Plan Review Details - Permit 20021075
Plan Review Stops For Permit 20021075
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By cthroop Date 2020-04-23 Time 16:20 Rev Time 0.00
Received By cthroop Date 2020-04-15 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By cthroop Date 2020-03-06 Time 11:38 Rev Time 0.00
Received By cthroop Date 2020-03-04 Time 17:10 Sent To  
Notes
2020-03-06 11:56:05PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT
 PER R BROWN
  
 CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II
  
 GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING
 CHAPT. 8
  
 1. PROVIDE FLOOR PLAN WITH DEMENSIONS OF EXISTING
 CONDITIONS
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2. MECHANICAL, ELECTRICAL & PLUMBING PERMITS SHALL BE
 REQUIRED.
  
 PERMITS
 105.1 REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-04-23 Cont ID  
Sent By cthroop Date 2020-04-23 Time 15:49 Rev Time 0.00
Received By cthroop Date 2020-04-23 Time 15:49 Sent To  
Notes
2020-04-23 15:49:51NEW ELECTRICAL PER MASTER 19090477.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By cthroop Date 2020-03-06 Time 12:13 Rev Time 0.00
Received By cthroop Date 2020-03-04 Time 17:11 Sent To  
Notes
2020-03-06 12:15:04PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT
 PER R BROWN
  
 CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II
  
 GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING
 CHAPT. 8
  
 1. PROVIDE A CODE COMPLIANT ELECTRICAL PLAN.
  
 PERMITS
 105.1 REQUIRED.
  
 2. PROVIDE FLOOR PLAN.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 3. PROVIDE RISER DIAGRAHM.
  
 RISER:
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
  
 4. PROVIDE LOAD CALCULATIONS.
  
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE E3602.2
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2
  
 5. PROVIDE PANEL SCHEDULE.
  
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902.
  
 6. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-06 Cont ID  
Sent By cthroop Date 2020-03-06 Time 14:36 Rev Time 0.00
Received By cthroop Date 2020-02-25 Time 13:34 Sent To I
Notes
2020-02-26 13:35:04REVISION ROUTED TO CTHROOP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2020-05-28 Cont ID  
Sent By lmarchan Date 2020-05-28 Time 15:09 Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 09:09 Sent To  
Notes
2020-05-28 14:49:52MU-2020-15464 - $1693.14 - PAID
2020-05-08 09:09:345/8 SENT TO IMPACT OFFICE FOR REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2020-04-24 Cont ID  
Sent By cthroop Date 2020-04-23 Time 15:51 Rev Time 0.00
Received By cthroop Date 2020-04-23 Time 15:51 Sent To  
Notes
2020-04-24 14:35:28IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-04-15 Cont ID  
Sent By shill Date 2020-04-15 Time 17:27 Rev Time 0.00
Received By shill Date 2020-04-15 Time 17:27 Sent To  
Notes
2020-04-15 17:28:15IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-04-23 Cont ID  
Sent By cthroop Date 2020-04-23 Time 15:50 Rev Time 0.00
Received By cthroop Date 2020-04-23 Time 15:50 Sent To  
Notes
2020-04-23 15:50:42MECHANICAL PER MASTER 190900477.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By cthroop Date 2020-03-06 Time 11:56 Rev Time 0.00
Received By cthroop Date 2020-03-04 Time 17:10 Sent To  
Notes
2020-03-06 12:13:47PLAN REVIEW - MECHANICAL PERMIT # 20021075
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER - BUILDING - PX3169
 PLANS EXAMINER - 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT
 PER R BROWN
  
 CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II
  
 IN ADDITION TO CODES IN EFFECT REFERENCED ABOVE -
 GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING
 CHAPT. 8
  
 1. PROVIDE CODE COMPLIANT MECHANICAL PLAN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 EQUIPMENT SCHEDULE ON PLAN SHALL MATCH EQUIPMENT ON
 MANUAL J.
  
 2. PROVIDE ENERGY SUBMITTAL.
 PROVIDE ENERGY GUAGE AND MANUAL J.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.+
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 3. BATHROOM EXHAUST
 M1507.4LOCAL EXHAUST RATES.
 LOCAL EXHAUST SYSTEMS SHALL BE DESIGNED TO HAVE THE
 CAPACITY TO EXHAUST THE MINIMUM AIR FLOW RATE
 DETERMINED IN ACCORDANCE WITH TABLE M1507.4.
  
 BATHROOMS-TOILET ROOMS - MECHANICAL EXHAUST CAPACITY OF
 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS
  
 4. M1411.3 CONDENSATE DISPOSAL.
 CONDENSATE FROM COOLING COILS AND EVAPORATORS SHALL BE
 CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE
 OF DISPOSAL. SUCH PIPING SHALL MAINTAIN A MINIMUM
 HORIZONTAL SLOPE IN THE DIRECTION OF DISCHARGE OF NOT
 LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (1-PERCENT SLOPE). CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A
 NUISANCE.
  
 5. M1602.3BALANCED RETURN AIR.
  
 6. E3901.12 HVAC OUTLET.
  
 7. M1411.8 LOCKING ACCESS PORT CAPS.
  
 8. M1307.2ANCHORAGE OF APPLIANCES.
 THIS DETAIL SHOULD BE SIGNED AND SEALED BY AN ENGINEER
  
 9. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-23 Cont ID  
Sent By cthroop Date 2020-04-23 Time 16:20 Rev Time 0.00
Received By cthroop Date 2020-04-23 Time 15:50 Sent To  
Notes
2020-04-23 16:21:35UNDERGROUNG PLUMBING PER AOR AFFIDAVIT. CT

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By cthroop Date 2020-03-06 Time 14:56 Rev Time 0.00
Received By cthroop Date 2020-03-04 Time 17:11 Sent To  
Notes
2020-03-06 15:05:26PLAN REVIEW - PLUMBING PERMIT # 20021075
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER - BUILDING - PX3169
 PLANS EXAMINER - 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PERMIT REQUIRED FOR WORK OF PREVIOUS OWNER W/O PERMIT
 PER R BROWN
  
 CLASSIFICATION OF WORK SHALL BE ALTERATION LEVEL II
  
 IN ADDITION TO CODES IN EFFECT REFERENCED ABOVE -
 GOVERNING CODES SHALL INCLUDE FBC EXISTING BUILDING
 CHAPT. 8
  
 1. PROVIDE CODE COMPLIANT PLUMBING PLAN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2. PROVIDE PLUMBING RISER DIAGRAHM.
  
 PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION
 107.3.5.3 (12)
  
 3. THE CONTRACTOR OR DESIGNER OF RECORD SHALL PROVIDE A
 TITLE BLOCK AND SIGNATURE ON THE MECHANICAL PLAN SHEET
 - SECTION 107.2.1 WPB. IF THE DESIGNER IS A FL.
 LICENSED ARCHITECT OR ENGINEER, HE/SHE SHALL ALSO
 PROVIDE AN ORIGINAL SEAL AND WET SIGNATURE PER FL.
 STATUE AND SECTIONS 61G15-16.003 AND 23.002 FAC.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-04-24 Cont ID  
Sent By cthroop Date 2020-04-24 Time 14:41 Rev Time 0.00
Received By shill Date 2020-04-24 Time 14:41 Sent To  
Notes
2020-04-24 14:31:53ONE PAPER ORIGINAL RECEIVED VIA DROPOFF BOX, ROUTED TO
 "STORAGE ONLY"
  
  
2020-04-15 16:00:05PAPER SUBMITTAL CONVERTED TO DIGITAL. SIGNATURE AND
 SEAL APPEAR CORRECT. CT