Plan Review Details - Permit 20020723
Plan Review Stops For Permit 20020723
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-04-03 Cont ID  
Sent By jpearson Date 2020-04-03 Time 16:02 Rev Time 0.00
Received By jpearson Date 2020-04-03 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-04-01 Cont ID  
Sent By jpearson Date 2020-04-01 Time 15:50 Rev Time 0.00
Received By jpearson Date 2020-04-01 Time 15:50 Sent To  
Notes
2020-04-01 15:50:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE REMOVED. PREVIOUS COMMENTS THAT HAVE
 NOT BEEN ADDRESSED SATISFACTORILY HAVE ADDITIONAL
 COMMENTS IN PARENTHESES. ANY NEW COMMENTS WILL BE
 LISTED AFTER PREVIOUS COMMENTS.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1 (NOT PROVIDED.)
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By jpearson Date 2020-03-30 Time 14:17 Rev Time 0.00
Received By jpearson Date 2020-03-30 Time 13:29 Sent To  
Notes
2020-03-30 13:37:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1 (NOT PROVIDED.)
  
 2. ELECTRICAL PERMIT REQUIRED BY LICENSED ELECTRICIAN
 FOR 120V CIRCUIT TO FACP. F.S. 489.505#7 FBC 105.1.
 WHEN RESUBMITTING PLEASE REFERENCE PERMIT NUMBER THAT
 HAS BEEN APPLIED FOR BY THE ELECTRICIAN TO SATISFY THIS
 COMMENT.
  
 NEW COMMENT:
  
 3. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. WPB FBC
 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-22 Cont ID  
Sent By fgiaquin Date 2020-03-22 Time 16:29 Rev Time 0.00
Received By fgiaquin Date 2020-03-21 Time 17:14 Sent To  
Notes
2020-03-22 16:32:00ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. ELECTRICAL PERMIT REQUIRED BY LICENSED ELECTRICIAN
 FOR 120V CIRCUIT TO FACP. F.S. 489.505#7 FBC 105.1.
 WHEN RESUBMITTING PLEASE REFERENCE PERMIT NUMBER THAT
 HAS BEEN APPLIED FOR BY THE ELECTRICIAN TO SATISFY THIS
 COMMENT.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-04-03 Cont ID  
Sent By pleduc Date 2020-04-03 Time   Rev Time 0.00
Received By pleduc Date 2020-04-03 Time 11:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-26 Cont ID  
Sent By pleduc Date 2020-03-26 Time   Rev Time 0.00
Received By pleduc Date 2020-03-26 Time 09:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-03-05 Cont ID  
Sent By pleduc Date 2020-03-05 Time   Rev Time 0.00
Received By pleduc Date 2020-03-05 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-07 Cont ID  
Sent By shill Date 2020-04-07 Time 05:29 Rev Time 0.00
Received By shill Date 2020-04-02 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-04-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-31 Time 08:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-30 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-25 Time 12:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-22 Cont ID  
Sent By fgiaquin Date 2020-03-22 Time 16:32 Rev Time 0.00
Received By fgiaquin Date 2020-03-04 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-06 Cont ID  
Sent By medwards Date 2020-04-06 Time 09:35 Rev Time 0.00
Received By medwards Date 2020-04-06 Time 09:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-27 Cont ID  
Sent By medwards Date 2020-03-27 Time 11:31 Rev Time 0.00
Received By medwards Date 2020-03-27 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-03-20 Cont ID  
Sent By medwards Date 2020-03-20 Time 08:43 Rev Time 0.00
Received By medwards Date 2020-03-20 Time 08:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-04-03 Cont ID  
Sent By jpearson Date 2020-04-03 Time 16:03 Rev Time 0.00
Received By jpearson Date 2020-04-03 Time 16:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-04-01 Cont ID  
Sent By jpearson Date 2020-04-01 Time 15:52 Rev Time 0.00
Received By jpearson Date 2020-04-01 Time 15:52 Sent To  
Notes
2020-04-07 05:29:54PLEASE EMAIL THE DIGITALLY SIGNED PAGE TO [email protected]
  
  
2020-04-01 15:52:27SHEET F-1 IS REQUIRED TO BE DESIGNED AND SIGNED/SEALED
 BY A DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-27 Cont ID  
Sent By medwards Date 2020-03-27 Time 11:33 Rev Time 0.00
Received By medwards Date 2020-03-27 Time 11:33 Sent To  
Notes
2020-03-27 11:34:49SHEET F-1 IS REQUIRED TO BE DESIGNED AND SIGNED/SEALED
 BY A DESIGN PROFESSIONAL OR SIGNED BY THE CONTRACTOR.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-03-22 Cont ID  
Sent By fgiaquin Date 2020-03-22 Time 16:29 Rev Time 0.00
Received By fgiaquin Date 2020-03-22 Time 16:26 Sent To  
Notes
2020-03-22 16:28:59ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1