Plan Review Details - Permit 20020883
Plan Review Stops For Permit 20020883
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-09-14 Cont ID  
Sent By fgiaquin Date 2020-09-14 Time 18:36 Rev Time 0.00
Received By fgiaquin Date 2020-09-14 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-07-06 Cont ID  
Sent By fgiaquin Date 2020-07-06 Time 17:55 Rev Time 0.00
Received By fgiaquin Date 2020-07-06 Time 17:06 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-02 Cont ID  
Sent By fgiaquin Date 2020-03-02 Time 07:12 Rev Time 0.00
Received By fgiaquin Date 2020-03-02 Time 06:49 Sent To I
Notes
2020-03-02 06:57:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ENGINEERED DRAWINGS MUST HAVE A WET SIGNATURE ON
 SEAL.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 2. GEC MINIMUM SIZE IS #6 AWG CU FOR A 1/0 SERVICE
 ENTRANCE CONDUCTOR. NEC 250.66
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-09-22 Cont ID  
Sent By lmarchan Date 2020-09-22 Time 16:36 Rev Time 0.00
Received By lmarchan Date 2020-09-01 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-07-06 Cont ID  
Sent By fgiaquin Date 2020-07-06 Time 17:55 Rev Time 0.00
Received By fgiaquin Date 2020-06-19 Time 15:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-02 Cont ID  
Sent By fgiaquin Date 2020-03-02 Time 07:12 Rev Time 0.00
Received By fgiaquin Date 2020-02-20 Time 13:24 Sent To  
Notes
2020-02-21 13:24:41ROUTED TO ELECTRICAL INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-14 Cont ID  
Sent By fgiaquin Date 2020-09-14 Time 18:36 Rev Time 0.00
Received By fgiaquin Date 2020-09-14 Time 18:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-06 Cont ID  
Sent By fgiaquin Date 2020-07-06 Time 17:55 Rev Time 0.00
Received By fgiaquin Date 2020-07-06 Time 17:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By eschneid Date 2020-09-22 Time 10:34 Rev Time 0.25
Received By eschneid Date 2020-09-22 Time 10:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By eschneid Date 2020-07-24 Time 11:53 Rev Time 0.25
Received By eschneid Date 2020-07-24 Time 11:53 Sent To  
Notes
2020-07-24 11:55:12FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE FDOT APPROVAL IF THE SURVEY
 SHOWS THE PROPOSED WIRELESS COMMUNICATION FACILITY IN
 THE RIGHT-OF-WAY.
  
 3) THE PROPOSED WIRELESS FACILITY (POLE) DOES NOT MEET
 THE CITY OF WEST PALM BEACH CONCEALMENT (STEALTH),
 STYLE OR HEIGHT REQUIREMENTS LISTED IN SECTIONS
 78-411(E), 78-411(F) AND 78-411(G) OF THE CITY CODE.
 PROVIDE A POLE THAT MEETS THE CITY CODE REQUIREMENTS.
 NOTE: AT&T HAS SHOWN POLES ON OTHER APPLICATIONS THAT
 MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  