| 2020-03-19 17:09:30 | 03/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS |
| | (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS |
| | AND THEIR GUESTS ONLY. NOT FOR THE PUBLIC. KITCHENETTE |
| | TO COMPLY WITH THE FAIR HOUSING ACT GUIDELINES. SEE |
| | REVISED COMMENT BELOW. |
| | 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED |
| | MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR |
| | ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE THE |
| | PARALLEL OR PERPENDICULAR CLEAR FLOOR SPACE AS REQUIRED |
| | BY FAIR HOUSING ACT GUIDELINES. |
| | |
| | |
| | REVISION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED |
| | MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR |
| | ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE REACH |
| | RANGE REQUIRED BY SEC. 308 FBC-ACCESSIBILITY. REVISE AS |
| | REQUIRED SHOWING COMPLIANCE. |
| | SEC. 212 AND SEC. 804 FBC-ACCESSIBILITY. |
| | |
| | 2- NEW MULTIPURPOSE ROOM IS BIGGER THAN THE ONE ON THE |
| | APPROVED PLANS. REVISE LIFE-SAFETY PLAN SHOWING THE NEW |
| | OCCUPANT LOAD. SEC. 1004.1.2 FBC-BUILDING. |
| | |
| | |
| | WHEN RESUBMITTING A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | 03/23/2020 REVISED COMMENT #1. TALKED TO ROSANA CASAS |
| | (ARCH.) MULTIPURPOSE ROOM IS TO BE USED BY RESIDENTS |
| | AND THEIR GUESTS ONLY. KITCHENETTE TO OMPLY WITH-THE |
| | FAIR HOUSING ACT GUIDELINES. SEE REVISED COMMENT BELOW. |
| | 1- A NEW KITCHENETTE IS SHOWN ON THE REVISED |
| | MULTIPURPOSE ROOM. THE MICROWAVE SHOWN ON THE INTERIOR |
| | ELEVATION ON SHEET A3.13 DOESN'T COMPLY WITH THE |
| | GUIDELINES FOR KITCHENS. SEE PAGE 2.14 AND PAGE 7.6 OF |
| | FAIR HOUSING ACT DESIGN MANUAL. REVISE PLANS AS |
| | REQUIRED SHOWING COMPLIANCE. |