| 2020-03-20 16:57:24 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT #20021256 |
| | 3/20/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTHE EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A FOOD SERVICE EQUIPMENT PLAN AND |
| | EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEETS A.0, A4.0 & P2.2: THE PLANS SHALL BE DESIGNED |
| | IN ACCORDANCE WITH THE FLORIDA ACCESSIBILITY SIXTH |
| | EDITION 2017 CODE. PLEASE REMOVE REFERENCES TO ADA. |
| | |
| | 3) A4.0, DETAIL C: PROVIDE THE HEIGHT OF THE SIDE WALL |
| | GRAB BAR FROM THE FINISHED FLOOR- SECTION 609.4 FBC |
| | ACC. A) SHOW THE REQUIRED 54" MINIMUM EXTENSION OF THE |
| | SIDE WALL GRAB BAR FROM THE REAR WALL- SECTION 604.5.1 |
| | FBC ACC. |
| | |
| | 4) A2.0 & A4.0: SHOW THE REQUIRED CLEAR FLOOR SPACE AND |
| | KNEE AND TOE CLEARANCE FOR THE ACCESSIBLE DRINKING |
| | FOUNTAIN- SEE SECTIONS 305, 306, & 602.2 FBC ACC. |
| | |
| | 5) A2.0, A4.0 & P2.2: THE BREAKROOM SINK IS NOT SHOWN |
| | ON ANY OF THE ARCHITECTURAL OF PLUMBING DRAWINGS APART |
| | FROM P2.2. PLEASE NOTE THE SINK SHALL BE ACCESSIBLE AND |
| | MEET ALL REQUIREMENTS LISTED UNDER SECTIONS 606.2 |
| | THROUGH 606.5 FBC ACC. |
| | |
| | 6) A2.0, A4.0, P1.1 & P2.2: PLEASE SHOW THE |
| | WASHER/DRYER CONSISTENTLY ON ALL THE DRAWINGS AND REFER |
| | TO SECTION 611 FBC ACC OR ACCESSIBILITY REQUIREMENTS. |
| | |
| | 6) P0.1: BECAUSE ALL PLUMBING FIXTURES ARE REQUIRED TO |
| | MEET THE CURRENT ASME AND NSF STANDARDS, "BY OWNER" IS |
| | NOT AN ACCEPTABLE ALTERNATIVE FROM PROVIDING |
| | MANUFACTURER AND MODEL NUMBERS OF THE 3-COMPARTMENT AND |
| | DEEP SINKS, AND THE TRENCH DRAINS- SECTIONS 418.1 & |
| | 412.1 FBC P. A) PLEASE ADD THE FLOOR SINKS AND HUB |
| | DRAINS TO THE SCHEDULE- |
| | |
| | 7) P0.1 & P1.1: A SEPARATE PERMIT IS REQUIRED FOR THE |
| | GREASE INTERCEPTOR, HOWEVER BASED ON THE CURRENT PLANS, |
| | A THOROUGH REVIEW CANNOT BE COMPLETED. PLEASE NOTE: |
| | A) THE GREASE INTERCEPTOR SIZING CALCULATIONS DO NOT |
| | INCLUDE THE VARIOUS FLOOR AND TROUGH DRAINS SHOWN ON |
| | THE PLANS. BECAUSE THERE ARE NO FOOD SERVICE PLANS IT |
| | IS NOT CLEAR IF THOSE FIXTURES NEED TO BE INCLUDED IN |
| | THE CALCULATIONS- SECTION 1003.1 FBC P. |
| | B) REFER TO SECTIONS 1000.3.4 THROUGH 1003.3.6 FBC P: |
| | MANUFACTURER'S SPECIFICATIONS MUST BE SUBMITTED WITH |
| | APPROVAL STAMP BY THE ENGINEER OF RECORD. |
| | C) CIVIL PLANS MUST BE SUBMITTED SHOWING THE LOCATION |
| | OF THE UNDERGROUND INTERCEPTOR AND THE INLET AND |
| | CONNECTION OF THE GREASE WASTE LINE AND THE DISCHARGE |
| | PIPING CONNECTION INTO THE MAIN SANITARY SEWER. PLEASE |
| | NOTE THAT HYDRO MECHANICAL TYPE INTERCEPTORS REQUIRE |
| | VENTED FLOW CONTROL DEVICES AND ALL INTERCEPTORS |
| | REQUIRE APPROVAL BY THE WPB UTILITIES DEPARTMENT. FOR |
