Plan Review Details - Permit 20030110
Plan Review Stops For Permit 20030110
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-24 Cont ID  
Sent By jwitmer Date 2020-05-24 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2020-05-24 Time 08:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-05-04 Cont ID  
Sent By jwitmer Date 2020-05-04 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2020-05-04 Time 07:01 Sent To  
Notes
2020-05-04 07:42:092017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030110
 ADD: 3101 S DIXIE HWY.
 CONT: KAST CONSTRUCTION
 TEL: 561-689-2910
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 04, 2020
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE ON SHEET S-1 BETWEEN THE
 ACCESSIBLE FLOOR PLAN OF THE RAMP AND THE ELEVATION
 VIEW THERE IS A NOTE STATING SEE ALTERNATE LANDING PLAN
 DESIGN FOR RAMPSGREATER THAN 30 FEET LONG. THERE IS NO
 ALTERNATE FLOOR PLAN SHOWING A SWITCHBACK DESIGN. 2017
 FBC-ACCESSIBILITY CODE 405.7.4 CHANGE IN DIRECTION.
  
 1ST ROUND OF COMMENTS. BOTH SHEETS C4.00 AND EX-1 BOTH
 SHOW THE LOCATION OF THE TEMPORARY LEASING TRAILER
 LOCATION ON THE SITE PLANS. BOTH SHOW AN ACCESSIBLE
 RAMP WITH A SWITCHBACK AND MID-LANDING. THE S-1 SHEET
 GREAT AMERICAN RAMP AND STAIR SHOWS A STRAIGHT RUN
 ACCESSIBLE RAMP NO SWITCHBACK AND NO MID-LANDING.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 DISCREPANCY IN PLANS.
  
 2) COMPLIED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-12 Cont ID  
Sent By jwitmer Date 2020-03-12 Time 14:53 Rev Time 0.00
Received By jwitmer Date 2020-03-12 Time 11:57 Sent To  
Notes
2020-03-12 14:52:592017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030110
 ADD: 3101 S DIXIE HWY.
 CONT: KAST CONSTRUCTION
 TEL: 561-689-2910
 E-MAIL:
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 12, 2020
 ACTION: DENIED
  
 1) BOTH SHEETS C4.00 AND EX-1 BOTH SHOW THE LOCATION OF
 THE TEMPORARY LEASING TRAILER LOCATION ON THE SITE
 PLANS. BOTH SHOW AN ACCESSIBLE RAMP WITH A SWITCHBACK
 AND MID-LANDING. THE S-1 SHEET GREAT AMERICAN RAMP AND
 STAIR SHOWS A STRAIGHT RUN ACCESSIBLE RAMP NO
 SWITCHBACK AND NO MID-LANDING. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED. DISCREPANCY IN PLANS.
  
 2) BOTH SHEETS C4.00 AND EX-1 BOTH SHOW THE LOCATION OF
 THE TEMPORARY LEASING TRAILER LOCATION BUT THE PLANS DO
 NOT SHOW ACCESSIBLE PARKING NEAR THE ACCESSIBLE RAMP.
 PLEASE SHOW THE ACCESSIBLE PATH OF TRAVEL FROM THE
 ACCESSIBLE PARKING SPACE AND ACCESS AISLE TO THE
 BEGINNING OF THE ACCESSIBLE RAMP TO THE LEASING OFFICE.
 2017 FBC-ACCESSIBILITY CODE 206.2.1AT LEAST ONE
 ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN THE SITE FROM
 THE ACCESSIBLE PARKING SPACE AND ACCESS AISLE TO THE
 ACCESSIBLE BUILDING OF FACILITY ENTRANCE THEY SERVE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-06-25 Cont ID  
Sent By jpearson Date 2020-06-25 Time 09:07 Rev Time 0.00
Received By jpearson Date 2020-06-25 Time 08:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-29 Cont ID  
Sent By jpearson Date 2020-05-29 Time 15:23 Rev Time 0.00
Received By jpearson Date 2020-05-29 Time 13:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-07 Cont ID  
Sent By jpearson Date 2020-05-07 Time 08:23 Rev Time 0.00
Received By jpearson Date 2020-05-07 Time 07:22 Sent To  
Notes
2020-05-07 08:23:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
  
 NEW COMMENT:
  
 2. NEW TEMPORARY POWER SHEET PROVIDED DOES NOT SHOW ANY
 ELECTRICAL INFORMATION. IT ONLY SHOWS THE LOCATION OF
 THE TRAILER AND GENERATOR. PROVIDE RISER DIAGRAM, LOAD
 CALCULATION, AND PANEL SCHEDULES - AN ELECTRICAL PLAN.
 WPB FBC 107.2.1, 105.1; NEC 215.5, 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-25 Cont ID  
Sent By jpearson Date 2020-03-25 Time 12:35 Rev Time 0.00
Received By jpearson Date 2020-03-25 Time 12:35 Sent To  
Notes
2020-03-25 12:33:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. THIS RESPONSIBLE PERSON MUST BE A LICENSED
 DESIGN PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. THE ELECTRICAL RISER SHEET AND OTHER SHEETS
 ARE NOT IN COMPLIANCE. PROVIDE CORRECTION. WPB FBC
 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-30 Cont ID  
Sent By pleduc Date 2020-04-30 Time   Rev Time 0.00
Received By pleduc Date 2020-04-30 Time 10:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By pleduc Date 2020-03-06 Time   Rev Time 0.00
Received By pleduc Date 2020-03-06 Time 16:29 Sent To  
Notes
2020-03-06 16:36:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF ON THE FOUNDATION PALN
 SHEET OF 4 TRAILERS, BUT TWO TRAILERS ON ANOTHER
 SEPARATE SHEET.
  
 PLEASE CONFIRM HOW MAY TRAILERS ARE CONNECTED TOGETHER.
  
  
  
 2) THERE IS NO INDICATION OF RAMP DETAILS NOR STAIRS
 AND GUARDRAILS
  
 PLEASE REVIEW AND PROVIDE IN COMPLIANCE WITH NFPA 101,
 CH 7, MEANS OF EGRESS.
  
  
  
 3) THERE IS NO INDICATION OF A FIRE EXTINGUISHERS
 WITHIN OR OUTSIDE THE TRAILER.
  
 PLEASE PROVIDE 1 AT LEAST 5LB ABC.
  
  
  
 4) PLEASE PROVIDE FOR A TEMPORARY SIGN PRIOR TO
 ENTERING THE LOOP PARKING LOT FOR FIRE DEPARTMENT
 VEHICLES STATING:
  
 "NO FIRE DEPARTMENT TURNAROUND BEYOND THIS POINT"
  
 INSTALL UNTIL TRAILER IS REMOVED.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-06-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-24 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-06-09 Cont ID  
Sent By cpuell Date 2020-06-09 Time 10:06 Rev Time 0.00
Received By cpuell Date 2020-05-20 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-19 Cont ID  
Sent By lmarchan Date 2020-05-19 Time 11:00 Rev Time 0.00
Received By lmarchan Date 2020-04-29 Time 15:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-30 Cont ID  
Sent By lmarchan Date 2020-03-30 Time 10:19 Rev Time 0.00
Received By lmarchan Date 2020-03-03 Time 13:37 Sent To  
Notes
2020-03-04 13:37:50B25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-30 Cont ID  
Sent By medwards Date 2020-04-30 Time 07:45 Rev Time 0.00
Received By medwards Date 2020-04-30 Time 07:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-19 Cont ID  
Sent By medwards Date 2020-03-19 Time 17:06 Rev Time 0.00
Received By medwards Date 2020-03-19 Time 17:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-06-25 Cont ID  
Sent By jpearson Date 2020-06-25 Time 09:07 Rev Time 0.00
Received By jpearson Date 2020-06-25 Time 09:07 Sent To  
Notes
2020-06-24 14:45:27NEW SIGNATURE FILES LOCATED IN 'SIGNATURES' FOLDER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-29 Cont ID  
Sent By jpearson Date 2020-05-29 Time 15:32 Rev Time 0.00
Received By jpearson Date 2020-05-29 Time 15:32 Sent To  
Notes
2020-05-29 15:32:28PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-05-07 Cont ID  
Sent By jpearson Date 2020-05-07 Time 08:24 Rev Time 0.00
Received By jpearson Date 2020-05-07 Time 08:24 Sent To  
Notes
2020-05-07 08:23:57PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY, A
 SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE BUILDING
 DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1;
 FS 471/481
2020-04-30 10:51:39PAPER DOCUMENTS NOT S&S; REVIEW NEEDED FOR UPLOADED
 DOCUMENTS
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-06-04 Cont ID  
Sent By jroach Date 2020-06-04 Time 11:11 Rev Time 0.00
Received By jroach Date 2020-05-28 Time 16:00 Sent To  
Notes
2020-06-04 11:11:49PROVISOS:
  
 1. THE LEASING OFFICE SHALL BE PROVIDED AT LEAST FIVE
 (5) OFF-STREET PARKING SPACES.
  
 2. THE LEASING OFFICE CAN ONLY BE USED BY THE FIRMS
 ASSOCIATED WITH THE DEVELOPMENT OF THE PROJECT, AND CAN
 ONLY BE USED TO LEASE UNITS WITHIN THE PROJECT. THERE
 SHALL BE NO LEASE OF OTHER OFF-SITE PROJECTS.
  
 3. THE TEMPORARY SALES/LEASING OFFICE SHALL NOT BE
 PERMITTED FOR MORE THAN 18 MONTHS, OR PRIOR TO ISSUANCE
 OF A CO FOR THE PROJECT, WHICHEVER COMES FIRST.
  
 4. THE TEMPORARY SALES/LEASING OFFICE SHALL NOT BE
 ILLUMINATED OR USED FOR ANY BUSINESS ACTIVITY AFTER
 9:00PM.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2020-05-28 Cont ID  
Sent By jroach Date 2020-05-28 Time 15:32 Rev Time 0.00
Received By jroach Date 2020-05-28 Time 15:31 Sent To  
Notes
2020-05-28 15:34:30ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 05.28.2020
 PERMIT NO.: 20030110
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 A. [ PARTIALLY SATISFIED ] - PURUSANT TO SEC.
 94-273(D)(73) OF THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS), AT LEAST FIVE (5) OFF-STREET
 PARKING SPACES SHALL BE PROVIDED FOR EACH SALES/LEASING
 OFFICE.
  
 A.1 [ NEW COMMENT ] - AS DISCUSSED ON 05.28.2020,
 PLEASE PROVIDE ADDITIONAL INFORMATION REGARDING THE
 PROPOSED OPENING OF PHASE I AND THE OPERATIONS OF THE
 PARKING LOT SURROUNDING THE TRAILER, UNTIL SUCH TIME AS
 THE TRAILER IS REMOVED AND THE PARKING AREA COMPLETED.
  
 PLEASE NOTE THE FOLLOWING CONDITIONS THAT WILL BE
 IMPOSED UPON ISSUANCE OF THE PERMIT, IN ACCORDANCE WITH
 SEC. 94-273(D)(73):
  
 1. THE LEASING OFFICE CAN ONLY BE USED BY THE FIRMS
 ASSOCIATED WITH THE DEVELOPMENT OF THE PROJECT, AND CAN
 ONLY BE USED TO LEASE UNITS WITHIN THE PROJECT. THERE
 SHALL BE NO LEASE OF OTHER OFF-SITE PROJECTS.
  
 2. THE TEMPORARY SALES/LEAVING OFFICE SHALL NOT BE
 PERMITTED FOR MORE THAN 18 MONTHS, OR PRIOR TO ISSUANCE
 OF A CO FOR THE PROJECT, WHICHEVER COMES FIRST.
  
 3. THE TEMPORARY SALES/LEASING OFFICE SHALL NOT BE
 ILLUMINATED OR USED FOR ANY BUSINESS ACTIVITY AFTER
 9:00PM.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
2020-05-19 08:56:38CUSTOMER REQUESTED REVIEW CYCLE BE CLOSED TO ALLOW FOR
 RESUBMITTAL WITH KNOWLEGE THAT SECOND ZONINGIS PENDING
 AND THAT THE HOLD UP AN ONGOING PLANNING PROCES.

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-26 Cont ID  
Sent By jroach Date 2020-03-26 Time 14:11 Rev Time 0.00
Received By jroach Date 2020-03-26 Time 14:11 Sent To  
Notes
2020-03-26 14:22:10ZONING PLAN REVIEW
 ________________________________________
  
 DATE OF REVIEW: 03.26.2020
 PERMIT NO.: 20030110
 ________________________________________
  
 REVIEW STATUS: FAILED
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 A. PURUSANT TO SEC. 94-273(D)(73) OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), AT LEAST FIVE
 (5) OFF-STREET PARKING SPACES SHALL BE PROVIDED FOR
 EACH SALES/LEASING OFFICE.
  
 PLEASE NOTE THE FOLLOWING CONDITIONS THAT WILL BE
 IMPOSED UPON ISSUANCE OF THE PERMIT, IN ACCORDANCE WITH
 SEC. 94-273(D)(73):
  
 1. THE LEASING OFFICE CAN ONLY BE USED BY THE FIRMS
 ASSOCIATED WITH THE DEVELOPMENT OF THE PROJECT, AND CAN
 ONLY BE USED TO LEASE UNITS WITHIN THE PROJECT. THERE
 SHALL BE NO LEASE OF OTHER OFF-SITE PROJECTS.
  
 2. THE TEMPORARY SALES/LEAVING OFFICE SHALL NOT BE
 PERMITTED FOR MORE THAN 18 MONTHS, OR PRIOR TO ISSUANCE
 OF A CO FOR THE PROJECT, WHICHEVER COMES FIRST.
  
 3. THE TEMPORARY SALES/LEASING OFFICE SHALL NOT BE
 ILLUMINATED OR USED FOR ANY BUSINESS ACTIVITY AFTER
 9:00PM.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved