Plan Review Details - Permit 20020701
Plan Review Stops For Permit 20020701
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-02-29 Cont ID  
Sent By pvalenti Date 2020-02-29 Time 15:05 Rev Time 0.00
Received By pvalenti Date 2020-02-29 Time 15:05 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-19 Cont ID  
Sent By pvalenti Date 2020-02-19 Time 15:25 Rev Time 0.00
Received By pvalenti Date 2020-02-19 Time 15:25 Sent To  
Notes
2020-02-19 15:28:16***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ASBESTOS REQUIREMENTS:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-17 Cont ID  
Sent By pvalenti Date 2020-03-17 Time 08:14 Rev Time 0.00
Received By pvalenti Date 2020-03-17 Time 08:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-19 Cont ID  
Sent By pvalenti Date 2020-02-19 Time 15:37 Rev Time 0.00
Received By pvalenti Date 2020-02-19 Time 15:28 Sent To  
Notes
2020-02-19 15:39:26***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 FBC B 107.2.1 PLEASE PROVIDE NOTES ON PLANS INDICATING
 THAT THE WALLS TO BE REMOVED ARE NON-BEARING AND NON
 FIRE RATED WALLS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-11 Cont ID  
Sent By jleahy Date 2020-03-11 Time 16:37 Rev Time 0.00
Received By jleahy Date 2020-03-11 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-14 Cont ID  
Sent By tklarge Date 2020-03-14 Time 03:15 Rev Time 0.00
Received By tklarge Date 2020-02-18 Time 13:23 Sent To  
Notes
2020-02-19 13:23:26ROUTED TO PVALENTI

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-03-14 Cont ID  
Sent By tklarge Date 2020-03-14 Time 03:14 Rev Time 0.00
Received By tklarge Date 2020-03-14 Time 03:08 Sent To  
Notes
***NONE***