANS ARE ILLEGIBLE. THE SUBMITTED FLOOR PLAN IS
 UNACCEPTABLE. PLEASE REVIEW THE FOLLOWING SECTIONS FROM
 THE WEST PALM BEACH AMENDMENTS TO THE FBC: FBC 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED
 WHEN APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) THE $1500.00 VALUE IS TOO LOW. THE VALUE USED FOR
 PERMITTING IS THE COMPLETE REPLACEMENT COST FOR ALL
 MATERIALS AND LABOR. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 4) PROVIDE ELECTRICAL PLAN FOR REVIEW THAT IS DESIGNED
 BY AND SIGNED AND SEALED BY A LICENSED DESIGN
 PROFESSIONAL OR DESIGNED BY AND SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 5) PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 6) PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
  
 7) PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 8) PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 9) SHOW THE LOCATIONS OF THE EXISTING SERVICE RISER AND
 PANEL ON THE FLOOR PLANS. WPB FBC 107.2.1
  
 10) PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 11) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 NOTE ON PLANS. NEC 210.12; FBC RE E3902.16
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 ROBERT MCDOUGAL
 COMBINATION PLANS EXAMINER
 561-805-6714
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-30 Cont ID  
Sent By cthroop Date 2020-07-30 Time 11:37 Rev Time 0.00
Received By cthroop Date 2020-07-09 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-25 Cont ID  
Sent By rmcdouga Date 2020-03-25 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2020-03-04 Time 13:11 Sent To  
Notes
2020-03-05 13:11:59R05

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By rmcphers Date 2020-03-17 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2020-03-17 Time 10:32 Sent To  
Notes
2020-03-17 10:33:31PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-07-20 Cont ID  
Sent By medwards Date 2020-07-20 Time 13:04 Rev Time 0.00
Received By medwards Date 2020-07-20 Time 12:55 Sent To  
Notes
2020-07-20 13:05:51PLEASE RESPOND TO THE 1ST CYCLE REVIEW COMMENTS. WE
 MUST SEE HOW THIS NEW ADDITION WILL BE CONDITIONED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By medwards Date 2020-03-13 Time 13:33 Rev Time  
Received By medwards Date   Time   Sent To  
Notes
2020-03-13 13:35:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT 20030157
  
 CODES IN EFFECT:
  
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS PROJECT APPEARS TO BE ADDING ADDITIONAL
 CONDITIONED SQUARE FOOTAGE. PLEASE PROVIDE THE REQUIRE
 INFORMATION ON THESE PLANS. SHOW WHERE THE HVAC SYSTEM
 IS LOCATED FOR THIS ADDITION. ATTACH SPEC SHEETS FOR
 THIS SYSTEM. PROVIDE SPEC SHEETS FOR THE BATH EXHAUST
 FAN. SHOW LOCATION OF EXHAUST TERMINATION. SHOW
 LOCATION OF CONDENSING UNIT. PROVIDE ENERGY
 CALCULATIONS FOR THIS ADDITION.
 SEE FBC EC R103.2 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DRAWN TO SCALE UPON
 SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE CODE
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED, AND SHOW IN SUFFICIENT DETAIL
 PERTINENT DATA AND FEATURES OF THE BUILDING, SYSTEMS
 AND EQUIPMENT AS HEREIN GOVERNED. DETAILS SHALL
 INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING AS
 APPLICABLE:
 1.INSULATION MATERIALS AND THEIR R-VALUES.
 2.FENESTRATION U-FACTORS AND SOLAR HEAT GAIN
 COEFFICIENTS (SHGC).
 3.AREA-WEIGHTED U-FACTOR AND SOLAR HEAT GAIN
 COEFFICIENTS (SHGC) CALCULATIONS.
 4.MECHANICAL SYSTEM DESIGN CRITERIA.
 5.MECHANICAL AND SERVICE WATER-HEATING SYSTEM AND
 EQUIPMENT TYPES, SIZES AND EFFICIENCIES.
 6.EQUIPMENT AND SYSTEM CONTROLS.
 7.DUCT SEALING, DUCT AND PIPE INSULATION AND LOCATION.
 8.AIR SEALING DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-21 Cont ID  
Sent By ccole Date 2020-07-21 Time 10:15 Rev Time 0.00
Received By ccole Date 2020-07-21 Time 09:51 Sent To  
Notes
2020-07-21 10:17:382ND REVIEW FBC-2017 PLUMBING
 PERMIT #20030157
 7/21/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENT #6 FROM THE 1ST REVIEW PRINTED BELOW WAS NOT
 ADDRESSED- PLEASE COMPLY.
  
 6) THE $1500.00 COST ON THE PERMIT APPLICATION IS
 UNDERVALUED FOR THE ENTIRE SCOPE OF THE PROJECT THAT
 INCLUDES BUILDING, MECHANICAL, ELECTRICAL, AND
 PLUMBING. PLEASE NOTE THAT PERMIT VALUE IS BASED ON
 LABOR, MATERIALS, FIXTURES, APPLIANCES, EQUIPMENT AND
 DESIGN FEES FOR ALL PHASES OF CONTRUCTION. PLEASE
 PROVIDE COPIES OF SIGNED CONTRACTS AND/OR ESTIMATES,
 INVOICES VERIFYING TOTAL VALUE OF THE PROJECT- SECTION
 109.3 WPB AMENDMENTS TO THE FBC-17.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICA/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By ccole Date 2020-03-25 Time 12:40 Rev Time 0.00
Received By ccole Date 2020-03-25 Time 12:40 Sent To  
Notes
2020-03-25 12:55:571ST REVIEW FBC-2017 PLUMBING
 PERMIT #20030157
 3/25/20
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR PLUMBING
 ALTERATIONS, AND CORRELATING DRAWINGS AND DETAILS ON A
 SEPARATE PLAN SHEET. PROVIDE A DIMENSIONED FLOOR PLAN
 DRAWING FOR THE BATHROOM SHOWING LOCATIONS OF THE
 FIXTURES AND REQUIRED FIXTURE CLEARANCES PER FIGURE
 R307.1 FBC RES. THE PLAN SHALL BE PREPARED BY, AND BEAR
 THE SIGNATURE OF THE PLUMBING SUB-CONTRACTOR OF RECORD,
 OR CAN BE PREPARED BY A FL. LICENSED ARCHITECT OR
 ENGINEER IN ACCORDANCE WITH SECTIONS 107.1 & 107.2.1
 WPB.
  
 2) REFER TO SECTION R2708.4 FBC RES AND PLACE A NOTE ON
 THE PLAN INDICATING THE SHOWER WILL BE EQUIPPED WITH
 EITHER A PRESSURE-BALANCED THERMOSTSATIC-MIXING OR
 COMBINATION PRESSURE-BALANCE/THERMOSTATIC-MIXING VALVE
 TYPE WITH A HIGH LIMIT STOP. SPECS (CUTSHEET) FOR THE
 VALVE MAY BE SUBMITTED WITH THE CORRECTED PLAN OR
 AVAILABLE ONSITE FOR INSPECTION.
  
 3) FOR ONSITE CONSTRUCTED SHOWER PANS REFER TO SECTION
 R2709.1 THROUGH P2709.4 FBC RES AND PROVIDE SHOWER
 RECEPTOR SLOPING AND LINING DETAILS.
  
 4) REFER TO SECTION R307.2 FBC RES AND INDICATE HOW THE
 SHOWER FLOOR AND WALLS WILL BE FINISHED.
  
 5) PROVIDE A CORRECTED AND CLEAR SANITARY ISOMETRIC ON
 THE NEW PLAN THAT SHOWS THE REQUIRED DRAINAGE AND VENT
 PIPES SIZES FOR THE FIXTURES- SECTIONS P3005.1 AND
 P3105.1 FBC RES. FOR TYPICAL WET VENT REQUIREMENTS SEE
 SECTION P3108.1 FBC RES.
  
 6) THE $1500.00 COST ON THE PERMIT APPLICATION IS
 UNDERVALUED FOR THE ENTIRE SCOPE OF THE PROJECT THAT
 INCLUDES BUILDING, MECHANICAL, ELECTRICAL, AND
 PLUMBING. PLEASE NOTE THAT PERMIT VALUE IS BASED ON
 LABOR, MATERIALS, FIXTURES, APPLIANCES, EQUIPMENT AND
 DESIGN FEES FOR ALL PHASES OF CONTRUCTION. PLEASE
 PROVIDE COPIES OF SIGNED CONTRACTS AND/OR ESTIMATES,
 INVOICES VERIFYING TOTAL VALUE OF THE PROJECT- SECTION
 109.3 WPB AMENDMENTS TO THE FBC-17.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICA/PLUMBINGL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2020-07-28 Cont ID  
Sent By rmcphers Date 2020-07-28 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2020-07-28 Time 10:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By rmcphers Date 2020-03-17 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2020-03-17 Time 10:33 Sent To  
Notes
2020-03-17 10:34:20SEE BUILDING COMMENTS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By rmcphers Date 2020-07-28 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2020-07-28 Time 10:28 Sent To  
Notes
2020-07-28 10:28:51SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 2 Status F Date 2020-07-17 Cont ID  
Sent By llouie Date 2020-07-17 Time   Rev Time 0.00
Received By llouie Date 2020-07-17 Time   Sent To  
Notes
2020-07-17 08:42:25** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PROPOSED TERRACE ENCLOSURE DOES NOT MEET THE
 MINIMUM BUILDING SIDE SETBACK OF 5 FT. AND THEREFORE,
 THE EXISTING TERRACE CANNOT BE ENCLOSED. [3/13/2020
 REPEAT COMMENT - DUE TO THE QUALITY OF THE SCANNED
 PLANS, STAFF CANNOT CONFIRM IF CHANGES HAD BEEN MADE TO
 ADDRESS THIS COMMENT.]
  
 2.) THE QUALITY OF THE SCANNED PLANS IS NOT GOOD, WHICH
 MAKES THE INFORMATION IN THE SITE PLAN, ARCHITECTURAL
 PLANS, ETC. DIFFICULT TO REVIEW FOR COMPLIANCE WITH THE
 ZONING CODE. PLEASE ADDRESS.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By llouie Date 2020-03-13 Time   Rev Time  
Received By llouie Date 2020-03-13 Time   Sent To  
Notes
2020-03-13 16:09:03** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE PROPOSED TERRACE ENCLOSURE DOES NOT MEET THE
 MINIMUM BUILDING SIDE SETBACK OF 5 FT. AND THEREFORE,
 THE EXISTING TERRACE CANNOT BE ENCLOSED.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  