Plan Review Details - Permit 20021115
Plan Review Stops For Permit 20021115
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-05-27 Cont ID  
Sent By jgomez Date 2020-05-27 Time 10:15 Rev Time 0.00
Received By jgomez Date 2020-05-27 Time 10:13 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By jwitmer Date 2020-03-03 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2020-03-03 Time 13:23 Sent To  
Notes
2020-03-03 13:23:42PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-05-27 Cont ID  
Sent By jgomez Date 2020-05-27 Time 10:15 Rev Time 0.00
Received By jgomez Date 2020-05-27 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-03 Cont ID  
Sent By jwitmer Date 2020-03-03 Time 13:58 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2020-03-03 13:57:412017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20021115
 ADD: 1200 S. FLAGLER DR. SUITE: 303
 CONT: CAMBRIDGE CONSTRUCTION LLC
 TEL: 561-784-3722
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 03/2020
 ACTION: DENIED
  
 1) W 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR TO BE LICENSED IN
 THE TRADE THAT THEY WILL BE CREATING THE PLANS TO BE
 SUBMITTED TO THE BUILDING DEPARTMENT. FOR EACH TRADE
 THE CONTRACTOR RESPONSIBLE FOR THE PLAN MUST PRINT
 THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER.
  
 2) THE SUBMITTED FLOOR PLAN HAS A NOTE TO DROP THE
 CEILINGS IN BOTH BEDROOMS TO ACCOMMODATE NEW CEILING
 FANS. THE PLANS ARE SILENT AS TO HOW FAR THE CEILINGS
 ARE TO BE DROPPED. THE PLANS DO NOT INDICATE THE TYPE
 OF ANCHOR TO BE FASTENED INTO THE CONCRETE DECK ABOVE,
 DEPTH OF FASTENER INTO THE CONCRETE DECK, IS THE
 CONCRETE DECK POST TENSION?
 PROVIDE THE TYPE OF FRAMING MEMBER TO BE INSTALLED SIZE
 AND SPACING, PLEASE NOT THIS IS A HIGHRISE AND ALL
 FRAMING MEMBERS ARE TO BE NON-COMBUSTIBLE. PLEASE
 PROVIDE THE JOIST SPACING IN INCHES, THE SPAN, IS THE
 MID-POINT UNSUPPORTED OR IS THERE A MID-SPAN SUPPORT.
 PLEASE PROVIDE THE TYPE OF CEILING MATERIAL AND
 THICKNESS AND ALLOWABLE SPANS? 2017 FBC-B 2508.1/ TABLE
 2508.1 STEEL FRAMING FOR GYPSUM BOARD ASTM C754.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-10 Cont ID  
Sent By jleahy Date 2020-03-10 Time 12:32 Rev Time 0.00
Received By jleahy Date 2020-03-10 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 11:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-05-27 Cont ID  
Sent By jgomez Date 2020-05-27 Time 10:15 Rev Time 0.00
Received By jgomez Date 2020-05-08 Time 16:17 Sent To I
Notes
2020-05-08 16:18:20ROUTED TO B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-10 Cont ID  
Sent By tklarge Date 2020-03-10 Time 14:31 Rev Time 0.00
Received By tklarge Date 2020-02-26 Time 13:10 Sent To  
Notes
2020-02-27 13:10:22B07

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-10 Cont ID  
Sent By tklarge Date 2020-03-10 Time 14:31 Rev Time 0.00
Received By tklarge Date 2020-03-10 Time 14:28 Sent To  
Notes
***NONE***