Plan Review Details - Permit 20030076
Plan Review Stops For Permit 20030076
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-03-27 Cont ID  
Sent By cpuell Date 2020-03-27 Time 11:23 Rev Time 0.00
Received By jwitmer Date 2020-05-12 Time 07:33 Sent To  
Notes
2020-05-12 09:39:372017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030076
 ADD: 185 BANYAN BLVD. / UNIT 200
 CONT: ANF GROUP
 TEL: 561-260-2561
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 12, 2020
 ACTION: BUILDING PROVISOS
  
 1) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  
 2A) 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS
 OF THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO
 BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD.
  
 2B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 3) COMPONENTS & CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL
 REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, &
 ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2017 FBC-B 1604.4 ANALYSIS. THE ROOF TOP A/C STAND
 PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING
 THE AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE
 PRODUCT APPROVAL IS TO BE REVIEWED BY THE DESIGNER OF
 RECORD, APPROVED BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2020-04-22 10:26:19UNIT CHANGED TO 200
2020-03-27 13:49:31UNIT ESTABLISHED AT 200
2020-03-27 11:23:35PLEASE CONTACT [email protected] TO ESTABLISH A UNIT
 NUMBER FOR THE PERMIT. CP
2020-03-03 10:49:09SHOULD HAVE A UNIT NUMBER

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-05 Cont ID  
Sent By jwitmer Date 2020-08-05 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2020-08-05 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-17 Cont ID  
Sent By jwitmer Date 2020-07-17 Time 12:00 Rev Time 0.00
Received By jwitmer Date 2020-07-17 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-12 Cont ID  
Sent By jwitmer Date 2020-05-12 Time 09:58 Rev Time 0.00
Received By jwitmer Date 2020-05-12 Time 07:33 Sent To  
Notes
2020-05-12 09:35:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030076
 ADD: 185 BANYAN BLVD. / 2ND FLOOR LEVEL
 CONT: ANF GROUP
 TEL: 561-260-2561
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 12, 2020
  
 ACTION: BUILDING PROVISOS
  
 1) WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER
 OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
  
 2A) 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS
 OF THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO
 BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD.
  
 2B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 3) COMPONENTS & CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL
 REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, &
 ROOF TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 2017 FBC-B 1604.4 ANALYSIS. THE ROOF TOP A/C STAND
 PRODUCT APPROVALS, TO BE
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE
 FOLLOWING REQUIREMENTS CALCULATING
 THE AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF
 HEIGHT OF THE STAND AND COMPRESSORS, WEIGHT, CIRCLED
 THE DESIGN PARAMETERS IN THE TABLES,
 ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE
 STAND AND THE STAND TO THE ROOF. THE
 PRODUCT APPROVAL IS TO BE REVIEWED BY THE DESIGNER OF
 RECORD, APPROVED BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 17:49 Rev Time 0.00
Received By shill Date 2020-03-23 Time 11:06 Sent To  
Notes
2020-03-23 11:07:152017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20030076
 ADD: 185 BANYAN BLVD. 2ND FLOOR LEVEL
 CONT: ANF GROUP, INC.
 TEL: 561-260-2561 CONTACT: KIM LIDDELL
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: MON. MARCH 23/2020
 ACTION: DENIED
  
 1) SHEET G-002 CODE ANALYSIS:
 1A) UNDER THE HEADING OF EXISTING BUILDING
 CATEGORIZATION & PHYSICAL PROPERTIES THIS SHEET LIST
 THE 5TH EDITION OF THE 2014 FBC UNDER WHICH THESE PLANS
 WERE DEVELOPED. IF IN DOING SO PLEASE ALSO REFERENCE
 THE SHELL BUILDING PERMIT NUMBER 17110857 WHICH WAS
 UNDER THE 2014 FLORIDA BUILDING CODE AND THIS PROPOSED
 TENANT SPACE IS THE FIRST BUILD OUT FOR THIS AREA OF
 THE BUILDING. SEE THE 2017 EXISTING BUILDING CODE
 101.4.1. SUBSEQUENT PERMITS SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING FOR ALL NEW
 CONSTRUCTION.
  
 2) AREA PLUMBING CALCULATIONS LIST A D. F. = DRINKING
 FOUNTAIN, OWNER PROVIDED BOTTLED WATER DISPENSER.
 PLEASE REVIEW THE REQUIREMENTS OF THE 2017
 FBC-ACCESSIBILITY CODE:
 2A) DRINKING FOUNTAIN. 2017 FBC-ACCESSIBILITY CODE
 SECTION 211.2 MINIMUM NUMBER. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 2B) 2017 FBC-ACCESSIBILITY CODE SECTION 602.1 DRINKING
 FOUNTAINS SHALL COMPLY WITH 307. 2. PROTRUSION LIMITS.
 OBJECTS WITH THE LEADING EDGE MORE THAN 27 INCHES AND
 NOT MORE THAN 80 INCHES ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES MAXIMUM HORIZONTALLY
 INTO THE CIRCULATION PATH.
  
 3) SHEET A-111 THE LOUNGE DOOR 228 IT APPEARS ON THE
 LATCH SIDE OF THE INSWING DOOR THERE IS APPROXIMATELY
 13 ? INCHES NOT THE REQUIRED 18 INCHES OF SIDE
 CLEARANCE.
 2017 FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING
 CLEARANCES. DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING
 CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY
 AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. SEE
 FIGURE 404.2.1(A).
 4) SHEET A-2.11:
 4A) DETAIL # 06 SHOWS A TELEPHONE DEVICE NEXT TO THE
 DOOR IN THE LOUNGE AT A HEIGHT OF 4 FEET 6 INCHES ABOVE
 FINISH FLOOR. THIS HEIGHT IS ABOVE THE REACH RANGES AND
 OPERABLE PARTS.
  
 4A)(1) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 4A)(2) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4B) DETAIL # 10 SHOW A STAFF WORK AREA WITH COUNTER
 HEIGHT OF 4 FOOT HIGH AND A SERIES OF ELECTRICAL
 OUTLETS ABOVE THE COUNTER TOP.
 4B) DETAIL # 06 SHOWS A TELEPHONE DEVICE NEXT TO THE
 DOOR IN THE LOUNGE AT A HEIGHT OF 4 FEET 6 INCHES ABOVE
 FINISH FLOOR. THIS HEIGHT IS ABOVE THE REACH RANGES AND
 OPERABLE PARTS.
  
 4B)(1) 308 REACH RANGES. 308.2 FORWARD REACH. / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 5) SHEET A-401:
 5A) RESTROOM DETAILS BOTH A AND B BOTH SHOW THE REAR
 GRAB BAR BEING DIMENSIONED 6 INCHES FROM THE CORNER OF
 THE RESTROOMS. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE SECTION 604.5.2 REAR WALL. THE
 REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 5B) MOUNTING DETAILS 1 & 2 BOTH SHOW THE GRAB BARS
 BEING DIMENSIONED FROM THE FLOOR TO THE CENTERLINE OF
 THE GRAB BAR. PLEASE UPDATE THE PLANS TO THE 2017
 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB
 BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 5C) MOUNTING DETAIL # 3 IS FOR THE TOILET TISSUE
 DISPENSER. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 5D) MOUNTING DETAILS 8 & 9. COAT HOOKS AND SHELVES 2017
 FBC-ACCESS. CODE 603.4. COAT HOOKS SHALL BE LOCATED
 WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308.
 SHELVES SHALL BE LOCATED 40 INCHES MINIMUM AND 48
 INCHES MAXIMUM ABOVE THE SELF FOR AN (ACCESSIBLE
 SHELF).
  
 6) SHEET A-141 & M-4;
 6A) BOTH SHEETS SHOW A NEW ROOF TOP EXHAUST FAN. SHEET
 A-141 NOTE # 1 INDICATES NEW EXHAUST FAN SIZE ???X???
 ROOF SLAB OPENING. PLEASE PROVIDE THE REQUIRED SIZE OF
 THE PROPOSED HOLE THROUGH THE ROOF DETAIL # 2 OF SHEET
 A-141 STATES FOR THE NEW GALVANIZED STEEL ANGLES REFER
 TO THE STRUCTURAL DRAWINGS. IN THIS REVIEW CYCLE THERE
 IS NO STRUCTURAL DRAWINGS TO REFER TOO.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6B ) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE
 NEW ROOF TOP COMPONENTS. 2017 FBC-B 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN:
  
 6B) 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 6B)2. RISK CATEGORY.
  
 6B) 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 6B) 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 6B) 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 6B) 6.TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6C) COMMENT 6A REFERS TO NEW GALVANIZED STEEL ANGLE
 RE-ENFORCEMENT THAT IS GOING TO BE REQUIRED. THIS
 REVIEW THERE IS NO MENTION OF THE TYPE OF WELDING ,SIZE
 OF BEAD THAT WILL BE REQUIRED. THIS IS ADDITIONAL
 INFORMATION THAT WILL BE NEEDED FOR CODE COMPLIANCE. WE
 WILL ALSO NEED TO SHOW COMPLIANCE WITH:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 6D) DETAIL # 2 ALSO STATES TO SECURE THE ROOF CURB TO
 THE METAL DECK USING APPROVED FASTENERS AT 4 INCHES ON
 CENTER ENGINEERED TO WITHSTAND WINDLOADS. PLEASE
 PROVIDE THE ENGINEERING FOR THE BOLTS AND THE SIZE OF
 THE BOLTS TO BE INSTALLED IN THIS APPLICATION.
  
 6E) WE WILL ALSO NEED THE PRODUCT APPROVALS FOR THE
 ROOF TOP COMPONENTS AND CLADDING. 2017 FBC-B ,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF
 TOP VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 6F) NOTE # 3 NEW ROOF TOP COMPRESSORS CU-9, 10 & 11
 WILL ALSO NEED TO BE ANCHORED TO THE NEW 12 FOOT LONG
 PRE-ENGINEERED A/C STAND. NOTE 4 INDICATES THERE IS AN
 EXISTING A/C COMPRESSOR STAND ANCHORED TO THE ROOF, BUT
 THERE WILL BE 3 NEW COMPRESSORS, C6, 7 & 8.
  
 6G) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS.
  
 THE ROOF TOP A/C STAND PRODUCT APPROVAL TO BE SUBMITTED
 MUST BE REVIEWED BY THE DESIGNER OF RECORD. PLEASE
 IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE
 AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 6G) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 6H) THE ROOF PLAN ALSO SHOWS AN 18 INCH X 18 INCH
 INTAKE GRAVITY VENTILATOR PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR THIS ROOF TOP COMPONENT. PLEASE ALSO
 PROVIDE DOCUMENTATION FOR THE EF-1 ROOF TOP UPBLAST
 EXHAUST FAN. 1609.6.4.4.1 COMPONENTS & CLADDING.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-20 Cont ID  
Sent By jpearson Date 2020-05-20 Time 13:25 Rev Time 0.00
Received By jpearson Date 2020-05-20 Time 08:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-04-08 Cont ID  
Sent By jpearson Date 2020-04-08 Time 12:36 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:24 Sent To  
Notes
2020-04-08 10:00:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE AND DOWNSTREAM PANEL INCLUDING INFORMATION FROM
 THE POWER COMPANY STATING WHAT THE AVAILABLE SHORT
 CIRCUIT CURRENT IS FOR THE SERVICE TO CONFIRM THE
 STATED AIC RATING OF THE SERVICE EQUIPMENT AND PANELS
 IS ADEQUATE. NEC 110.9, 110.10
 2. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 3. PROVIDE AIC RATING OF ANY SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 4. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. WHILE A DETAIL WAS
 PROVIDED FOR LIGHTING CONTROLS, THE LIGHTING PLAN DOES
 NOT SHOW IMPLEMENTATION. FBC EC C405.2; WPB FBC 107.2.1
 5. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 6. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED
 PER NEC 517.13. WHAT TYPE OF HEALTH CARE FACILITY IS
 THIS? PROVIDE DETAILS. WPB FBC 107.2.1; NEC 517.13
 7. IS THERE ANY TYPE OF ESSENTIAL ELECTRICAL SYSTEM
 REQUIRED FOR THIS FACILITY? THE PLAN PROVIDED IS
 LACKING INFORMATION. PROVIDE DETAILS. NEC 517.25,517.40
 8. IS THERE ANY TYPE OF PEDIATRIC CARE AT THIS FACILITY
 THAT WOULD REQUIRE TAMPER-RESISTANT RECEPTACLES? THE
 PLAN PROVIDED IS LACKING INFORMATION. PROVIDE DETAILS.
 NEC 517.18(C)
 9. FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, LIGHTNING
 PROTECTION, GENERATORS, COMMERCIAL HOOD SYSTEMS, WALK
 IN COOLERS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND PLAN SUBMITTALS FOR ANY
 OF THESE SYSTEMS PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-19 Cont ID  
Sent By pleduc Date 2020-03-19 Time   Rev Time 0.00
Received By pleduc Date 2020-03-19 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-05 Cont ID  
Sent By lmarchan Date 2020-08-05 Time 15:29 Rev Time 0.00
Received By lmarchan Date 2020-07-17 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-07-17 Time 12:00 Rev Time 0.00
Received By lmarchan Date 2020-06-01 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-20 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-21 Time 11:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-04-13 Cont ID  
Sent By lmarchan Date 2020-04-13 Time 11:56 Rev Time 0.00
Received By lmarchan Date 2020-03-16 Time 12:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By lmarchan Date 2020-07-17 Time 08:15 Rev Time 0.00
Received By lmarchan Date 2020-06-11 Time 11:19 Sent To  
Notes
2020-07-17 08:15:59NO FEES DUE PERMIT IMPACT OFFICE.
2020-06-11 11:20:076/11/20 SENT TO IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 17:49 Rev Time 0.00
Received By shill Date 2020-03-23 Time 17:49 Sent To  
Notes
2020-03-23 17:50:06IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-05-08 Cont ID  
Sent By medwards Date 2020-04-23 Time 15:47 Rev Time 0.00
Received By medwards Date 2020-05-08 Time 13:51 Sent To  
Notes
2020-05-08 13:52:38ENERGY CALCULATIONS WERE IN A DOWNLOADED PACKAGE.
2020-04-23 15:47:42REVIEW FBC-2017 MECHANICAL
 PERMIT-20030076
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 NARRATIVE RESPONSE LETTER NOTE 1 FOR MECHANICAL STATES
 ?ENERGY CALCULATIONS AND HEATING/COOLING LOAD
 CALCULATIONS ARE PROVIDED AS AN ATTACHMENT TO THIS
 RESPONSE LETTER.? I DO NOT SEE THIS ATTACHMENT. PLEASE
 SUBMIT DOCUMENTS REFERENCED. FBC FS 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By shill Date 2020-03-27 Time 09:11 Rev Time 0.00
Received By shill Date 2020-03-27 Time 09:11 Sent To  
Notes
2020-03-27 09:12:42FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC P = FBC PLUMBING
  
 1. 2017 FBC ENERGY CODE. PROVIDE ENERGY CALCULATIONS
 AND HEATING/COOLING LOAD CALCULATIONS AS REQUIRED.
 2. 2017 FBC WIND LOADING. FOR ALL ROOF TOP MOUNTED
 EQUIPMENT, CURBS, PIPING AND PIPE STANDS, ETC. PROVIDE
 EITHER NOA OR FLORIDA APPROVED DETAILS WITH APPROVAL
 NUMBERS OR SIGNED AND SEALED STRUCTURAL DOCUMENTS WITH
 CALCULATIONS FOR WITHSTANDING WIND LOADING FOR WEST
 PALM BEACH AREA.
 3. 2017 FBC 107.2.1 PROVIDE REFRIGERANT PIPING SIZING
 ON DRAWINGS.
 PLEASE PROVIDE COMMENT/RESPONSE LETTER WITH RESUBMITTAL
 FOR EXPEDITIOUS REVIEW.
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-07-21 Cont ID  
Sent By ccole Date 2020-07-21 Time 11:37 Rev Time 0.00
Received By ccole Date 2020-07-21 Time 10:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-06-18 Cont ID  
Sent By ccole Date 2020-06-18 Time 15:07 Rev Time 0.00
Received By ccole Date 2020-06-17 Time 15:06 Sent To  
Notes
2020-06-18 15:08:243RD REVIEW FBC-2017 PLUMBING
 PERMIT #20030076
 6/18//2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: THE MODEL NUMBER OF THE WATER HEATER SHOWN
 IN THE EQUIPMENT SCHEDULE DOES NOT MATCH ANY OF THE
 MODEL NUMBERS SHOWN IN THE WATER HEATER SPECS. A) THE
 90% (.90) EFF IS UNDER THE MINIMUM (.9172) REQUIRED
 PERFORMANCE PER TABLE C404.2 FBC EC. PLEASE SEE THE
 EQUATION FOR ELECTRIC WATER HEATERS LESS THAN 12 KW.
  
 2) SHEETS A101 & P3: PLACE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS TO CLARIFY THE LOCATIONS OF ALL
 ACCESSIBLE EXAM, MEDICAL, AND LAB SINKS- SECTION 212.3
 AND 606.1 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-05-12 Cont ID  
Sent By ccole Date 2020-05-12 Time 12:46 Rev Time 0.00
Received By ccole Date 2020-05-12 Time 09:16 Sent To  
Notes
2020-05-12 12:48:292ND REVIEW FBC-2017 PLUMBING
 PERMIT #20030076
 5/12/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P6: THE REQUESTED LEGEND FOR THE NUMBERED
 NOTES AT THE WATER HEATER DETAIL WAS NOT PROVIDED-
 SECTION 107.2.1 WPB.
  
 2) P6: WATER HEATER PAN DRAIN PIPE AND TERMINATION
 LOCATION NOT SHOWN- SECTIONS 504.7.1 & 504.7.2 FBC P.
  
