Plan Review Details - Permit 20020821
Plan Review Stops For Permit 20020821
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 12:43 Rev Time 0.00
Received By rmcphers Date 2020-03-10 Time 08:47 Sent To  
Notes
2020-03-11 12:43:33CHANGE OF OCCUPANCY FBC EXISTING BUILDING 1001.2
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) GROUP HOME IS A CHANGE OF OCCUPANCY FROM A SINGLE
 FAMILY HOUSE. FBC EXISTING BUILDING 1012
 2) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3
 3) GROUP HOME FALLS UNDER FBC 310.6 (R-4) - SHOW THE
 REQUIRED SPRINKLER SYSTEM PER FBC 903.2.8
 4) SHOW WHICH APPLIES - - CONDITION 1 OR 2 - - - PER
 FBC 310.6.1
 5) PLEASE SHOW THE OCCUPANT LOAD PER FBC 1004
 6) PLEASE SHOW THE MEANS OF EGRESS - EXIT DOOR SIZES
 AND LOCATIONS. FBC EXISTING BUILDING 1012.4
 7) PLEASE FILL OUT A BUILDING PERMIT APPLICATION (CHECK
 "STRUCTURAL") FOR THE CHANGE OF OCCUPANCY - SHOW IN THE
 "FURTHER WORK DESCRIPTION" ON THE PERMIT APPLICATION
 "CHANGE OF OCCUPANCY FROM ____ TO ___".
 8) PLEASE SHOW SEPARATION WALLS TO COMPLY WITH FBC 420
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-05 Cont ID  
Sent By fgiaquin Date 2020-03-05 Time 06:36 Rev Time 0.00
Received By fgiaquin Date 2020-03-05 Time 06:21 Sent To I
Notes
2020-03-05 06:29:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW (MINIMUM 2 COPIES
 OF PLANS, ONLY ONE SUBMITTED), SIGNED AND SEALED BY A
 LICENSED DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 2. ELECTRICAL CONTRACTOR AND SEPARATE ELECTRICAL PERMIT
 REQUIRED FOR 120V CIRCUIT TO FACP AND SURGE PROTECTOR.
 WHEN RESUBMITTING REFERENCE PERMIT NUMBER OF ELECTRICAL
 PERMIT FOR 120V WIRING. 120V WIRING IS OUT OF SCOPE FOR
 EF LICENSE PER F.S.489.505
  
 3. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE
 VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL.
  
 CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 4. PASS WITH FIRE DEPARTMENT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-04 Cont ID  
Sent By pleduc Date 2020-03-04 Time   Rev Time 0.00
Received By pleduc Date 2020-03-04 Time 11:31 Sent To E
Notes
2020-03-04 11:36:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS INDICATED A LIMITED FIRE ALARM
 SYSTEM THAT IS NOT CODE COMPLINAT.
  
 PER NFPA 101, CH 32 NEW RESIDENTIAL BOARD AND CARE
 OCCUPANCIES
  
 33.2.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 33.2.3.4.1 FIRE ALARM SYSTEMS. A MANUAL FIRE ALARM
 SYSTEM SHALL
 BE PROVIDED IN ACCORDANCE WITH SECTION 9.6, UNLESS THE
 PROVISIONS
 OF 33.2.3.4.1.1 OR 33.2.3.4.1.2 ARE MET.
 33.2.3.4.1.1 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED
 WHERE
 INTERCONNECTED SMOKE ALARMS COMPLYING WITH 33.2.3.4.3
 AND NOT
 LESS THAN ONE MANUAL FIRE ALARM BOX PER FLOOR ARRANGED
 TO
 CONTINUOUSLY SOUND THE SMOKE DETECTOR ALARMS ARE
 PROVIDED.
 33.2.3.4.1.2 OTHER MANUALLY ACTIVATED CONTINUOUSLY
 SOUNDING
 ALARMS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION
 SHALL BE
 PERMITTED IN LIEU OF A FIRE ALARM SYSTEM.
 33.2.3.4.2 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION
 SHALL BE
 IN ACCORDANCE WITH 9.6.3.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS IN A WRITTEN NARRATIVE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-11 Cont ID  
Sent By rmcphers Date 2020-03-11 Time 12:44 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 13:26 Sent To  
Notes
2020-03-11 12:45:57PLANS TAKEN TO PERMIT LIBRARY
2020-03-05 07:32:49ROUTED TO MECHANICAL INBOX
2020-02-20 13:26:13ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-03-10 Cont ID  
Sent By medwards Date 2020-03-10 Time 09:45 Rev Time  
Received By medwards Date   Time   Sent To  
Notes
2020-03-10 09:46:12NO DUCT DETECTORS SHOWN IN THIS SYSTEM.