| 2020-02-26 05:56:19 | 1) EXISTING PLANS ON FILE WITH THE CITY SHOW THE |
| | FOLLOWING APPLIANCES ON THE EXISTING GAS SYSTEM. THE |
| | BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO |
| | THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF THE EXISTING APPLIANCES, THE BTU LOAD OF |
| | EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | POOL HEATER - 400,000 BTU'S |
| | WATER HEATER - 35,000 BTU'S |
| | COOKTOP - 30,000 BTU'S |
| | BBQ - 40,000 BTU'S |
| | DRYER - 22,000 BTU'S |
| | 2) THE EXISTING GAS PLAN ON FILE WITH THE CITY SHOWS A |
| | DEVELOPED LENGTH OF 80 FEET TO THE MOST REMOTE OUTLET |
| | ON THE SYSTEM. THIS LENGTH SHALL BE USED FOR THIS |
| | SYSTEM, NOT 30 FEET AS SHOWN ON THE SUBMITTED |
| | RISER.2017 FBC-FUEL GAS SEC. 402.4.1. |
| | 3) THE SUBMITTED GAS SIZING TABLE FOR THE PE PIPE IS |
| | FROM THE 2006 EDITION OF NFPA 54. THE EDITION IN EFFECT |
| | IS THE 2015 EDITION. SUBMIT A COPY OF THE SIZING TABLE |
| | FROM THE CURRENTLY ADOPTED EDITION. NOTE: THE SIZING |
| | TABLE NUMBER HAS CHANGED. IT IS NO LONGER TABLE 6.2 |
| | (S). |
| | 4) THE MINIMUM SIZE PE LINE TO THE GENERATOR SHALL BE 1 |
| | 1/4 INCHES BASED ON THE 80 FEET DEVELOPED LENGTH AND |
| | THE SIZING TABLE. |
| | 5) THE CORRECT TOTAL BTU LOAD ON THE SYSTEM SHALL BE |
| | LISTED ON THE GAS PLANS.WPB AMND. TO FBC SEC. 107.2.1, |
| | 2017 FBC-FUEL GAS SECS.401.8, 402.2 |
| | 6) SHOW THE SIZE AND THE TYPE OF PIPE COMING OFF THE |
| | METER. THIS LINE SHALL BE SIZE FOR THE MAXIMUM DEMAND |
| | ON THE SYSTEM. 2017 FBC-FUEL GAS SEC.402.1. |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | GENERATOR.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SUBMIT AN EXPANDED VIEW OF THE PIPING ARRANGEMENT AT |
| | THE GAS METER.THE GAS RISER APPEARS TO SHOW TWO |
| | SEPARATE LINES ON THE DISCHARGE SIDE OF THE |
| | METER.CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |