Plan Review Details - Permit 20021169
Plan Review Stops For Permit 20021169
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2020-02-29 Cont ID  
Sent By pvalenti Date 2020-02-29 Time 14:58 Rev Time 0.00
Received By pvalenti Date 2020-02-29 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 15:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By jwitmer Date 2020-03-03 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2020-03-03 Time 11:01 Sent To  
Notes
2020-03-03 13:11:522017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20021169
 ADD: 2475 MERCER AVE. SUITE: 105
 CONT: SEARCH CONSTRUCTION, INC.
 TEL: 561-346-8191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 03/2020
 ACTION: DENIED
 1) BOTH SETS OF PLANS IN THE TITLEBLOCK SOMEONE HAS
 USED PEN TO SCRATCH THROUGH AND HAND WRITTEN WPB AS
 PART OF THE ADDRESS.
 61G1-16.004 TITLE BLOCK. ARCHITECT. (3) NAME OR
 IDENTIFICATION OF PROJECT.
  
 2) SHEET A-1 THE BREAKROOM SINK IS SHOWN TO BE
 ACCESSIBLE COUNTER AT 32 INCHES ABOVE FINISH FLOOR. IT
 WOULD APPEAR YOU ARE GOING TO USE A SIDE APPROACH TO
 THE SINK. PLEASE SHOW YOUR CLEAR FLOOR AREA 30X 48
 INCHES FOR A SIDE APPROACH. 2017 FBC-ACCESSIBILITY CODE
 305.5 & FIGURE 305.5(B) PARALLEL APPROACH.
  
 3) SHEET A-1 HANDICAPPED ACCESSIBLE DETAILS:
  
 3A) PLEASE NOTE THE GRAB BAR FOR THE WATER CLOSET IS
 SHOWN TO BE MEASURED/ DIMENSIONED FROM FINISH FLOOR TO
 THE CENTERLINE OF THE GRAB BAR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3B) PLEASE NOTE THE TOILET PAPER HOLDER FOR PLACEMENT
 IS SHOWN TO BE CENTERLINE 36 INCHES FROM THE REAR WALL
 LINE. PLEASE SHOW COMPLIANCE WITH TOILET PAPER
 DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-05-01 Cont ID  
Sent By jpearson Date 2020-05-01 Time 08:27 Rev Time 0.00
Received By jpearson Date 2020-05-01 Time 08:11 Sent To  
Notes
2020-04-22 13:12:09REVISED PLAN. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-20 Cont ID  
Sent By jpearson Date 2020-03-20 Time 14:53 Rev Time 0.00
Received By jpearson Date 2020-03-20 Time 14:53 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By pleduc Date 2020-04-23 Time   Rev Time 0.00
Received By pleduc Date 2020-04-23 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-01 Time   Rev Time 0.00
Received By jgomez Date 2020-04-20 Time 17:08 Sent To  
Notes
2020-04-22 17:08:53CONVERTED TO DIGITAL. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-20 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-26 Time 13:08 Sent To  
Notes
2020-02-27 13:08:48B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By ccole Date 2020-04-23 Time 10:02 Rev Time 0.00
Received By ccole Date 2020-04-23 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By ccole Date 2020-03-17 Time 08:40 Rev Time 0.00
Received By ccole Date 2020-03-17 Time 08:40 Sent To  
Notes
2020-03-17 08:44:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20021169
 3/17/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL PLANS SHOWING ALL REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS- SUPPLY AND RETURN
 DUCT, DIFFUSER, AND GRILL RELOCATIONS ETC.- SECTION
 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-27 Cont ID  
Sent By jwitmer Date 2020-04-27 Time 15:31 Rev Time 0.00
Received By jwitmer Date 2020-04-27 Time 15:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By jwitmer Date 2020-03-17 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2020-03-17 Time 10:09 Sent To  
Notes
2020-03-17 10:21:022017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 20021169
 ADD: 2475 MERCER AVE. SUITE: 105
 CONT: SEARCH CONSTRUCTION, INC.
 TEL: 561-346-8191
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 017TH/ 2020
 ACTION: DENIED
 1) BOTH SETS OF PLANS IN THE TITLEBLOCK SOMEONE HAS
 USED PEN TO SCRATCH THROUGH AND HAND WRITTEN WPB AS
 PART OF THE ADDRESS.
 61G1-16.004 TITLE BLOCK. ARCHITECT. (3) NAME OR
 IDENTIFICATION OF PROJECT.
  
 2) SHEET A-1 THE BREAKROOM SINK IS SHOWN TO BE
 ACCESSIBLE COUNTER AT 32 INCHES ABOVE FINISH FLOOR. IT
 WOULD APPEAR YOU ARE GOING TO USE A SIDE APPROACH TO
 THE SINK. PLEASE SHOW YOUR CLEAR FLOOR AREA 30X 48
 INCHES FOR A SIDE APPROACH. 2017 FBC-ACCESSIBILITY CODE
 305.5 & FIGURE 305.5(B) PARALLEL APPROACH.
  
 3) SHEET A-1 HANDICAPPED ACCESSIBLE DETAILS:
  
 3A) PLEASE NOTE THE GRAB BAR FOR THE WATER CLOSET IS
 SHOWN TO BE MEASURED/ DIMENSIONED FROM FINISH FLOOR TO
 THE CENTERLINE OF THE GRAB BAR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
  
 3B) PLEASE NOTE THE TOILET PAPER HOLDER FOR PLACEMENT
 IS SHOWN TO BE CENTERLINE 36 INCHES FROM THE REAR WALL
 LINE. PLEASE SHOW COMPLIANCE WITH TOILET PAPER
 DISPENSERS. 2017 FBC-ACCESS. CODE 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS.
 DISPENSERS SHALL NOT BE OF A TYPE THAT CONTROLS
 DELIVERY OR THAT DOES NOT ALLOW CONTINUOUS PAPER FLOW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-22 Cont ID  
Sent By jgomez Date 2020-04-22 Time 17:07 Rev Time 0.00
Received By jgomez Date 2020-04-22 Time 17:07 Sent To  
Notes
2020-04-22 17:08:12CONVERTED TO DIGITAL.
 DRAWINGS WITH ARCHITECT'S ORIGINAL SEAL/SIGNATURE ON
 CITY'S FILE. JG