Plan Review Details - Permit 20020920
Plan Review Stops For Permit 20020920
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-28 Cont ID  
Sent By jleahy Date 2020-07-28 Time 13:49 Rev Time 0.00
Received By jleahy Date 2020-07-28 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-10 Cont ID  
Sent By jleahy Date 2020-07-10 Time 09:14 Rev Time 0.00
Received By jleahy Date 2020-07-10 Time 09:06 Sent To  
Notes
2020-07-10 09:17:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ES LICENSE FOR "LIMITED ENERGY SYSTEM SPECIALTY" IS NOT
 ALLOWED TO WIRE SYSTEMS THAT CONNECT TO THE FIRE ALARM
 SYSTEM. SEE SCOPE BELOW
  
  
 (4) LIMITED ENERGY SYSTEMS SPECIALTY. THE SCOPE OF
 CERTIFICATION OF A LIMITED ENERGY SYSTEMS SPECIALTY
 CONTRACTOR INCLUDES THE INSTALLATION, REPAIR,
 FABRICATION, ERECTION, ALTERATION, ADDITION TO, OR
 DESIGN OF ELECTRICAL WIRING, FIXTURES, APPLIANCES,
 THERMOSTATS, APPARATUS, RACEWAYS, CONDUIT, AND FIBER
 OPTICS (TRANSMISSION OF LIGHT OVER STRANDED GLASS) OR
 ANY PART THEREOF NOT TO EXCEED 98 VOLTS, (RMS). THE
 SCOPE OF WORK OF THIS LICENSE DOES NOT INCLUDE
 INSTALLATION, REPAIR, FABRICATION, ERECTION,
 ALTERATION, ADDITION TO, OR DESIGN OF ELECTRICAL
 WIRING, FIXTURES, APPLIANCES, THERMOSTATS, APPARATUS,
 RACEWAYS, CONDUIT, THAT ARE PART OF AN ALARM SYSTEM.
 (A) THE SCOPE OF CERTIFICATION IS LIMITED TO ELECTRICAL
 CIRCUITS AND EQUIPMENT AS SET FORTH IN SECTION
 489.505(7), F.S.
 (B) THE SCOPE OF CERTIFICATION SHALL NOT INCLUDE WORK
 PERFORMED BY PUBLIC UTILITIES EXEMPT UNDER THE TERMS OF
 SECTION 489.503(4), F.S., OR EXEMPT DUE TO THE
 REGULATORY JURISDICTION OF THE FLORIDA PUBLIC SERVICE
 COMMISSION.
 (C) THE SCOPE OF WORK OF THIS LICENSE MAY ALSO BE
 PERFORMED BY THE FOLLOWING CERTIFIED AND REGISTERED
 LICENSE CATEGORIES: UNLIMITED ELECTRICAL CONTRACTOR,
 ALARM SYSTEM CONTRACTOR I, ALARM SYSTEM CONTRACTOR II,
 AND RESIDENTIAL ELECTRICAL CONTRACTOR.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By ppetty Date 2020-03-16 Time 09:00 Rev Time 0.00
Received By jleahy Date 2020-03-16 Time 09:00 Sent To  
Notes
2020-03-16 09:01:17PLEASE SEE F/D NOTE
2020-03-04 14:04:23SENT TO FIRE TRAVELING WITH 20030146 JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-07-17 Cont ID  
Sent By pleduc Date 2020-07-17 Time   Rev Time 0.00
Received By pleduc Date 2020-07-13 Time 10:35 Sent To  
Notes
2020-07-13 10:39:24PLAN SHEETS WERE FOUND TO BE ADDED AFTER A TELEPHONE
 CONVERSATION WITH THE APPLICANT.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By pleduc Date 2020-03-11 Time   Rev Time 0.00
Received By pleduc Date 2020-03-11 Time 10:44 Sent To E
Notes
2020-03-11 11:08:05THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1A) DOES THE SUBMITTING AND INSTALLING CONTRACTOR HAVE
 A FCC LICENSE?
  
 PLEASE PROVIDE.
  
  
  
 1B) THERE IS NO HEAT MAP / COLOR SPECTRUM REPORT OF
 EACH FLOOR PLAN SHOWING THE AREAS THAT WOULD REQUIRE
 ENHANCEMENT.
  
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED
 THROUGHOUT THE BUILDING AS A PERCENTAGE OF FLOOR AREA
 AS SPECIFIED
 IN 24.5.2.2.1 THROUGH 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 FIRE COMMAND
 CENTER(S), THE FIRE PUMP ROOM(S), EXIT STAIRS, EXIT
 PASSAGEWAYS,
 ELEVATOR LOBBIES, STANDPIPE CABINETS, SPRINKLER
 SECTIONAL
 VALVE LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT
 FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS
 SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA RADIO
 COVERAGE.
  
 PLEASE PROVIDE A REPORT SHOWING ALL AREAS, THUS
 DEFENDING THE POSITION OF THE EQUIPMENT
  
  
 2) THERE IS AN INDICATION OF RUNNING CABLE UP THROUGH
 EXISTING PENETRATIONS.
  
 PLEASE BE SPECIFIC AND IDENTIFY THOSE PENETRATIONS.
  
  
 3) THERE ARE NO PRODUCT SHEETS INDUCING LISTINGS AND
 COMBATABILITY.
  
 24.5.2.5.2 COMPONENT ENCLOSURES. ALL REPEATER,
 TRANSMITTER, RECEIVER,
 SIGNAL BOOSTER COMPONENTS, AND BATTERY SYSTEM
 COMPONENTS
 SHALL BE CONTAINED IN A NEMA4- OR 4X-TYPE ENCLOSURE(S).
  
 PLEASE PROVIDE.
  
  
 4) THERE ARE INDICATIONS OF SPLITTERS AND COAX CABLE AS
 PLENUM RATED, BUT ARE THEY FIRE RATED?
  
 27.7.1.6 WIRING INSIDE BUILDINGS.
 27.7.1.6.1 AT THE COMMUNICATIONS CENTER, ALL
 CONDUCTORS,
 CABLES, AND FIBER-OPTIC CABLES SHALL EXTEND AS DIRECTLY
 AS POSSIBLE
 TO THE OPERATIONS CENTER IN CONDUITS, DUCTS, SHAFTS,
 RACEWAYS,
 OR OVERHEAD RACKS AND TROUGHS LISTED OR IDENTIFIED AS
 SUITABLE
 TO PROVIDE PROTECTION AGAINST PHYSICAL DAMAGE.
 27.7.1.6.2* WHERE INSTALLED IN BUILDINGS, CONDUCTORS
 AND
 FIBER-OPTIC CABLES SHALL BE INSTALLED IN ANY OF THE
 FOLLOWING WIRING
 METHODS:
 (1) ELECTRICAL METALLIC TUBING
 (2) INTERMEDIATE METAL CONDUIT
 (3) RIGID METAL CONDUIT
 EXCEPTION: RIGID NONMETALLIC CONDUIT SHALL BE PERMITTED
 WHERE APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
  
 HOW WILL SPLITTERS BE PROTECTED?
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status F Date 2023-02-21 Cont ID  
Sent By shill Date 2023-02-21 Time 10:45 Rev Time 0.00
Received By shill Date 2023-02-21 Time 10:45 Sent To  
Notes
2023-02-21 13:00:52THIS APPEARS TO BE A BDA/DAS SYSTEM. PLEASE COORDINATE
 WITH [email protected] AND MARK FILLA, 561-233-0837,
 
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-13 Cont ID  
Sent By lmarchan Date 2020-07-13 Time 10:57 Rev Time 0.00
Received By lmarchan Date 2020-06-09 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-16 Cont ID  
Sent By ppetty Date 2020-03-16 Time 09:01 Rev Time 0.00
Received By ppetty Date 2020-02-21 Time 10:10 Sent To  
Notes
2020-02-25 10:10:38ROUTED TO ELECTRICAL INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-21 Cont ID  
Sent By shill Date 2023-02-21 Time 08:32 Rev Time 0.00
Received By shill Date 2023-02-21 Time 08:32 Sent To  
Notes
2023-02-21 08:32:42PER FRONT SCREEN NOTES WE ARE IN POSSESSION OF S&S
 PAPER ORIGINAL
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-07-28 Cont ID  
Sent By shill Date 2020-07-28 Time 07:51 Rev Time 0.00
Received By shill Date 2020-07-28 Time 07:51 Sent To  
Notes
2020-07-28 07:52:43SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS SUBMITTED ARE SCANNED COPIES OF ORIGINAL
 SIGNED AND SEALED ENGINEERING.
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL ONE ORIGINAL SIGNED AND SEALED