| 2020-03-09 15:40:08 | RESIDENTIAL (R2) ROOFING SUB BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1) FOOTPRINT OF ROOF PLAN SUBMITTED DOESN'T MATCH THE |
| | ROOF PLAN FOR MASTER PERMIT 19040464. REVISE AS |
| | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2) ROOF TILE NOA 18-0509.15 SUBMITTED SHOW ON PAGE 5 OF |
| | 8 THAT THE CONCRETE TILE WILL BE FASTENED WITH 1 #8 |
| | SCREW. THE ATTACHMENT RESISTANCE EXPRESSED AS A MOMENT |
| | FOR 1 #8 SCREW IS 20.7. USING TABLE 2A OF THE FRSA/TRI |
| | MANUAL (REVISED 5TH EDITION) AS A REFERENCE, THE 20.7 |
| | UPLIFT MOMENT IS VERY LOW FOR A 5 STORY BUILDING. NOTE: |
| | TABLE 2A OF THE FRSA/TRI MANUAL IS FOR THE FIELD TILE |
| | ONLY. |
| | PROVIDE ENGINEERING CALCULATIONS FOR THE REQUIRED |
| | UPLIFT MOMENT OF THE TILE IN ALL ROOF ZONES OF THIS |
| | BUILDING AND REVISE THE FASTENING METHOD TO COMPLY WITH |
| | SUCH CALCULATIONS. SEC. 107.2.1.1 AND SEC. 107.2.1.2 |
| | CITY AMENDMENTS. |
| | |
| | 3) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE CALCULATIONS, PRODUCT |
| | APPROVALS AND FASTENING METHOD AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| | DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |