Plan Review Details - Permit 20020853
Plan Review Stops For Permit 20020853
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-27 Cont ID  
Sent By rmcphers Date 2020-04-27 Time 14:45 Rev Time 0.00
Received By rmcphers Date 2020-04-27 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-16 Cont ID  
Sent By rmcphers Date 2020-04-16 Time 15:45 Rev Time 0.00
Received By rmcphers Date 2020-04-16 Time 15:38 Sent To  
Notes
2020-04-16 15:46:04SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE JOB "VALUE" ON THE PERMIT
 APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2020-03-19 Time 15:59 Sent To  
Notes
2020-03-19 16:03:04SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE JOB "VALUE" ON THE PERMIT
 APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-16 Cont ID  
Sent By jpearson Date 2020-04-16 Time 11:00 Rev Time 0.00
Received By jpearson Date 2020-04-16 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By fgiaquin Date 2020-03-06 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2020-03-06 Time 06:47 Sent To I
Notes
2020-03-06 06:51:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO VALUE OR SQUARE FOOTAGE LISTED ON PERMIT
 APPLICATION. FBC 107.2.1
  
 2. NO 120V DISCONNECT WITHIN SIGHT OF SIGN. PROVIDE
 CORRECTION. NEC 600.6A1
  
 3. ASTRONOMICAL TIMECLOCK REQUIRED PER FBC CE 405.2.5
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.5
  
 4. PLANS HAS REFERENCED INCORRECT NEC AND FBC EDITIONS.
 THE CURRENT ADOPTED EDITION OF THE NEC IS 2014, THE
 PLAN HAS 2011 ON IT AND THE CURRENT ADOPTED EDITION OF
 THE FBC IS 2017 AND 2014 IS REFERENCED.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-27 Cont ID  
Sent By rmcphers Date 2020-04-27 Time 14:45 Rev Time 0.00
Received By rmcphers Date 2020-04-24 Time 16:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-24 Cont ID  
Sent By lmarchan Date 2020-04-24 Time 16:07 Rev Time 0.00
Received By lmarchan Date 2020-04-14 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-19 Cont ID  
Sent By rmcphers Date 2020-03-19 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2020-02-20 Time 13:37 Sent To  
Notes
2020-03-19 16:03:57PLANS TAKEN TO PERMIT LIBRARY
2020-03-06 17:46:41ROUTED TO MISC 2 INBOX
2020-02-29 10:19:18ROUTED TO ELECTRICAL INBOX
2020-02-28 15:40:01ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/28/20 EL
2020-02-21 13:37:26ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-04-15 Cont ID  
Sent By shill Date 2020-04-15 Time 12:56 Rev Time 0.00
Received By shill Date 2020-04-15 Time 12:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-14 Cont ID  
Sent By shill Date 2020-04-14 Time 17:51 Rev Time 0.00
Received By shill Date 2020-04-14 Time 17:51 Sent To  
Notes
2020-04-14 17:52:05FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED DATED
 ORIGINALS. SCANS WERE UPLOADED. I'VE EMAILED THE
 ENGINEER REQUESTING ORIGINALS.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-24 Cont ID  
Sent By elevesqu Date 2020-04-24 Time 16:01 Rev Time 0.00
Received By elevesqu Date 2020-04-24 Time 16:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-28 Cont ID  
Sent By elevesqu Date 2020-02-28 Time 15:39 Rev Time 0.00
Received By elevesqu Date 2020-02-28 Time 15:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved