Plan Review Details - Permit 20030014
Plan Review Stops For Permit 20030014
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-24 Cont ID  
Sent By jgomez Date 2020-03-24 Time 16:02 Rev Time 0.00
Received By jgomez Date 2020-03-24 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-23 Cont ID  
Sent By jgomez Date 2020-03-23 Time 10:27 Rev Time 0.00
Received By jgomez Date 2020-03-23 Time 09:38 Sent To  
Notes
2020-03-23 10:31:43 
 REVISION, SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- 03/23/2020 REVISED COMMENT #1. TALKED TO ROSANA
 CASAS (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY
 RESIDENTS AND THEIR GUESTS ONLY. NOT FOR THE PUBLIC.
 KITCHENETTE TO COMPLY WITH THE FAIR HOUSING ACT
 GUIDELINES. SEE REVISED COMMENT BELOW.
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE THE
 PARALLEL OR PERPENDICULAR CLEAR FLOOR SPACE AS REQUIRED
 BY FAIR HOUSING ACT GUIDELINES.
  
 RESPONSE:
 PLANS WERE NOT REVISED. NEED TO REVISE PLANS SHOWING
 COMPLIANCE. THE BUILT IN MICROWAVE DOESN'T COMPLY. SEC.
 107.2.1 CITY AMENDMENTS.
 (NOTE: DISCUSSED THIS WITH ROBERT BROWN- BUILDING
 OFFICIAL. MICROWAVE NEEDS TO COMPLY).
  
 2- OK.
  
  
 WHEN RESUBMITTING A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By jgomez Date 2020-03-19 Time 17:09 Rev Time 0.00
Received By jgomez Date 2020-03-19 Time 14:32 Sent To  
Notes
2020-03-19 17:09:3003/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS
 (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS
 AND THEIR GUESTS ONLY. NOT FOR THE PUBLIC. KITCHENETTE
 TO COMPLY WITH THE FAIR HOUSING ACT GUIDELINES. SEE
 REVISED COMMENT BELOW.
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE THE
 PARALLEL OR PERPENDICULAR CLEAR FLOOR SPACE AS REQUIRED
 BY FAIR HOUSING ACT GUIDELINES.
  
  
 REVISION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE REACH
 RANGE REQUIRED BY SEC. 308 FBC-ACCESSIBILITY. REVISE AS
 REQUIRED SHOWING COMPLIANCE.
 SEC. 212 AND SEC. 804 FBC-ACCESSIBILITY.
  
 2- NEW MULTIPURPOSE ROOM IS BIGGER THAN THE ONE ON THE
 APPROVED PLANS. REVISE LIFE-SAFETY PLAN SHOWING THE NEW
 OCCUPANT LOAD. SEC. 1004.1.2 FBC-BUILDING.
  
  
 WHEN RESUBMITTING A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
 03/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS
 (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS
 AND THEIR GUESTS ONLY. KITCHENETTE TO OMPLY WITH-THE
 FAIR HOUSING ACT GUIDELINES. SEE REVISED COMMENT BELOW.
 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED
 MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR
 ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE
 GUIDELINES FOR KITCHENS. SEE PAGE 2.14 AND PAGE 7.6 OF
 FAIR HOUSING ACT DESIGN MANUAL. REVISE PLANS AS
 REQUIRED SHOWING COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-19 Cont ID  
Sent By jpearson Date 2020-03-19 Time 10:27 Rev Time 0.00
Received By jpearson Date 2020-03-19 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-03-25 Cont ID  
Sent By pleduc Date 2020-03-25 Time   Rev Time 0.00
Received By pleduc Date 2020-03-25 Time 09:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-23 Cont ID  
Sent By pleduc Date 2020-03-23 Time   Rev Time 0.00
Received By pleduc Date 2020-03-23 Time 10:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-19 Cont ID  
Sent By pleduc Date 2020-03-19 Time   Rev Time 0.00
Received By pleduc Date 2020-03-19 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-27 Time 15:03 Rev Time 0.00
Received By jgomez Date 2020-03-24 Time 11:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-20 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-19 Cont ID  
Sent By jgomez Date 2020-03-19 Time 17:11 Rev Time 0.00
Received By jgomez Date 2020-03-18 Time 15:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-27 Cont ID  
Sent By jgomez Date 2020-03-27 Time 15:01 Rev Time 0.00
Received By jgomez Date 2020-03-27 Time 14:53 Sent To  
Notes
2020-03-27 15:02:56E-MAIL WAS SENT BY JOHN PEARSON TO THE ELECTRICAL
 ENGINEER ON 03/19/2020 NOTIFYING HIM ABOUT THE SELF
 CERTIFIED SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-23 Cont ID  
Sent By jpearson Date 2020-03-23 Time 11:17 Rev Time 0.00
Received By jpearson Date 2020-03-23 Time 11:16 Sent To  
Notes
2020-03-23 11:16:56ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By lmarchan Date 2020-03-20 Time 08:05 Rev Time 0.00
Received By lmarchan Date 2020-03-20 Time 08:05 Sent To  
Notes
2020-03-19 10:10:32ELECTRICAL SHEETS: PER THE WPB AMENDMENTS TO THE FBC,
 EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL
 PLAN REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. SELF-CERTIFICATION IS NOT
 ACCEPTABLE FOR ENGINEERS. PROVIDE CORRECTION. WPB FBC
 107.1; FS 471/481