Plan Review Details - Permit 20030146
| Plan Review Stops For Permit 20030146 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-03-01 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-03-01 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2023-03-01 07:13:07 | [email protected] | | | | | | 1. SUBMIT A COST BREAKDOWN FOR THIS JOB (COVERS TWO | | | PERMITS, ONE FOR EACH TOWER). | | | 2. THIS APPEARS TO BE A BDA/DAS SYSTEM. PLEASE | | | COORDINATE WITH [email protected] AND MARK FILLA, | | | 561-233-0837, . THIS PERMIT WILL NOT | | | BE ISSUED UNTIL EITHER FIRE MARSHALL CHIEF LEDUC, CITY | | | OF WEST PALM BEACH, OR MARK FILLA, PALM BEACH COUNTY, | | | GIVES APPROVAL FOR ISSUANCE. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2020-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-28 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-28 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2020-07-28 13:57:01 | PROVISO!!!! | | | | | | SIGNED COPY OF PLANS TO BE SUBMITTED BEFORE FINAL | | | INSPECTION TO VERIFY THE VALUE ON PERMIT APPLICATION. | | | JLEAHY | | 2020-03-04 14:05:23 | SENT TO FIRE TRAVELING WITH 20020920 JL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2023-03-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2023-03-01 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2023-03-01 11:50:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A PROPOSED BDA; HOWEVER, | | | THE RF DATA SHALL BE SUBMITTED TO MARK FILLA, PBC | | | PUBLIC RADIO MANAGER AND MYSELF VIA EMAIL FOR REVEIW | | | AND TESTING CONFIORMATIONS BEFORE A PERMIT IS | | | SUBMITTED. | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE UPDATED RF | | | SCANNING INFORMATION VIS EMAIL AS REQUIRED. | | | | | | [email protected] 561-233-0837 | | | | | | [email protected] 561-804-4709 | | | | | | 1A) THE SUBMITTED PLANS AR DATE 7/9/2020, AND MUCH MAY | | | HAVE CHANGED WITH IN THE PBC INFASTUCTURE AND SIGNAL | | | STRENGTH | | | | | | 1.7.12 PLANS AND SPECIFICATIONS. | | | | | | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | PLEASE UPDATE THE TESTING DATA AND SUBMIT AS REQUIRED. | | | | | | [email protected] 561-233-0837 | | | | | | [email protected] 561-804-4709 | | | | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2023-03-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-03-01 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-03-01 |
Time |
07:13 |
Sent To |
|
|
| Notes |
|
|
|