Plan Review Details - Permit 20020699
Plan Review Stops For Permit 20020699
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By rmcphers Date 2020-08-31 Time 08:49 Rev Time 0.00
Received By rmcphers Date 2020-08-31 Time 08:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By rmcphers Date 2020-08-03 Time 12:17 Rev Time 0.00
Received By rmcphers Date 2020-08-03 Time 12:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 10:21 Rev Time 0.00
Received By rmcphers Date 2020-03-06 Time 10:21 Sent To  
Notes
2020-03-06 10:40:33REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107.2.1
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE EXISTING
 LAYOUT NOTING WHAT EACH ROOM IS USED FOR AT THE PRESENT
 TIME.
 2) MARK THE FLOOR PLAN PROVIDED AS "PROPOSED FLOOR
 PLAN" SHOWING THE USE FOR EACH ROOM, THE DIMENSIONS OF
 THE CHANGED OR ADDED ROOMS, ETC..
 3) SHOW ADDED WALL DETAILS.
 4) PLEASE PROVIDE A BUILDING PERMIT APPLICATION FROM A
 CONTRACTOR LICENSED TO PERFORM THE WALL INSTALLATION.
 5) IF CREATING A NEW BEDROOM PLEASE SHOW THE EMERGENCY
 EGRESS TO COMPLY WITH FBC R310.1
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By fgiaquin Date 2020-08-31 Time 20:04 Rev Time 0.00
Received By fgiaquin Date 2020-08-31 Time 20:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-08-01 Cont ID  
Sent By fgiaquin Date 2020-08-01 Time 19:36 Rev Time 0.00
Received By fgiaquin Date 2020-08-01 Time 18:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By jleahy Date 2020-03-06 Time 08:12 Rev Time 0.00
Received By jleahy Date 2020-03-06 Time 08:12 Sent To B
Notes
2020-03-06 08:15:41FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ELECTRIC SHOWN SUBMIT A PLAN SHOWING LOCATIONS OF
 SWITCHES, OUTLETS , LIGHTING, AND LOCATION OF SMOKE
 DETECTORS IN REFERENCE TO THE BATHROOM.
  
 2) PLAN WILL NEED TO BE SIGNED BY ELECTRICAL
 CONTRACTOR.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By lcrespo Date 2020-08-31 Time 10:53 Rev Time 0.00
Received By lcrespo Date 2020-08-31 Time 10:16 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By abelisle Date 2020-08-03 Time 18:35 Rev Time 0.00
Received By abelisle Date 2020-08-03 Time 18:35 Sent To I
Notes
2020-08-03 18:43:138/3/2020 2ND GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 PLEASE ADRESS PREVIOUS PLAN REVIEW COMMENTS.
  
 1. ON THE GAS ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 2. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3.
  
 3. PLEASE SHOW TYPE OF GAS (LP OR NATURAL) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1
  
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE AND UNION SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR PER THE 2017 FBC
 RES. SEC. G2420.4.
  
 6. THERE IS NO DRYER SHOWN ON PLANS OF ELECTRICAL AND
 IF THE DRYER A GAS TYPE PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
  
 8. IF USING METAL LOUVER, PLEASE SHOW THE LOCATION OF
 THE METAL LOUVERS THAT ARE BEING INSTALLED FOR THE
 COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 9. THE PLANS INDICATE A TANKLESS WATER HEATER AND IT IS
 NOT THE ONLY GAS APPLIANCE IN THIS SYSTEM? SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS
  
 10. I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL
 CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 11. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
  
