Plan Review Details - Permit 20020861
Plan Review Stops For Permit 20020861
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-24 Cont ID  
Sent By pvalenti Date 2020-02-24 Time 17:27 Rev Time 0.00
Received By pvalenti Date 2020-02-24 Time 17:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-22 Cont ID  
Sent By pvalenti Date 2020-02-22 Time 13:49 Rev Time 0.00
Received By pvalenti Date 2020-02-22 Time 13:48 Sent To  
Notes
2020-02-22 14:30:23***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 3103.1.1, TEMPORARY STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 PLEASE PROVIDE THE FOLLOWING:
  
 1) FBC CHAPTER 16, PROVIDE STRUCTURAL EVALUATION OF
 STRUCTURE SIGNED AND SEALED BY A DESIGN PROFESSIONAL.
  
 2) FBC CHAPTER 10, PROVIDE A LIFE SAFETY PLAN
 A) STATE THE OCCUPANT LOAD
 B) IDENTIFY THE MEANS OF EGRESS
 C) IDENTIFY THE PATH OF TRAVEL
  
 3) FBC A 201.3 IDENTIFY THE ACCESSIBLE ROUTE ON SITE
 PLAN
 4) FBC B 1008.2.1 LIGHTING IS REQUIRED GREATER THAN 1
 FOOT CANDLE
 5) FBC B 1203 VENTILLATION IS REQUIRED
 6) FBC B TABLE 2902.1, PROVIDE ACCESSIBLE PORTABLE
 RESTROOMS/SANITARY FACILITIES PER FBC TABLE 2902.1 IF
 PERMANENT ACCESSIBLE FACILITIES ARE NOT LOCATED WITHIN
 500' OF TENT.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-05 Cont ID  
Sent By jleahy Date 2020-03-05 Time 15:47 Rev Time 0.00
Received By jleahy Date 2020-03-05 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-05 Cont ID  
Sent By jleahy Date 2020-03-03 Time 08:39 Rev Time 0.00
Received By jleahy Date 2020-03-03 Time 08:39 Sent To  
Notes
2020-03-03 08:39:56NEEDS AN ELECTRICAL PERMIT FOR THE LIGHTING. JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-05 Cont ID  
Sent By pleduc Date 2020-03-05 Time   Rev Time 0.00
Received By pleduc Date 2020-03-05 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-05 Cont ID  
Sent By sholder Date 2020-03-05 Time 15:38 Rev Time 0.00
Received By sholder Date 2020-02-22 Time 08:08 Sent To  
Notes
***NONE***