| | FURTHER INFORMATION PLEASE CONTACT CHIEF PLUMBING |
| | INSPECTOR TIMOTHY LARGE- 561-805-6692. |
| | |
| | 8) P0.1 & P2.2 WATER HEATER: A) SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS WITH APPROVAL STAMP BY THE EOR- SECTION |
| | 502.1 FBC P. B) REFER TO SECTION 502.5 AND INDICATE HOW |
| | THE WATER HEATER WILL BE SUPPORTED ABOVE THE CEILING |
| | AND HOW ACCESS WILL BE PROVIDED. PLEASE NOTE THAT A |
| | 30X30" LEVEL WORKING SPACE SHALL BE PROVIDED IN FRONT |
| | OF THE CONTROL SIDE OF THE APPLIANCE. C) PROVIDE THE |
| | CORRECT CODE SECTIONS SHOWN IN THE WATER PIPING DETAIL- |
| | SECTIONS 504.7 THROUGH 504.7.2 FBC P. D) THE 0.93 |
| | ENERGY FACTOR IN THE SCHEDULE DOES NOT MATCH THE 0.92 |
| | FACTOR IN THE ENERGYGAUGE COMPLIANCE REPORT- SEE TABLE |
| | C404.2 FBC EC- NOTE THE 0.90 MIN. EFF REQUIRED IS NOT |
| | IN COMPLIANCE WITH THE TABLE. |
| | |
| | 9) P0.1 & P1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | CIRCULATION PUMP AND VERIFY REQUIRED AUTOMATIC ON/OFF |
| | CONTROLS WILL BE PROVIDED- SECTION C404.6.1 FBC EC. |
| | |
| | 10) P1.1 & P1.2: VERIFY THE WATER SERVICE PIPE AND |
| | WATER DISTRIBUTION PIPES ARE ADEQUATELY SIZED TO |
| | PROVIDE THE REQUIRED FLOW RATES AND PRESSURES FOR THE |
| | NEW FIXTURES PER TABLE 604.3 FBC P. |
| | |
| | 11) P1.1. & P1.2: TEMPERATURE LIMITING DEVICES ARE |
| | REQUIRED TO PROVIDE TEMPERED WATER TO THE LAVATORIES- |
| | SECTION 416.5 FBC P. PLEASE INCLUDE THE DEVICES IN THE |
| | FIXTURE SCHEDULE ON SHEET P0.1- SECTION 607.1.2 FBC P. |
| | |
| | 12) P1.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF THE |
| | REQUIRED WATER HAMMER ARRESTORS ON THE WASHING MACHINE |
| | SUPPLY LINES AND ALL OTHER FIXTURES OR APPLIANCES WITH |
| | QUICK CLOSING VALVES- SECTION 604.9 FBC P. |
| | |
| | 13) P1.2: PROVIDE SYMBOLS TO SHOW THE LOCATIONS OF THE |
| | REQUIRED BACKFLOW PREVENTERS ON WATER LINES CONNECTING |
| | TO THE COFFEE MACHINE, ICE MACHINE, ICE MAKERS ETC.- |
| | SECTIONS 608.3, 608.16.1 & 608.16.10 FBC P. |
| | |
| | 14) P1.2 & P1.3: FIXTURE TRAP AND FIXTURE VENT SIZES |
| | NOT SHOWN- TABLE 709.1 AND SECTION 906.2 FBC P. |
| | |
| | 15) P1.1 & P1.3: IT APPEARS THE FLOOR DRAINS IN THE |
| | MAIN SHOW ROOM WILL BE VENTED VIA A COMBINATION WASTE |
| | AND VENT SYSTEM PER SECTION 915.1 FBC P, HOWEVER NO |
| | VENT SIZES ARE SHOWN IN THE ISOMETRIC TO VERIFY |
| | ADEQUATE SIZING AND DISTANCE AS REQUIRED BY SECTIONS |
| | 915.2.3 THROUGH 915.2.5. |
| | |
| | 16) P1.1 & P1.3: SHOW THE HUB DRAIN CONNECTIONS INTO |
| | THE ISOMETRIC DRAWING- SECTION 710.1 FBC P. |
| | |
| | 17) P1.1 & P1.3: IT APPEARS TWO FD'S LOCATED UPSTREAM |
| | OF THE DELI DRAIN BRANCH CONNECTION ARE NOT SHOWN IN |
| | THE ISOMETRIC- SECTION 710.1 FBC P |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |