| | BUILDING REVIEW CHECKLIST. |
| | BUILDING REVIEW WAS APPROVED ON 01/29/2020 WITH PROVISO |
| | TO ALLOW PERMIT ISSUANCE. THE PROVISO ITEMS HAVE NOT |
| | BEEN SUBMITTED. PLEASE PROVIDE THE FOLLOWING: |
| | |
| | 1- REVISE AND RE-SUBMIT TRUSS PACKAGE: |
| | (A)TRUSS ENGINEER TO REVISE THE TRUSS DESIGN CRITERIA. |
| | BUILDING IS LOCATED IN EXPOSURE "C" NOT "B". SEE PLANS |
| | AND REVISE AS REQUIRED. |
| | (B)ENGINEER OF RECORD NEED TO REVIEW AND APPROVED THE |
| | TRUSS PACKAGE BEFORE SUBMITTAL. |
| | |
| | 2- REVISE ENERGY CALCULATIONS: |
| | (A) PROVIDE CORRECT JURISDICTION NUMBER (604700). |
| | (B)REVISE DOOR INFORMATION PAGE 3 OF 4. DOOR NOA |
| | 17-1212.10 SUBMITTED IS FOR GLAZED DOOR. THIS DOOR |
| | NEEDS TO BE IN WINDOW GLAZING AREA. SEC. R405.5.3.3 |
| | FBC-ENERGY CONSERVATION. |
| | (C) REVISE OVERHANG DEPTH AND SEPARATION OF WINDOW |
| | LOCATED ON THE NORTH SIDE. SEE PLANS AND REVISE AS |
| | REQUIRED. . |
| | |
| | 3- DOOR NOA 17-1212.10 DON'T HAVE IMPACT GLAZING. |
| | PROVIDE SHUTTERS PRODUCT APPROVAL (2 COPIES) AND |
| | COMPLETE INSTALLATION SCHEDULE. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS (DOORS, |
| | WINDOWS, SHINGLES, SHUTTERS). |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |