Plan Review Details - Permit 20020920
| Plan Review Stops For Permit 20020920 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-07-28 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-28 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-28 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-07-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-07-10 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-07-10 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2020-07-10 09:17:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | ES LICENSE FOR "LIMITED ENERGY SYSTEM SPECIALTY" IS NOT | | | ALLOWED TO WIRE SYSTEMS THAT CONNECT TO THE FIRE ALARM | | | SYSTEM. SEE SCOPE BELOW | | | | | | | | | (4) LIMITED ENERGY SYSTEMS SPECIALTY. THE SCOPE OF | | | CERTIFICATION OF A LIMITED ENERGY SYSTEMS SPECIALTY | | | CONTRACTOR INCLUDES THE INSTALLATION, REPAIR, | | | FABRICATION, ERECTION, ALTERATION, ADDITION TO, OR | | | DESIGN OF ELECTRICAL WIRING, FIXTURES, APPLIANCES, | | | THERMOSTATS, APPARATUS, RACEWAYS, CONDUIT, AND FIBER | | | OPTICS (TRANSMISSION OF LIGHT OVER STRANDED GLASS) OR | | | ANY PART THEREOF NOT TO EXCEED 98 VOLTS, (RMS). THE | | | SCOPE OF WORK OF THIS LICENSE DOES NOT INCLUDE | | | INSTALLATION, REPAIR, FABRICATION, ERECTION, | | | ALTERATION, ADDITION TO, OR DESIGN OF ELECTRICAL | | | WIRING, FIXTURES, APPLIANCES, THERMOSTATS, APPARATUS, | | | RACEWAYS, CONDUIT, THAT ARE PART OF AN ALARM SYSTEM. | | | (A) THE SCOPE OF CERTIFICATION IS LIMITED TO ELECTRICAL | | | CIRCUITS AND EQUIPMENT AS SET FORTH IN SECTION | | | 489.505(7), F.S. | | | (B) THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE WORK | | | PERFORMED BY PUBLIC UTILITIES EXEMPT UNDER THE TERMS OF | | | SECTION 489.503(4), F.S., OR EXEMPT DUE TO THE | | | REGULATORY JURISDICTION OF THE FLORIDA PUBLIC SERVICE | | | COMMISSION. | | | (C) THE SCOPE OF WORK OF THIS LICENSE MAY ALSO BE | | | PERFORMED BY THE FOLLOWING CERTIFIED AND REGISTERED | | | LICENSE CATEGORIES: UNLIMITED ELECTRICAL CONTRACTOR, | | | ALARM SYSTEM CONTRACTOR I, ALARM SYSTEM CONTRACTOR II, | | | AND RESIDENTIAL ELECTRICAL CONTRACTOR. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-03-16 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-03-16 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2020-03-16 09:01:17 | PLEASE SEE F/D NOTE | | 2020-03-04 14:04:23 | SENT TO FIRE TRAVELING WITH 20030146 JLEAHY |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2020-07-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-07-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-07-13 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2020-07-13 10:39:24 | PLAN SHEETS WERE FOUND TO BE ADDED AFTER A TELEPHONE | | | CONVERSATION WITH THE APPLICANT. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2020-03-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2020-03-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2020-03-11 |
Time |
10:44 |
Sent To |
E |
|
| Notes |
| 2020-03-11 11:08:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1A) DOES THE SUBMITTING AND INSTALLING CONTRACTOR HAVE | | | A FCC LICENSE? | | | | | | PLEASE PROVIDE. | | | | | | | | | | | | 1B) THERE IS NO HEAT MAP / COLOR SPECTRUM REPORT OF | | | EACH FLOOR PLAN SHOWING THE AREAS THAT WOULD REQUIRE | | | ENHANCEMENT. | | | | | | 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE | | | PROVIDED | | | THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA | | | AS SPECIFIED | | | IN 24.5.2.2.1 THROUGH 24.5.2.2.3. | | | 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE | | | FIRE COMMAND | | | CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT | | | PASSAGEWAYS, | | | ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER | | | SECTIONAL | | | VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE | | | AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH | | | 99 PERCENT | | | FLOOR AREA RADIO COVERAGE. | | | 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING | | | AREAS | | | SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO | | | COVERAGE. | | | | | | PLEASE PROVIDE A REPORT SHOWING ALL AREAS, THUS | | | DEFENDING THE POSITION OF THE EQUIPMENT | | | | | | | | | 2) THERE IS AN INDICATION OF RUNNING CABLE UP THROUGH | | | EXISTING PENETRATIONS. | | | | | | PLEASE BE SPECIFIC AND IDENTIFY THOSE PENETRATIONS. | | | | | | | | | 3) THERE ARE NO PRODUCT SHEETS INDUCING LISTINGS AND | | | COMBATABILITY. | | | | | | 24.5.2.5.2 COMPONENT ENCLOSURES. ALL REPEATER, | | | TRANSMITTER, RECEIVER, | | | SIGNAL BOOSTER COMPONENTS, AND BATTERY SYSTEM | | | COMPONENTS | | | SHALL BE CONTAINED IN A NEMA4- OR 4X-TYPE ENCLOSURE(S). | | | | | | PLEASE PROVIDE. | | | | | | | | | 4) THERE ARE INDICATIONS OF SPLITTERS AND COAX CABLE AS | | | PLENUM RATED, BUT ARE THEY FIRE RATED? | | | | | | 27.7.1.6 WIRING INSIDE BUILDINGS. | | | 27.7.1.6.1 AT THE COMMUNICATIONS CENTER, ALL | | | CONDUCTORS, | | | CABLES, AND FIBER-OPTIC CABLES SHALL EXTEND AS DIRECTLY | | | AS POSSIBLE | | | TO THE OPERATIONS CENTER IN CONDUITS, DUCTS, SHAFTS, | | | RACEWAYS, | | | OR OVERHEAD RACKS AND TROUGHS LISTED OR IDENTIFIED AS | | | SUITABLE | | | TO PROVIDE PROTECTION AGAINST PHYSICAL DAMAGE. | | | 27.7.1.6.2* WHERE INSTALLED IN BUILDINGS, CONDUCTORS | | | AND | | | FIBER-OPTIC CABLES SHALL BE INSTALLED IN ANY OF THE | | | FOLLOWING WIRING | | | METHODS: | | | (1) ELECTRICAL METALLIC TUBING | | | (2) INTERMEDIATE METAL CONDUIT | | | (3) RIGID METAL CONDUIT | | | EXCEPTION: RIGID NONMETALLIC CONDUIT SHALL BE PERMITTED | | | WHERE APPROVED | | | BY THE AUTHORITY HAVING JURISDICTION. | | | | | | HOW WILL SPLITTERS BE PROTECTED? | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
F |
Date |
2023-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-02-21 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-02-21 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2023-02-21 13:00:52 | THIS APPEARS TO BE A BDA/DAS SYSTEM. PLEASE COORDINATE | | | WITH [email protected] AND MARK FILLA, 561-233-0837, | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-07-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-07-13 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-06-09 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-03-16 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2020-03-16 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2020-02-21 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2020-02-25 10:10:38 | ROUTED TO ELECTRICAL INBOX |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-02-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-02-21 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-02-21 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2023-02-21 08:32:42 | PER FRONT SCREEN NOTES WE ARE IN POSSESSION OF S&S | | | PAPER ORIGINAL | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2020-07-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2020-07-28 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2020-07-28 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2020-07-28 07:52:43 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | DOCUMENTS SUBMITTED ARE SCANNED COPIES OF ORIGINAL | | | SIGNED AND SEALED ENGINEERING. | | | | | | FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | | ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN | | | ORIGINAL. | | | | | | EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED | | | PAPER ORIGINAL WITH A WET SIGNATURE TO: | | | | | | SAMANTHA M. HILL | | | CHIEF PLANS EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | |
|
|
|