 12. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
  
 13. ALL GAS AS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2017 FBC RES. SEC. G2413.2 AND
 G2404.3.
  
 14. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 15. SHOW THE RELOCATION OF WATER HEATER, SUBMIT TWO
 COPIES OF A HOUSE PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 16. A SEPERATE GAS PERMIT IS REQUIRED
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By lcrespo Date 2020-02-21 Time 18:48 Rev Time 0.00
Received By lcrespo Date 2020-02-21 Time 18:48 Sent To  
Notes
2020-02-21 18:49:3202/21/2020 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE GAS ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
 2. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC FG SEC. 402.3 OR 2017 FBC RES.
 SEC. G2413.3.
 3. PLEASE SHOW TYPE OF GAS (LP OR NATURAL) PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC
 RES. SEC. G2413.4.1
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE AND UNION SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR PER THE 2017 FBC
 RES. SEC. G2420.4.
 6. THERE IS NO DRYER SHOWN ON PLANS OF ELECTRICAL AND
 IF THE DRYER A GAS TYPE PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017
 FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND
 VENTILATION AIR SYSTEM.
 8. IF USING METAL LOUVER, PLEASE SHOW THE LOCATION OF
 THE METAL LOUVERS THAT ARE BEING INSTALLED FOR THE
 COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED PER THE WPB AMENDMENTS TO
 FBC SEC.107.2.1.
 9. THE PLANS INDICATE A TANKLESS WATER HEATER AND IT IS
 NOT THE ONLY GAS APPLIANCE IN THIS SYSTEM? SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 GAS
 10. PLEASE NOTE THERE IS NOT A PERMIT ON FILE FOR
 EXISTING GAS AND IF NOT TO CODE IT MAY REQUIRE TO BE
 BOUGHT UP TO CODE AT OWNER EXPENSE WITH A NEW PERMIT
 AND REVIEW.
 11. THIS TANKLESS UNIT CALL FOR 10.5" WATER COLUMN AND
 THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES.
 SEC. G2421.1.
 12. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1.
 13. ALL GAS AS APPLIANCES SHALL BE LISTED AND LABELED.
 THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2017 FBC RES. SEC. G2413.2 AND
 G2404.3.
 14. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
 15. SHOW THE RELOCATION OF WATER HEATER, SUBMIT TWO
 COPIES OF A HOUSE PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 16. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-31 Cont ID  
Sent By fgiaquin Date 2020-08-31 Time 20:04 Rev Time 0.00
Received By fgiaquin Date 2020-08-25 Time 13:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-06 Cont ID  
Sent By cpuell Date 2020-08-06 Time 13:47 Rev Time 0.00
Received By cpuell Date 2020-07-20 Time 11:18 Sent To  
Notes
2020-07-07 15:19:11ROUTED TO BLDG. MISC 1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-06 Cont ID  
Sent By rmcphers Date 2020-03-06 Time 10:41 Rev Time 0.00
Received By rmcphers Date 2020-02-18 Time 13:25 Sent To  
Notes
2020-03-06 10:42:55PLANS TAKEN TO PERMIT LIBRARY
2020-02-22 07:52:08ROUTED TO MECHANICAL INBOX
2020-02-19 13:25:32ROUTED TO PLUMBING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2020-03-02 Cont ID  
Sent By hmoser Date 2020-03-02 Time 13:20 Rev Time 0.00
Received By hmoser Date 2020-03-02 Time 13:20 Sent To  
Notes
2020-03-02 13:23:01NO MECHANICAL WORK BEING PERFORMED AT THIS TIME. HM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-08-31 Cont ID  
Sent By lcrespo Date 2020-08-31 Time 10:37 Rev Time 0.00
Received By lcrespo Date 2020-08-31 Time 10:16 Sent To  
Notes
2020-08-31 10:37:4408/31/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL,
 CONTRACTORS OR THEIR REPRESENTATIVES FROM THE
 RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By abelisle Date 2020-08-03 Time 18:45 Rev Time 0.00
Received By abelisle Date 2020-08-03 Time 17:57 Sent To I
Notes
2020-08-03 18:51:558/3/2020 PLUMBING 2ND REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 PLEASE ADDRESS PREVIOUS PLAN REVIEW COMMENTS
  
 1. A GAS PERMIT IS REQUIRED FOR BY A LICENSED
 CONTRACTOR PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2. THE SCOPE OF WORK REQUIRES PLAN OF BEFORE AND AFTER
 ALL TRADES, IN THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE PLAN;
 FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; AND
 ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
 FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
  
 3. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. EXISTING AND PROPOSED PLAN DOES NOT SHOW ANY WORK TO
 BE DONE TO THE KITCHEN SINK AND RANGE LOCATIONS. PLEASE
 CLARIFY
  
 5. IF THE MAIN DRAIN LINE TO CITY WILL IT BE CHANGE TO
 PVC AND IF SO PLEASE CLARIFY ON PLANS AND SHOW TWO
 CLEAN OUTS, ONE AT THE EXIT OF BUILDING AND ONE NET IN
 FROM OF TAP (IF NOT ONE THERE FROM CITY LATERAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-21 Cont ID  
Sent By lcrespo Date 2020-02-21 Time 18:43 Rev Time 0.00
Received By lcrespo Date 2020-02-21 Time 18:43 Sent To  
Notes
2020-02-21 18:46:3802/21/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BUILDING PERMIT, MECHANICAL PERMIT AND GAS PERMIT
 IS REQUIRED FOR BY A LICENSED CONTRACTOR PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
 2. THE SCOPE OF WORK REQUIRES PLAN OF BEFORE AND AFTER
 ALL TRADES, IN THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE PLAN;
 FOUNDATION PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS
 LAYOUT; ALL FENESTRATION PENETRATIONS; FLASHING; AND
 ROUGH OPENING DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
 FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 3. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
 4. WASHING MACHINE DRAIN REQUIRES A 3" LINE ON MOST
 MANUFACTURES RECOMMENDATION PLEASE REVISE ISOMETRIC TO
 REFLECT SIZE OF DRAIN LINE PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 5. IF THE MAIN DRAIN LINE TO CITY WILL IT BE CHANGE TO
 PVC AND IF SO PLEASE CLARIFY ON PLANS AND SHOW TWO
 CLEAN OUTS, ONE AT THE EXIT OF BUILDING AND ONE NET IN
 FROM OF TAP (IF NOT ONE THERE FROM CITY LATERAL) PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-07-20 Cont ID  
Sent By pvalenti Date 2020-07-20 Time 09:22 Rev Time 0.00
Received By pvalenti Date 2020-07-20 Time 09:20 Sent To  
Notes
2020-07-20 09:21:48PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW APPROVED THROUGH ORIGINAL PAPER
 SUBMITTALS.