 3) P1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE
 WATER HEATER IN THE EQUIPMENT SCHEDULE AND SUBMIT A CUT
 SHEET TO VERIFY THE COMPLIANCE DATA NOTED IN THE
 ENERGYGAUGE SUBMITTAL- TABLE C404.2 FBC EC.
  
 4) P3 & P5: A) SHOW THE REFRIGERATOR ICE MAKE LINE
 CONNECTION AND REQUIRED WATER HAMMER ARRESTOR- SECTION
 604.9 FBC P. B) SHOW THE REQUIRED WATER HAMMER ARRESTOR
 FOR THE EWC1- SECTION 604.9. C) SHOW THE REQUIRED
 BACKFLOW PREVENTERS AND CONNECTION LOCATIONS TO THE ICE
 MAKER LINE, THE COFFEE MAKER, AND ALL OTHER DEVICES,
 APPLIANCES, APPURTENANCES, APPARATUS USED FOR SOME
 SPECIAL FUNCTION SUCH AS STERILIZATION OR PROCESSING-
 SECTIONS 608.3 & 608.16.10 FBC P.
  
 5) P1: PROVIDE EQUIPMENT SCHEDULES FOR THE BACKFLOW
 PREVENTERS- TABLE 608.1 FBC P.
  
 6) P1, P3, & P5: SHOW THE MIXING VALVE LOCATIONS FOR
 THE PUBLIC LAVATORIES- SECTION 416.5 FBC P. INDICATE
 THE VALVE IS ASSE 1070 COMPLIANT- SECTION 607.1.2 FBC
 P.
  
 7) MISSING ACCESSIBILITY DETAILS:
 A) DRINKING FOUNTAIN CLEAR FLOOR SPACE APPROACH, KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1
 FBC ACC.
 B) LOUNGE AND WAITING ROOM SINK CLEAR FLOOR SPACE
 APPROACHES, WAITING ROOM SINK RIM OR COUNTER HEIGHT,
 AND KNEE AND TOE CLEARANCES- SECTION 606.1 FBC ACC.
 C) DESIGNATED ACCESSIBLE EXAM ROOM SINK IDENTIFIED,
 CLEAR FLOOR SPACE APPROACH, SINK RIM OR COUNTER HEIGHT,
 KNEE AND TOE CLEARANCES- SECTIONS 212.3 & 606.1 FBC
 ACC.
 D) MEDICAL ROOM AND LAB ROOM SINK CLEAR FLOOR SPACE
 APPROACHES, SINK RIM OR COUNTER HEIGHTS, KNEE AND TOE
 CLEARANCES- SECTIONS 212.3 & 606.1 FBC ACC.
  
 8) A-101 & A-401: TOILET ROOM 232 OR 119- WHICH IS IT?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-27 Cont ID  
Sent By jbaker Date 2020-03-27 Time 09:03 Rev Time 0.00
Received By shill Date 2020-03-27 Time 06:38 Sent To  
Notes
2020-03-27 09:04:06FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
 FBC P = FBC PLUMBING
  
 1. 2017 FBC 107.2.1 PROVIDE LEGEND OF NUMBERED NOTES
 INDICATED ON WATER HEATER DETAIL. ALSO PROVIDE A
 SUBMITTAL OR SOME INFORMATION ON WATER HEATER
 EFFICIENCY. NO RELIEF PIPING IS SHOWN ON DETAIL.
 2. 2017 FBC 107.2.1 PROVIDE LEGEND FOR NUMBERED
 BATHROOM APPURTENANCES ON ENLARGED ARCHITECTURAL PLAN
 FOR ACCESSIBILITY IDENTIFICATION AND CODE COMPLIANCE
 AND MAKE SURE MIRRORS, TOILET PAPER, ETC ARE
 DIMENSIONED.
  
  
 REVIEWED REMOTELY BY JAMES BAKER, PE
 PX3997, PE77268
 561-805-6724
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-08-05 Cont ID  
Sent By jwitmer Date 2020-08-05 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2020-08-05 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-07-17 Cont ID  
Sent By jwitmer Date 2020-07-17 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2020-07-17 Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By medwards Date 2020-04-23 Time 15:55 Rev Time 0.00
Received By medwards Date 2020-04-23 Time 15:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-03-23 Cont ID  
Sent By shill Date 2020-03-23 Time 17:57 Rev Time 0.00
Received By shill Date 2020-03-23 Time 17:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By aaponte Date 2020-04-28 Time 08:43 Rev Time 0.00
Received By aaponte Date 2020-04-28 Time 08:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-04-13 Cont ID  
Sent By aaponte Date 2020-04-13 Time 11:45 Rev Time 0.00
Received By aaponte Date 2020-04-13 Time 11:45 Sent To  
Notes
***NONE***