Plan Review Details - Permit 20021174
Plan Review Stops For Permit 20021174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By pvalenti Date 2020-03-10 Time 09:41 Rev Time 0.00
Received By pvalenti Date 2020-03-10 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By pvalenti Date 2020-03-03 Time 16:50 Rev Time 0.00
Received By pvalenti Date 2020-03-03 Time 13:06 Sent To  
Notes
2020-03-03 17:00:55***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW (TENTS) DENIED:
  
 1) FBC B 107.2.1, PLEASE CHANGE MIAMI ADDRESS TO WEST
 PALM BEACH ADDRESS ON ALL PAGES.
  
 2) FBC B 107.2.1, PLEASE CHANGE THE CONTACTY LIST ON
 PLANS FROM MIAMI PERSONELL TO WEST PALM BEACH
 PERSONELL.
  
 3) FBC B 1609.4.3, PLEASE CHANGE THE WIND EXPOSURE AND
 RECALCULATE THE WIND LOADS FOR THE TENTS ON ALL OF THE
 SUBMITTED TENT PACKAGES.
  
 4) FBC B 107.2.1, PLEASE PROVIDE THE LAG BOLT SIZES FOR
 THE DETAIL ON PAGE S-6, BASE PLATE CONNECTIONS TO THE
 DOCKS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By pleduc Date 2020-03-11 Time   Rev Time 0.00
Received By pleduc Date 2020-03-11 Time 13:59 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 14:29 Sent To Z
Notes
2020-03-04 14:44:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE REFERENCES TO MIAMI ON EACH TITLE PAGE AND
 MIAMI PERSONNEL ON PAGE 7
  
 PLEASE CORRECT.
  
  
  
 2) THERE IS LARGE BOST INDICATED ON EVERNIA ST THAT
 APPEARS TO BLOCK INGRESS/EGRESS.
  
 WAS THIS BOAT LOCATION APPROVED THROUGH ASSISTANT FIRE
 CHIEF GRIBBLE?
  
 IF SO PLEASE PROVIDE A NOTE.
  
 IF NOTE CORRECT AND PROVIDE FREE INGRESS/EGRESS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-09 Cont ID  
Sent By lmarchan Date 2020-03-09 Time 10:21 Rev Time 0.00
Received By lmarchan Date 2020-03-02 Time 15:26 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status N Date 2020-03-03 Cont ID  
Sent By cthroop Date 2020-03-03 Time 08:14 Rev Time 0.00
Received By cthroop Date 2020-03-02 Time 15:26 Sent To  
Notes
2020-03-03 08:14:56OCCUPANT LOAD DOES NOT QUALIFY FOR THRESHOLD. NO S.I.
 REQUIRED. CT

Review Stop Z ZONING
Rev No 1 Status P Date 2020-03-10 Cont ID  
Sent By aaponte Date 2020-03-09 Time 10:09 Rev Time 0.00
Received By aaponte Date 2020-03-09 Time 10:09 Sent To  
Notes
***NONE***